Skip to main content

Schneider-Electric
XMLDM02V1S11

vacuum switch XMLD -1 bar - 2 stages fixed scale - 2 C/O
Barcode: 3389110944150
Tariff code: 9032810000

This product is discontinued.

Please contact us for possible replacement product options.

Link to the manufacturers site: XMLDM02V1S11 - vacuum switch XMLD -1 bar - 2 stages fixed scale - 2 C/O

Main

Range of produc: Telemecanique Pressure sensors XM

Product or component type: Electromechanical pressure sensor

Pressure sensor type: Electromechanical vacuum sensor

Device short name: XMLD

Pressure rating: -1 bar

Controlled fluid: Air (0…70 °C); Fresh water (0…70 °C); Hydraulic oil (0…70 °C)

Fluid connection type: G 1/4 (female) conforming to ISO 228

Electrical connection: Screw-clamps terminals, 1 x 0.5...2 x 2.5 mm²

AWG gauge: AWG 20...AWG 14

Cable entry: Cable gland 9…13 mm

Contacts type and composition: 2 C/O snap action, silver contacts; 2 C/O staggered, silver contacts

Product specific application: Dual stage

Pressure switch type of operation: Detection of 2 single thresholds

Electrical circuit type: Control circuit

Scale type: Fixed differential

Local display: Without

Maximum permissible accidental pressure: 9 bar

Destruction pressure: 18 bar

Pressure actuator: Diaphragm

Materials in contact with fluid: Zinc alloy; Nitrile; 304L stainless steel

Enclosure material: Zinc alloy

[In] rated current: 3 A, B300, AC-15 (Ue = 120 V) conforming to EN/IEC 60947-5-1; 1.5 A, B300, AC-15 (Ue = 240 V) conforming to EN/IEC 60947-5-1; 0.1 A, R300, DC-13 (Ue = 250 V) conforming to EN/IEC 60947-5-1

Complementary

Spread between 2 stages: 0.02…0.88 bar

Natural differential at low setting: 0.1 bar

Natural differential at high setting: 0.1 bar

Maximum permissible pressure - per cycle: 5 bar

Terminal block type: 8 terminals

Maximum operating rate: 120 cyc/mn

Repeat accuracy: 2 %

[Ui] rated insulation voltage: 300 V conforming to UL 508; 500 V conforming to EN/IEC 60947-1; 300 V conforming to CSA C22.2 No 14

[Uimp] rated impulse withstand voltage: 6 kV conforming to EN/IEC 60947-1

Maximum resistance across terminals: 25 mOhm conforming to IEC 255-7 category 3; 25 mOhm conforming to NF C 93-050 method A

Short-circuit protection: 10 A cartridge fuse, type gG (gl)

Mechanical durability: 3000000 cycles

Setting: External

Terminals description ISO n°1: (13-14-11-12)OF

Terminals description ISO n°2: (23-24-21-22)OF

height: 158 mm

Depth: 90 mm

Width: 55 mm

Net weight: 1.015 kg

Environment

Standards: CE; CSA C22.2 No 14; EN/IEC 60947-5-1; UL 508

product certifications: CSA; UL; EAC

Protective treatment: TC standard version

ambient air temperature for operation: -25…70 °C

Ambient air temperature for storage: -40…70 °C

Operating position: Any position

Vibration resistance: 4 gn conforming to IEC 60068-2-6 (f = 30…500 Hz)

Shock resistance: 50 gn conforming to IEC 60068-2-27

Electrical shock protection class: Class I conforming to IEC 1140; Class I conforming to IEC 536; Class I conforming to NF C 20-030

IP degree of protection: IP66 conforming to EN/IEC 60529

Packing Units

Unit Type of Package 1: PCE

Number of Units in Package 1: 1

Package 1 Height: 6.0 cm

Package 1 Width: 10.5 cm

Package 1 Length: 14.0 cm

Package 1 Weight: 1.05 kg

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)

Mercury free: Yes

RoHS exemption information: Yes

Environmental Disclosure: ENVPEP110914EN

Circularity Profile: N/A

© 2018 Alplan Kft.