Schneider-Electric
LC1E3210U5
Tariff code: 8536490099
Link to the manufacturers site: LC1E3210U5 - EasyPact TVS contactor 3P(3 NO) - AC-3 - <= 440 V 32A - 240 V AC coil
Main
Range: Easy TeSys
Range of produc: Easy TeSys Control
Product or component type: Contactor
Device short name: LC1E
contactor application: Resistive load; Motor control
utilisation category: AC-3; AC-1
Poles description: 3P
[Ue] rated operational voltage: Power circuit: <= 690 V AC 50/60 Hz
[Ie] rated operational current: 32 A (at <55 °C) at <= 440 V AC AC-3 for power circuit; 50 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage: 240 V AC 50 Hz
Complementary
Motor power kW: 7.5 kW at 220...230 V AC 50/60 Hz (AC-3); 15 kW at 380...400 V AC 50/60 Hz (AC-3); 15 kW at 415 V AC 50/60 Hz (AC-3); 15 kW at 440 V AC 50/60 Hz (AC-3); 18.5 kW at 500 V AC 50/60 Hz (AC-3); 18.5 kW at 660...690 V AC 50/60 Hz (AC-3)
Pole contact composition: 3 NO
[Ith] conventional free air thermal current: 50 A (at 55 °C)
Irms rated making capacity: 320 A at 440 V AC for power circuit conforming to IEC 60947-4-1
Rated breaking capacity: 256 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current: 260 A 40 °C - 10 s for power circuit; 138 A 40 °C - 60 s for power circuit; 60 A 40 °C - 600 s for power circuit
Associated fuse rating: 10 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1; 63 A gG at <= 690 V coordination type 1 for power circuit
Average impedance: 2.5 mOhm - Ith 50 A 50 Hz for power circuit
Power dissipation per pole: 2 W AC-3; 5 W AC-1
[Ui] rated insulation voltage: 690 V conforming to IEC 60947-4-1
Overvoltage category: III
Pollution degree: 3
[Uimp] rated impulse withstand voltage: 6 kV coil not connected to the power circuit conforming to IEC 60947
Mechanical durability: 8000000 cycles
Electrical durability: 1000000 cycles AC-3; 350000 cycles AC-1
Control circuit type: AC at 50 Hz
Control circuit voltage limits: 0.85...1.1 Uc (-5…55 °C):operational 50 Hz; 0.3...0.6 Uc (-5…55 °C):drop-out 50 Hz
Inrush power in VA: 95 VA 50 Hz cos phi 0.75 (at 20 °C); 95 VA 60 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in VA: 8.3 VA 50 Hz cos phi 0.3 (at 20 °C); 8.5 VA 60 Hz cos phi 0.3 (at 20 °C)
Heat dissipation: 2…3 W for control circuit
Operating time: 12...22 ms on closing; 4...19 ms on opening
Maximum operating rate: 1800 cyc/h 60 °C
Connections - terminals: Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end; Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end; Power circuit: screw clamp terminals 1 1.5…6 mm² - cable stiffness: solid without cable end; Power circuit: screw clamp terminals 2 1.5…6 mm² - cable stiffness: solid without cable end; Power circuit: screw clamp terminals 1 1…6 mm² - cable stiffness: flexible with cable end; Power circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible with cable end
Tightening torque: Control circuit: 1.2 N.m; Power circuit: 2.1 N.m
Auxiliary contact composition: 1 NO
Minimum switching voltage: 17 V for control circuit
Minimum switching current: 5 mA for control circuit
Insulation resistance: > 10 MOhm for control circuit
Non-overlap time: 1.5 ms on energisation guaranteed between NC and NO contact; 1.5 ms on de-energisation guaranteed between NC and NO contact
mounting support: Plate; DIN rail
Environment
Standards: IEC 60947-1; IEC 60947-5-1; IEC 60947-4-1
product certifications: EAC; CE
IP degree of protection: IP2X conforming to IEC 60529
Protective treatment: TH (pollution degree 3) conforming to IEC 60068-2-30 test Db
Permissible ambient air temperature around the device: -20…70 °C at Uc; -60…80 °C storage; -5…55 °C operation
Operating altitude: 3000 m without derating
Fire resistance: 850 °C conforming to IEC 60695-2-1
Mechanical robustness: Vibrations contactor open (1.5 Gn, 5...300 Hz) ; Vibrations contactor closed (3 Gn, 5...300 Hz) ; Shocks contactor closed (10 Gn for 11 ms) ; Shocks contactor open (6 Gn for 11 ms)
height: 84 mm
Width: 56 mm
Depth: 86 mm
Net weight: 0.45 kg
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 8.6 cm
Package 1 Width: 8.4 cm
Package 1 Length: 5.6 cm
Package 1 Weight: 449 g
Unit Type of Package 2: S02
Number of Units in Package 2: 24
Package 2 Height: 15 cm
Package 2 Width: 30 cm
Package 2 Length: 40 cm
Package 2 Weight: 11.184 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Free of Substances of Very High Concern above the threshold
REACh free of SVHC: Yes
EU RoHS Directive: Compliant
Toxic heavy metal free: Yes
Mercury free: Yes
China RoHS Regulation: X
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP1610006EN
Circularity Profile: ENVEOLI1610006
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
© 2018 Alplan Kft.