motor controller LTMR TeSys T - 100..240 V AC 8 A for CANopen
Barcode: 3389119404693
Tariff code:

This product is discontinued.

Please contact us for possible replacement product options.

Link to the manufacturers site: LTMR08CFM - motor controller LTMR TeSys T - 100..240 V AC 8 A for CANopen

Main

range: TeSys

product name: TeSys T

device short name: LTMR

product or component type: Motor controller

device application: Equipment monitoring and control

measurement current: 0.4…8 A

[Us] rated supply voltage: 100...240 V AC 50/60 Hz

current consumption: 8...62.8 mA

supply voltage limits: 93.5…264 V AC

communication port protocol: CANopen

bus type: CANopen ISO 1198 interface, addressing 1...127, transmission rate 10...1000 kbit/s, SUB-D 9 with 4 twisted shielded pairs cable; CANopen ISO 1198 interface, addressing 1...127, transmission rate 10...1000 kbit/s, terminal block with 4 twisted shielded pairs cable

Complementary

[Ui] rated insulation voltage: 690 V conforming to EN/IEC 60947-1; 690 V conforming to CSA C22.2 No 14; 690 V conforming to UL 508

[Uimp] rated impulse withstand voltage: 4 kV supply, inputs and outputs conforming to EN/IEC 60947-4-1; 6 kV current or voltage measurement circuit conforming to EN/IEC 60947-4-1; 0.8 kV communication circuit conforming to EN/IEC 60947-4-1

short-circuit withstand: 100 kA conforming to EN/IEC 60947-4-1

associated fuse rating: 4 A gG for output; 0.5 A gG for control circuit

protection type: Power factor variation; Reverse polarity protection; Thermal protection; Phase failure; Load fluctuation; Overload; Phase unbalance; Thermal overload protection; Overload (long time); Locked rotor; Earth-leakage protection

network and machine diagnosis type: Event recording; Trip history information; Phase fault and earth fault trip counters; Trip context information; Waiting time after overload tripping; Remaining operating time before overload tripping; Running hours counter/operating time; Motor control command recording; Starting current and time; Fault recording

logic input number: 6

input current: 3.1 mA at 100 V; 7.5 mA at 240 V

current state 0 guaranteed: Logic input: 0...40 V and <= 15 mA for 25 ms

current state 1 guaranteed: Logic input: 79...264 V and >= 2 mA for 25 ms

maximum operating frequency: 2 Hz

load current: 5 A at 250 V AC for logic output; 5 A at 30 V DC for logic output

permissible power: 480 VA (AC-15), Ie = 2 A, 500000 cycles (output); 30 W (DC-13), Ie = 1.25 A, 500000 cycles (output)

maximum operating rate: 1800 cyc/h

contacts type and composition: 1 NO + 1 NC fault signal; 3 NO

metering type: Temperature; Phase current I1, I2, I3 RMS; Imbalance current; Average current Iavg; Earth-fault current

measurement accuracy: 5...15 % earth fault current internal measurement; 1 % voltage (100...830 V); 3 % power factor; 5 % earth fault current external measurement; +/- 30 min/year internal clock; 0,02 temperature; 1 % current; 5 % active and reactive power

overvoltage category: III

connection pitch: 5.08 mm

connections - terminals: Control circuit: connector 1 cable(s) 0.25…2.5 mm² (AWG 24...AWG 14) flexible with cable end; Control circuit: connector 1 cable(s) 0.2…2.5 mm² (AWG 24...AWG 14) flexible without cable end; Control circuit: connector 1 cable(s) 0.25…2.5 mm² (AWG 24...AWG 14) flexible without cable end; Control circuit: connector 1 cable(s) 0.2…2.5 mm² (AWG 24...AWG 14) solid without cable end; Control circuit: connector 2 cable(s) 0.2…1 mm² (AWG 24...AWG 14) flexible with cable end; Control circuit: connector 2 cable(s) 0.2…1.5 mm² (AWG 24...AWG 14) flexible without cable end; Control circuit: connector 2 cable(s) 0.5…1.5 mm² (AWG 24...AWG 14) flexible without cable end; Control circuit: connector 2 cable(s) 0.2…1 mm² (AWG 24...AWG 14) solid without cable end

tightening torque: Control circuit: 0.5…0.6 N.m flat screwdriver 3 mm

pollution degree: 3

electromagnetic compatibility: Electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2; Radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3; Fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4; Fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4; Voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11; Conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6; Temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5; Temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5; Control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5; Communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5; Relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5; Relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5; Control circuit: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5

width: 91 mm

height: 61 mm

depth: 122.5 mm

net weight: 0.53 kg

web services: Web server

compatibility code: LTMR

Environment

standards: IACS E10; CSA C22.2 No 14; UL 508; EN 60947-4-1; IEC 60947-4-1

product certifications: BV; GL; EAC; ATEX; KERI; CCC; ABS; C-Tick; CSA; DNV; UL; RMRoS; NOM; LROS (Lloyds register of shipping); RINA

protective treatment: 12 x 24 hour cycles conforming to EN/IEC 60068-2-30; 48 h conforming to EN/IEC 60070-2-11; TH conforming to EN/IEC 60068

fire resistance: 650 °C conforming to EN/IEC 60695-2-12; 960 °C conforming to UL 94

ambient air temperature for operation: -20…60 °C

ambient air temperature for storage: -40…80 °C

operating altitude: <= 2000 m without derating

mechanical robustness: Vibrations mounted on symmetrical rail: 1 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6; Vibrations plate mounted: 4 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6; Shocks half sine wave acceleration: 15 Gn for 11 ms conforming to EN/IEC 60068-2-27

IP degree of protection: IP20

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Free of Substances of Very High Concern above the threshold

EU RoHS Directive: Compliant

Mercury free: Yes

RoHS exemption information: Yes

China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure: ENVPEP060308EN_V2

Circularity Profile: ENVEOLI100411EN_V2

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

PVC free: Yes

Halogen content performance: Halogen free plastic parts product