Schneider-Electric
LV480433
Tariff code:
This product is discontinued.
There is a replacement product available.
Link to the manufacturers site: LV480433 - Switch-disconnector fuse body INFC 4 poles 4F - NFC - 63 A- lateral handle
Main
range of product: INF63
range: FuPact
product name: Fupact INF
device short name: INFC63
product or component type: Switch-disconnector-fuse
device application: Protection
poles description: 4P
protected poles description: 4f
fuse type: NFC
fuse size: 22 x 58 mm
network type: DC; AC
network frequency: 50/60 Hz
Complementary
control type: Without handle
rotary handle mounting location: Lateral
rotary handle mounting style: Extended
provision for padlocking: Padlockable
mounting mode: Vertical - horizontal
mounting support: DIN rail, with specific accessories; Mounting plate
[Ie] rated operational current: AC-22A: 63 A AC 50/60 Hz 220/240 V; AC-22A: 63 A AC 50/60 Hz 380/415 V; AC-22A: 63 A AC 50/60 Hz 440/480 V; AC-22A: 63 A AC 50/60 Hz 500/525 V; AC-22A: 63 A AC 50/60 Hz 660/690 V; AC-23A: 63 A AC 50/60 Hz 220/240 V; AC-23A: 63 A AC 50/60 Hz 380/415 V; AC-23A: 63 A AC 50/60 Hz 440/480 V; AC-23A: 63 A AC 50/60 Hz 500/525 V; AC-23A: 63 A AC 50/60 Hz 660/690 V; DC-22B: 63 A DC 220 V 2 poles in series; DC-23B: 63 A DC 220 V 2 poles in series; DC-21B: 63 A DC 440 V 4 poles in series
[Ith] conventional free air thermal current: 63 A ( 40 °C ) vertical; 45 A ( 70 °C ) horizontal; 48 A ( 65 °C ) horizontal; 45 A ( 70 °C ) vertical; 51 A ( 60 °C ) horizontal; 48 A ( 65 °C ) vertical; 53 A ( 55 °C ) horizontal; 51 A ( 60 °C ) vertical; 56 A ( 50 °C ) horizontal; 53 A ( 55 °C ) vertical; 56 A ( 50 °C ) vertical; 58 A ( 45 °C ) horizontal; 61 A ( 40 °C ) horizontal; 58 A ( 45 °C ) vertical; 63 A ( 35 °C ) horizontal
[Ithe] conventional enclosed thermal current: 63 A at 40 °C, Power dissipation per fuse: 7.5 W (300 mm x 350 mm x 200 mm)
maximum power: 30 kW at 380/400 V AC 50/60 Hz; 30 kW at 415 V AC 50/60 Hz; 37 kW at 500/525 V AC 50/60 Hz; 60 kW at 660/690 V AC 50/60 Hz; 18.5 kW at 220/240 V AC 50/60 Hz
rated duty: Uninterrupted
intermittent duty class: Class 120 - 60 %
[Ui] rated insulation voltage: 1000 V AC 50/60 Hz; 1000 V DC
[Uimp] rated impulse withstand voltage: 12 kV
[Ue] rated operational voltage: 250 V DC; 690 V AC 50/60 Hz; 690 V AC 50/60 Hz AC-20; 690 V DC DC-20
[Im] rated making and breaking capacity: Icm 105 kA at 690 V conforming to DIN (with fuse); Icm 13 kA at 690 V (without fuse); Icm 17 kA at 415 V (without fuse); Icm 17 kA at 500 V (without fuse); Icm 176 kA at 415 V conforming to BS (with fuse); Icm 220 kA at 500 V conforming to DIN (with fuse); Icn 100 kA at 500 V conforming to DIN (with fuse); Icn 50 kA at 690 V conforming to DIN (with fuse); Icn 80 kA at 415 V conforming to BS (with fuse)
suitability for isolation: Yes
contact position indicator: Yes
visible break: No
contact operation: Double-break
Environment
mechanical durability: 10000 cycles
electrical durability: AC-22A: 1500 cycles 500 V AC 50/60 Hz; AC-22A: 1500 cycles 690 V AC 50/60 Hz; AC-23A: 1500 cycles 500 V AC 50/60 Hz; AC-23A: 1500 cycles 690 V AC 50/60 Hz
[Icw] rated short-time withstand current: 0.46 kA for 30 s; 0.56 kA for 20 s; 1.44 kA for 3 s; 2.5 kA for 1 s
design: Horizontal design
connections terminals: Screw clamp terminals
connections - terminals: Screw clamp terminals 63 A 2.5…25 mm² flexible; Screw clamp terminals 63 A 2.5…25 mm² rigid
tightening torque: 2 N.m for terminal
height: 140 mm
width: 216.5 mm
depth: 142 mm
standards: EN/IEC 60947-5; EN/IEC 60269-1; EN/IEC 60947-3; EN/IEC 60947-1; EN/IEC 60269-4
product certifications: CCC
IP degree of protection: IP20 conforming to IEC 60529; IP65 conforming to IEC 60529
IK degree of protection: IK07 conforming to EN 50102; IK10 conforming to EN 50102
pollution degree: 3
ambient air temperature for operation: -25…70 °C
ambient air temperature for storage: -50…85 °C
compatibility code: INF63
Offer Sustainability
EU RoHS Directive: Under investigation
Environmental Disclosure: ENVPEP2003007EN
Circularity Profile: ENVEOLI2003007EN