Schneider-Electric
LV431867
Tariff code: 8536209090
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: LV431867 - circuit breaker Compact NSX250F, 36 kA at 415 VAC, Micrologic 5.2 A trip unit 100 A, 4 poles 4d
Main
range: ComPact
product name: ComPact NSX
range of product: ComPact NSX100...250
device short name: NSX250F
product or component type: Circuit breaker
device application: Distribution
poles description: 4P
protected poles description: 3t + N/2; 3t; 4t
neutral position: Left
[In] rated current: 100 A at 40 °C
[Ue] rated operational voltage: 690 V AC 50/60 Hz
network type: AC
network frequency: 50/60 Hz
suitability for isolation: Yes conforming to EN/IEC 60947-2
utilisation category: Category A
breaking capacity: 85 kA at 240 V AC 50/60 Hz conforming to UL 508; 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2; 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2; 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 35 kA at 480 V AC 50/60 Hz conforming to UL 508; 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 15 kA at 600 V AC 50/60 Hz conforming to UL 508
Breaking capacity code: F 36 kA 415 V AC
trip unit name: Micrologic 5.2 A
trip unit technology: Electronic
trip unit protection functions: LSI
control type: Toggle
mounting mode: Fixed
Complementary
[Ui] rated insulation voltage: 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage: 8 kV
[Ics] rated service breaking capacity: 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2; 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2; 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2; 8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
mechanical durability: 20000 cycles
electrical durability: 5000 cycles at 690 V In; 10000 cycles at 690 V In/2; 10000 cycles at 440 V In; 20000 cycles at 440 V In/2
mounting support: Backplate
upside connection: Front
downside connection: Front
connection pitch: 35 mm
protection type: L : for overload protection (long time); S : for short time short-circuit protection; I : for instantaneous short-circuit protection
trip unit rating: 100 A at 40 °C
long time pick-up adjustment type Ir: Adjustable
long time pick-up adjustment range: 40...100 A
long time delay adjustment type: Adjustable
[tr] long-time delay adjustment range: 15…400 s at 1.5 x Ir; 0.35…11 s at 7.2 x Ir; 0.5…16 s at 6 x Ir
thermal memory: 20 minutes before and after tripping
short-time pick-up adjustment type Isd: Adjustable
[Isd] short-time pick-up adjustment range: 1.5...10 x Ir
short-time delay adjustment type: Adjustable
[tsd] short-time delay adjustment range: 0…0.4 s
instantaneous pick-up adjustment type Ii: Adjustable
instantaneous pick-up adjustment range: 1.5...12 x In
earth-leakage protection: Without
neutral protection setting: 0.5 x Ir (3t + N/2); 1 x Ir (4t); 1.6 x Ir (3t + OSN); No protection (3t)
zone selective interlocking ZSI: With
number of slots: 5 slot(s)
local signalling: Flashing LED (green) for ready to operate; LED 105 % Ir (red) for overload; LED 90 % Ir (orange) for overload
display type: LCD display
type of measurement: Ammeter
communication of data: Instantaneous and demand values; Energy metering; Time-stamped histories and event tables; Power quality; Protection and alarm settings; Maintenance indicators; Maximeters/minimeters; Demand current and power
width: 140 mm
height: 161 mm
depth: 86 mm
net weight: 2.8 kg
compatibility code: NSX250
Environment
standards: EN/IEC 60947
product certifications: CCC; EAC; Marine
overvoltage category: Class II
electrical shock protection class: Class II
pollution degree: 3 conforming to IEC 60664-1
IP degree of protection: IP40 conforming to IEC 60529
IK degree of protection: IK07 conforming to IEC 62262
ambient air temperature for operation: -25…70 °C
ambient air temperature for storage: -40…85 °C
relative humidity: 0…95 %
operating altitude: 0...2000 m without derating; 2000 m...5000 m with derating
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Free of Substances of Very High Concern above the threshold
EU RoHS Directive: Compliant
Mercury free: Yes
RoHS exemption information: Yes
China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure: ENVPEP120606EN
Circularity Profile: ENVEOLI120604EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
© 2018 Alplan Kft.