Schneider-Electric
LC1D50AY7
Tariff code:
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: LC1D50AY7 - TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 50 A - 690 V AC 50/60 Hz coil
Main
range of product: TeSys D
range: TeSys
product name: TeSys D
product or component type: Contactor
device short name: LC1D
contactor application: Motor control; Resistive load
utilisation category: AC-4; AC-1; AC-3
poles description: 3P
pole contact composition: 3 NO
[Ue] rated operational voltage: Power circuit: <= 690 V AC 25...400 Hz; Power circuit: <= 300 V DC
[Ie] rated operational current: 50 A (at <60 °C) at <= 440 V AC AC-3 for power circuit; 80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
motor power kW: 15 kW at 220...230 V AC 50/60 Hz (AC-3); 22 kW at 380...400 V AC 50/60 Hz (AC-3); 30 kW at 500 V AC 50/60 Hz (AC-3); 33 kW at 660...690 V AC 50/60 Hz (AC-3); 25 kW at 415 V AC 50/60 Hz (AC-3); 30 kW at 440 V AC 50/60 Hz (AC-3); 11 kW at 400 V AC 50/60 Hz (AC-4)
motor power hp: 3 hp at 115 V AC 50/60 Hz for 1 phase motors; 7.5 hp at 230/240 V AC 50/60 Hz for 1 phase motors; 15 hp at 200/208 V AC 50/60 Hz for 3 phases motors; 15 hp at 230/240 V AC 50/60 Hz for 3 phases motors; 40 hp at 460/480 V AC 50/60 Hz for 3 phases motors; 40 hp at 575/600 V AC 50/60 Hz for 3 phases motors
control circuit type: AC at 50/60 Hz
[Uc] control circuit voltage: 690 V AC 50/60 Hz
auxiliary contact composition: 1 NO + 1 NC
[Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947
overvoltage category: III
[Ith] conventional free air thermal current: 10 A (at 60 °C) for signalling circuit; 80 A (at 60 °C) for power circuit
Irms rated making capacity: 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 900 A at 440 V for power circuit conforming to IEC 60947
rated breaking capacity: 900 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current: 400 A 40 °C - 10 s for power circuit; 810 A 40 °C - 1 s for power circuit; 84 A 40 °C - 10 min for power circuit; 208 A 40 °C - 1 min for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit
associated fuse rating: 10 A gG for signalling circuit conforming to IEC 60947-5-1; 100 A gG at <= 690 V coordination type 1 for power circuit; 100 A gG at <= 690 V coordination type 2 for power circuit
average impedance: 1.5 mOhm - Ith 80 A 50 Hz for power circuit
[Ui] rated insulation voltage: Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified; Power circuit: 690 V conforming to IEC 60947-4-1
electrical durability: 1.45 Mcycles 50 A AC-3 at Ue <= 440 V; 1.1 Mcycles 80 A AC-1 at Ue <= 440 V
power dissipation per pole: 3.7 W AC-3; 9.6 W AC-1
protective cover: With
mounting support: Plate; Rail
standards: CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 508
product certifications: CSA; UL; RINA; BV; CCC; DNV; GOST; LROS (Lloyds register of shipping); GL
connections - terminals: Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end; Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end; Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end; Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end; Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end; Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end; Power circuit: EverLink BTR screw connectors 1 cable(s) 1…35 mm²flexible without cable end; Power circuit: EverLink BTR screw connectors 2 cable(s) 1…25 mm²flexible without cable end; Power circuit: EverLink BTR screw connectors 1 cable(s) 1…35 mm²flexible with cable end; Power circuit: EverLink BTR screw connectors 2 cable(s) 1…25 mm²flexible with cable end; Power circuit: EverLink BTR screw connectors 1 cable(s) 1…35 mm²solid without cable end; Power circuit: EverLink BTR screw connectors 2 cable(s) 1…25 mm²solid without cable end
tightening torque: Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2; Power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25…35 mm² hexagonal screw head 4 mm; Power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1…25 mm² hexagonal screw head 4 mm
operating time: 4...19 ms opening; 12...26 ms closing
safety reliability level: B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
mechanical durability: 6 Mcycles
maximum operating rate: 3600 cyc/h 60 °C
Complementary
coil technology: Without built-in suppressor module
control circuit voltage limits: 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz; 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
inrush power in VA: 140 VA 60 Hz cos phi 0.75 (at 20 °C); 160 VA 50 Hz cos phi 0.75 (at 20 °C)
hold-in power consumption in VA: 13 VA 60 Hz cos phi 0.3 (at 20 °C); 15 VA 50 Hz cos phi 0.3 (at 20 °C)
heat dissipation: 4…5 W at 50/60 Hz
auxiliary contacts type: type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1
signalling circuit frequency: 25...400 Hz
minimum switching current: 5 mA for signalling circuit
minimum switching voltage: 17 V for signalling circuit
non-overlap time: 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact
insulation resistance: > 10 MOhm for signalling circuit
contact compatibility: M2
compatibility code: LC1D
Environment
IP degree of protection: IP20 front face conforming to IEC 60529
protective treatment: TH conforming to IEC 60068-2-30
pollution degree: 3
ambient air temperature for operation: -40…60 °C; 60…70 °C with derating
ambient air temperature for storage: -60…80 °C
operating altitude: 0...3000 m
fire resistance: 850 °C conforming to IEC 60695-2-1
flame retardance: V1 conforming to UL 94
mechanical robustness: Vibrations contactor open: 2 Gn, 5...300 Hz; Vibrations contactor closed: 4 Gn, 5...300 Hz; Shocks contactor closed: 15 Gn for 11 ms; Shocks contactor open: 10 Gn for 11 ms
height: 122 mm
width: 55 mm
depth: 120 mm
net weight: 0.855 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Free of Substances of Very High Concern above the threshold
REACh free of SVHC: Yes
EU RoHS Directive: Compliant
Toxic heavy metal free: Yes
Mercury free: Yes
RoHS exemption information: Yes
China RoHS Regulation: Pro-active China RoHS declaration (out of China RoHS legal scope)
Environmental Disclosure: ENVPEP1503009EN
Circularity Profile: ENVEOLI1503009EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
PVC free: Yes
© 2018 Alplan Kft.