Schneider-Electric
LC1F400FD
Tariff code:
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: LC1F400FD - TeSys F contactor - 3P (3 NO) - AC-3 - <= 440 V 400 A - coil 110 V DC
Main
range of product: TeSys F
range: TeSys
product name: TeSys F
product or component type: Contactor
device short name: LC1F
contactor application: Motor control; Resistive load
utilisation category: AC-3; AC-1; AC-4
poles description: 3P
pole contact composition: 3 NO
[Ie] rated operational current: 500 A (at <40 °C) at <= 440 V AC AC-1; 400 A (at <55 °C) at <= 440 V AC AC-3
motor power kW: 75 kW at 400 V AC 50/60 Hz (AC-4); 200 kW at 380...400 V AC 50/60 Hz (AC-3); 220 kW at 415 V AC 50/60 Hz (AC-3); 250 kW at 440 V AC 50/60 Hz (AC-3); 257 kW at 500 V AC 50/60 Hz (AC-3); 280 kW at 660...690 V AC 50/60 Hz (AC-3); 185 kW at 1000 V AC 50/60 Hz (AC-3); 110 kW at 220...230 V AC 50/60 Hz (AC-3)
control circuit type: DC standard
[Uc] control circuit voltage: 110 V DC
coil type: Standard
Complementary
[Uimp] rated impulse withstand voltage: 8 kV
overvoltage category: III
[Ith] conventional free air thermal current: 500 A (at 40 °C)
rated breaking capacity: 3200 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current: 3600 A 40 °C - 10 s; 2400 A 40 °C - 30 s; 1700 A 40 °C - 1 min; 1200 A 40 °C - 3 min; 1000 A 40 °C - 10 min
associated fuse rating: 400 A aM at <= 440 V; 500 A gG at <= 440 V
average impedance: 0.26 mOhm - Ith 500 A 50 Hz
[Ui] rated insulation voltage: 1000 V conforming to IEC 60947-4-1; 1500 V conforming to VDE 0110 group C
power dissipation per pole: 65 W AC-1; 42 W AC-3
mounting support: Plate
standards: IEC 60947-4-1; JIS C8201-4-1; EN 60947-4-1; EN 60947-1; IEC 60947-1
product certifications: UL; CSA; CB; ABS; BV; DNV; LROS (Lloyds register of shipping); RMRoS; RINA; UKCA
connections - terminals: Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end; Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end; Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end; Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end; Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end; Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end; Power circuit: bar 2 cable(s) - busbar cross section: 30 x 5 mm; Power circuit: lugs-ring terminals 2 cable(s) 150 mm²; Power circuit: bolted connection
tightening torque: Control circuit: 1.2 N.m; Power circuit: 35 N.m
control circuit voltage limits: Operational: 0.85...1.1 Uc (at 55 °C); Drop-out: 0.2...0.35 Uc (at 55 °C)
inrush power in W: 1000 W (at 20 °C)
hold-in power consumption in W: 6 W at 20 °C
heat dissipation: 6 W
operating time: 50...60 ms closing; 45...60 ms opening
mechanical durability: 10 Mcycles
maximum operating rate: 2400 cyc/h 55 °C
compatibility code: LC1F
power range: 110…220 kW at 480…500 V 3 phases; 110…220 kW at 380…440 V 3 phases; 110…220 kW at 200…240 V 3 phases; 250…500 kW at 480…500 V 3 phases
motor starter type: Direct on-line contactor
contactor coil voltage: 110 V DC standard
Environment
IP degree of protection: IP20 front face with shrouds conforming to IEC 60529; IP20 front face with shrouds conforming to VDE 0106
protective treatment: TH
ambient air temperature for operation: -5…55 °C
ambient air temperature for storage: -60…80 °C
permissible ambient air temperature around the device: -40…70 °C
operating altitude: 3000 m without derating
height: 206 mm
width: 213 mm
depth: 219 mm
net weight: 9.1 kg
Offer Sustainability
REACh Regulation: Free of Substances of Very High Concern above the threshold
EU RoHS Directive: Compliant
Mercury free: Yes
RoHS exemption information: Yes
China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins