Link to the manufacturers site: TSXDSY08R5A - discrete output module Modicon Premium - 8 O relay
Main
range of product: Modicon Premium Automation platform
product or component type: Discrete output module
discrete output number: 8
discrete output type: Relay protected
discrete output voltage: 24...240 V AC conforming to EN/IEC 61131-2 20...264 V; 24...48 V DC conforming to EN/IEC 61131-2 19...60 V
Complementary
[Ith] conventional free air thermal current: 5 A
response time: < 10 ms (activation); < 15 ms (deactivation)
contacts type and composition: 2 x 2 C/O + 2 x 2 NO
output overvoltage protection: RC circuit and Ge-Mov
output overload protection: 6.3 A, interchangeable fuse per common fast blow
short-circuit protection: 6.3 A, interchangeable fuse per common fast blow
insulation resistance: > 10 MOhm 500 V
power dissipation: (0.25 W + 0.24 W x No of outputs at state 1)
electrical durability: 1000000 cycles DC-12 24 W 24 V resistive; 1000000 cycles DC-12 50 W 48 V resistive; 1000000 cycles DC-3 24 W 24 V inductive; 1000000 cycles DC-3 50 W 48 V inductive; 2000000 cycles DC-3 10 W 24 V inductive; 2000000 cycles DC-3 24 W 48 V inductive; 300000 cycles DC-12 100 W 48 V resistive; 300000 cycles DC-12 50 W 24 V resistive; 100000 cycles AC-14 440 VA 220...240 V inductive; 100000 cycles AC-15 440 VA 220...240 V inductive; 1000000 cycles AC-12 100 VA 48 V resistive; 1000000 cycles AC-12 220 VA 100...120 V resistive; 1000000 cycles AC-12 440 VA 220...240 V resistive; 1000000 cycles AC-14 220 VA 220...240 V inductive; 1000000 cycles AC-15 220 VA 220...240 V inductive; 10000000 cycles AC-14 20 VA 100...120 V inductive; 10000000 cycles AC-15 20 VA 100...120 V inductive; 10000000 cycles AC-15 20 VA 220...240 V inductive; 150000 cycles AC-14 220 VA 100...120 V inductive; 150000 cycles AC-15 220 VA 100...120 V inductive; 1500000 cycles AC-14 110 VA 100...120 V inductive; 1500000 cycles AC-15 110 VA 100...120 V inductive; 2000000 cycles AC-14 50 VA 48 V inductive; 2000000 cycles AC-15 50 VA 48 V inductive; 3000000 cycles AC-14 110 VA 220...240 V inductive; 3000000 cycles AC-15 110 VA 220...240 V inductive; 500000 cycles AC-12 200 VA 48 V resistive; 500000 cycles AC-12 440 VA 100...120 V resistive; 500000 cycles AC-14 50 VA 24 V inductive; 500000 cycles AC-15 50 VA 24 V inductive; 5000000 cycles AC-14 20 VA 48 V inductive; 5000000 cycles AC-15 20 VA 48 V inductive; 700000 cycles AC-12 100 VA 24 V resistive
marking: CE
electrical connection: Screw terminal block
current consumption: 55 mA at 5 V DC; 80 mA at 24 V DC rack
module format: Standard
net weight: 0.42 kg
Environment
dielectric strength: 2000 V 50/60 Hz 60 s
standards: CSA C22.2 No 213 Class I Division 2 Group D; 73/23/EEC; 93/68/EEC; CSA C22.2 No 213 Class I Division 2 Group A; 92/31/EEC; 89/336/EEC; CSA C22.2 No 213 Class I Division 2 Group B; CSA C22.2 No 142; IEC 61131-2; UL 508; CSA C22.2 No 213 Class I Division 2 Group C
product certifications: DNV; LR; ABS; BV; RMRS; GL; RINA
ambient air temperature for operation: 0…60 °C
ambient air temperature for storage: -25…70 °C
relative humidity: 10…95 % without condensation for operation; 5…95 % without condensation for storage
operating altitude: 0...2000 m
protective treatment: TC
IP degree of protection: IP20
pollution degree: 2