Schneider-Electric
RM35TF30
Tariff code: 8536490099
Link to the manufacturers site: RM35TF30 - multifunction phase control relay RM35-T - range 194..528 V AC
Main
Range of produc: Harmony Control Relays
Relay type: Multifunction control relay
Product or component type: 3-phase control relay
Product specific application: For 3-phase supply
Relay name: RM35TF
Relay monitored parameters: Undervoltage and overvoltage in window mode; Phase sequence; Phase failure detection; Asymmetry
Time delay type: Adjustable 0.1...10 s, +/- 10 % of the full scale value
Switching capacity in VA: 1250 VA
Measurement range: 220...480 V voltage AC
Contacts type and composition: 2 C/O
Connections - terminals: Screw connectors
[Uc] control circuit voltage: 220...480 V
[In] rated current: 5 A
Complementary
Reset time: 1500 ms at 480 V
Maximum switching voltage: 250 V AC; 250 V DC
Minimum switching current: 10 mA at 5 V DC
Maximum switching current: 5 A AC; 5 A DC
Supply voltage limits: 194…528 V AC, 3 phases
Control circuit voltage limits: - 12 % + 10 % Un
Power consumption in VA: 0…22 VA at 400 V AC 50 Hz
Voltage detection threshold: < 194 V
control circuit frequency: 50...60 Hz +/- 10 %
Output contacts: 2 C/O
Nominal output current: 5 A
Measurement voltage limits: 176…528 V AC
Hysteresis: 2 %
run-up delay at power-up: 650 ms
Maximum measuring cycle: 140 ms measurement cycle as true rms value
Threshold adjustment voltage: 2...20 % of Un selected; -12...-2 % in the range 220 V AC; +2...+10 % in the range 480 V AC
Voltage range: 220...480 V phase to phase
Adjustment of asymmetry threshold: 5...15 % of Un selected
Repeat accuracy: 0.3 % for time delay; 0.5 % for input and measurement circuit
Measurement error: < 1 % over the whole range with voltage variation; 0.05 %/°C with temperature variation
Response time: < 200 ms (in the event of a fault)
Marking: CE
Overvoltage category: III conforming to IEC 60664-1
Insulation resistance: > 500 MOhm at 500 V DC conforming to IEC 60255-5; > 500 MOhm at 500 V DC conforming to IEC 60664-1
[Ui] rated insulation voltage: 400 V conforming to IEC 60664-1
Supply frequency: 50/60 Hz +/- 10 %
Operating position: Any position without derating
Connections - terminals: Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end; Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end; Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end; Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
Tightening torque: 0.6…1 N.m conforming to IEC 60947-1
Housing material: Self-extinguishing plastic
Local signalling: LED (green) for power ON; LED (yellow) for relay ON; LED (yellow) for fault
Mounting support: 35 mm symmetrical DIN rail conforming to IEC 60715
Electrical durability: 100000 cycles
Mechanical durability: 30000000 cycles
Operating rate: <= 360 operations/hour full load
Utilisation category: AC-12 conforming to IEC 60947-5-1; AC-13 conforming to IEC 60947-5-1; AC-14 conforming to IEC 60947-5-1; AC-15 conforming to IEC 60947-5-1; DC-12 conforming to IEC 60947-5-1; DC-13 conforming to IEC 60947-5-1
Safety reliability data: MTTFd = 399.5 years; B10d = 360000
Width: 35 mm
Net weight: 0.13 kg
Compatibility code: RM3
Environment
Electromagnetic compatibility: Emission standard for industrial environments conforming to IEC 61000-6-4; Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3; Immunity for industrial environments conforming to IEC 61000-6-2
Standards: IEC 60255-1
product certifications: GL; UL; CSA; GOST; C-Tick
Directives: 89/336/EEC - electromagnetic compatibility; 73/23/EEC - low voltage directive
Ambient air temperature for storage: -40…70 °C
Ambient air temperature for operation: -20…50 °C
Relative humidity: 95 % at 55 °C conforming to IEC 60068-2-30
Vibration resistance: 0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6; 1 gn (f= 57.6…150 Hz) conforming to IEC 60255-21-1
Shock resistance: 15 gn for 11 ms conforming to IEC 60255-21-1
IP degree of protection: IP20 (terminals) conforming to IEC 60529; IP30 (casing) conforming to IEC 60529
Pollution degree: 3 conforming to IEC 60664-1
Dielectric test voltage: 2 kV, 1 min AC 50 Hz
Non-dissipating shock wave: 4 kV
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 4.800 cm
Package 1 Width: 7.800 cm
Package 1 Length: 9.700 cm
Package 1 Weight: 133.000 g
Unit Type of Package 2: S03
Number of Units in Package 2: 48
Package 2 Height: 30.000 cm
Package 2 Width: 30.000 cm
Package 2 Length: 40.000 cm
Package 2 Weight: 7.070 kg
Unit Type of Package 3: P06
Number of Units in Package 3: 384
Package 3 Height: 75.000 cm
Package 3 Width: 60.000 cm
Package 3 Length: 80.000 cm
Package 3 Weight: 64.124 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free: Yes
China RoHS Regulation: X
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP1504008EN
Circularity Profile: ENVEOLI1504008EN
© 2018 Alplan Kft.