Schneider-Electric
LV481433
Tariff code: 8536508090
Link to the manufacturers site: LV481433 - FuPact GS SDF 250A 3P DIN 1 F&R CTRL
Main
Range: FuPacT
Product name: FuPacT GS
Device short name: GSD250
Product or component type: Switch-disconnector-fuse
Device application: Equipment protection, monitoring and control; Distribution
Poles description: 3P
Number of fuse carriers: 3
Fuse type: DIN
Fuse size: NH1
Suitability for isolation: Yes conforming to EN/IEC 60947-3
Visible break: No
Contact position indicator: Yes
[Ith] conventional free air thermal current: 250 A ( 35 °C ) power dissipation per fuse: 23 W
[Ithe] conventional enclosed thermal current: 250 A at 35 °C, Power dissipation per fuse: 23 W
maximum power dissipation per pole: 19 W
[Ue] rated operational voltage: 690 V AC 50/60 Hz; 800 V AC 50/60 Hz AC-20
[Ui] rated insulation voltage: 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage: 8 kV
[Ie] rated operational current: AC-22A: 250 A at 220/240 V AC 50/60 Hz; AC-23A: 250 A at 220/240 V AC 50/60 Hz; AC-22B: 250 A at 220/240 V AC 50/60 Hz; AC-23B: 250 A at 220/240 V AC 50/60 Hz; AC-22A: 250 A at 380/415 V AC 50/60 Hz; AC-23A: 250 A at 380/415 V AC 50/60 Hz; AC-22B: 250 A at 380/415 V AC 50/60 Hz; AC-23B: 250 A at 380/415 V AC 50/60 Hz; AC-22A: 250 A at 660/690 V AC 50/60 Hz; AC-23A: 250 A at 660/690 V AC 50/60 Hz; AC-22B: 250 A at 660/690 V AC 50/60 Hz; AC-23B: 250 A at 660/690 V AC 50/60 Hz
Complementary
Breaking capacity: 80 kA at 415 V (AC); 50 kA at 690 V (AC)
Rated operational power in W: 132 kW at 380/400 V; 220 kW at 660/690 V
Contacts type and composition: 3 NO
Type of operating handle: Direct frontal; External frontal; External right side
Provision for padlocking: 3 padlocks
Mounting position: Vertical
Mounting mode: Fixed
Mounting support: Backplate
Mechanical durability: 10000 cycles
Electrical durability: AC-22A: 1000 cycles 415 V AC 50/60 Hz; AC-23A: 1000 cycles 415 V AC 50/60 Hz; AC-22A: 1000 cycles 690 V AC 50/60 Hz; AC-23A: 1000 cycles 690 V AC 50/60 Hz
Connections - terminals: Power circuit: bare cable connectors32 mm²; Power circuit: lugs-ring terminals95…240 mm²
Tightening torque: Power circuit: 25 N.m
Width: 234 mm
height: 195 mm
Depth: 146 mm
Net weight: 3.2 kg
Standards: EN/IEC 60947-1; EN/IEC 60947-3
product certifications: CE; CCC; EAC
Environment
Electrical shock protection class: Class II front face
IP degree of protection: IP20 conforming to IEC 60529 (with terminal cover)
IK degree of protection: IK07 conforming to EN 50102
Pollution degree: 3 conforming to IEC 60947
ambient air temperature for operation: -20…70 °C
Ambient air temperature for storage: -40…80 °C
Fire resistance: 850 °C fuse cover conforming to IEC 60695-2-1; 960 °C body conforming to IEC 60695-2-1
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 20.000 cm
Package 1 Width: 21.000 cm
Package 1 Length: 34.000 cm
Package 1 Weight: 3.651 kg
Unit Type of Package 2: S04
Number of Units in Package 2: 2
Package 2 Height: 30.000 cm
Package 2 Width: 40.000 cm
Package 2 Length: 60.000 cm
Package 2 Weight: 7.952 kg
Unit Type of Package 3: P06
Number of Units in Package 3: 10
Package 3 Height: 75.000 cm
Package 3 Width: 60.000 cm
Package 3 Length: 80.000 cm
Package 3 Weight: 47.760 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Free of Substances of Very High Concern above the threshold
REACh free of SVHC: Yes
EU RoHS Directive: Compliant
Toxic heavy metal free: Yes
Mercury free: Yes
China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP2003006EN
Circularity Profile: ENVEOLI2003006EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins