Schneider-Electric
ATV212HD18M3X
Tariff code: 8504409590
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: ATV212HD18M3X - Altivar ATV212 frekvenciaváltó épületes alkalmazásokra, BACnet, 18kW, 3f, 200…240VAC, IP21, EMC szűrő nélkül
Main
device short name: ATV212
Product destination: Asynchronous motors
Network number of phases: 3 phases
Motor power kW: 18.5 kW
Motor power hp: 25 hp
Supply voltage limits: 170…264 V
Supply frequency: 50...60 Hz - 5...5 %
Line current: 55.8 A at 240 V; 67.3 A at 200 V
Range of product: Altivar 212
product or component type: Variable speed drive
Product specific application: Pumps and fans in HVAC
Communication port protocol: METASYS N2; Modbus; BACnet; LonWorks; APOGEE FLN
[Us] rated supply voltage: 200...240 V - 15...10 %
EMC filter: Without EMC filter
IP degree of protection: IP21
Complementary
Apparent power: 28.5 kVA at 240 V
Continuous output current: 74.8 A at 230 V
Maximum transient current: 82.3 A for 60 s
Speed drive output frequency: 0.5…200 Hz
Speed range: 1…10
Speed accuracy: +/- 10 % of nominal slip 0.2 Tn to Tn
Local signalling: 1 LED (red) for DC bus energized
Output voltage: <= power supply voltage
Isolation: Electrical between power and control
Type of cable: Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR; Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC; With UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC
Electrical connection: VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES: terminal 2.5 mm² / AWG 14; L1/R, L2/S, L3/T: terminal 25 mm² / AWG 3
Tightening torque: 0.6 N.m (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES); 4.5 N.m, 40 lb.in (L1/R, L2/S, L3/T)
Supply: Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 A, protection type: overload and short-circuit protection; Internal supply: 24 V DC (21…27 V), <200 A, protection type: overload and short-circuit protection
Sampling duration: 2 ms +/- 0.5 ms F discrete; 2 ms +/- 0.5 ms R discrete; 2 ms +/- 0.5 ms RES discrete; 3.5 ms +/- 0.5 ms VIA analog; 22 ms +/- 0.5 ms VIB analog
Response time: FM 2 ms, tolerance +/- 0.5 ms for analog output(s); FLA, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s); FLB, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s); RY, RC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
Accuracy: +/- 0.6 % (VIA) for a temperature variation 60 °C; +/- 0.6 % (VIB) for a temperature variation 60 °C; +/- 1 % (FM) for a temperature variation 60 °C
Linearity error: VIA: +/- 0.15 % of maximum value for input; VIB: +/- 0.15 % of maximum value for input; FM: +/- 0.2 % for output
Analogue output type: FM switch-configurable voltage 0...10 V DC, impedance: 7620 Ohm, resolution 10 bits; FM switch-configurable current 0...20 mA, impedance: 970 Ohm, resolution 10 bits
Discrete output type: Configurable relay logic: (FLA, FLC) NO - 100000 cycles; Configurable relay logic: (FLB, FLC) NC - 100000 cycles; Configurable relay logic: (RY, RC) NO - 100000 cycles
Minimum switching current: 3 mA at 24 V DC for configurable relay logic
Maximum switching current: 5 A at 250 V AC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R); 5 A at 30 V DC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R); 2 A at 250 V AC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R); 2 A at 30 V DC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R)
Discrete input type: F programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm; R programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm; RES programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
Discrete input logic: Positive logic (source) (F, R, RES), <= 5 V (state 0), >= 11 V (state 1); Negative logic (sink) (F, R, RES), >= 16 V (state 0), <= 10 V (state 1)
Dielectric strength: 2830 V DC between earth and power terminals; 4230 V DC between control and power terminals
Insulation resistance: >= 1 mOhm 500 V DC for 1 minute
Frequency resolution: Display unit: 0.1 Hz; Analog input: 0.024/50 Hz
Communication service: Write multiple registers (16) 2 words maximum; Read holding registers (03) 2 words maximum; Read device identification (43); Monitoring inhibitable; Time out setting from 0.1 to 100 s; Write single register (06)
Option card: Communication card for LonWorks
power dissipation in W: 698 W
Air flow: 239 m3/h
Specific application: HVAC
Discrete and process manufacturing: Building - HVAC compressor for scroll; Building - HVAC fan; Building - HVAC pump
Power range: 15…25 kW at 200…240 V 3 phases
Motor starter type: Variable speed drive
Discrete output number: 2
Analogue input number: 2
Analogue input type: VIA switch-configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits; VIB configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits; VIB configurable PTC probe: 0...6 probes, impedance: 1500 Ohm; VIA switch-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 10 bits
Analogue output number: 1
Physical interface: 2-wire RS 485
Connector type: 1 RJ45; 1 open style
Transmission rate: 9600 bps or 19200 bps
Transmission frame: RTU
Number of addresses: 1…247
Data format: 8 bits, 1 stop, odd even or no configurable parity
Type of polarization: No impedance
Asynchronous motor control profile: Voltage/frequency ratio, 5 points; Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo); Voltage/frequency ratio - Energy Saving, quadratic U/f; Flux vector control without sensor, standard; Voltage/frequency ratio, 2 points
Torque accuracy: +/- 15 %
Transient overtorque: 120 % of nominal motor torque +/- 10 % for 60 s
Acceleration and deceleration ramps: Automatic based on the load; Linear adjustable separately from 0.01 to 3200 s
Motor slip compensation: Not available in voltage/frequency ratio motor control; Automatic whatever the load; Adjustable
Switching frequency: 6...16 kHz adjustable; 8...16 kHz with derating factor
Nominal switching frequency: 8 kHz
Braking to standstill: By DC injection
Network frequency: 47.5...63 Hz
Prospective line Isc: 22 kA
Protection type: Overheating protection: drive; Thermal power stage: drive; Short-circuit between motor phases: drive; Input phase breaks: drive; Overcurrent between output phases and earth: drive; Overvoltages on the DC bus: drive; Break on the control circuit: drive; Against exceeding limit speed: drive; Line supply overvoltage and undervoltage: drive; Line supply undervoltage: drive; Against input phase loss: drive; Thermal protection: motor; Motor phase break: motor; With PTC probes: motor
width: 245 mm
height: 330 mm
depth: 190 mm
net weight: 11.55 kg
Environment
Pollution degree: 2 conforming to IEC 61800-5-1
IP degree of protection: IP20 on upper part without blanking plate on cover conforming to EN/IEC 61800-5-1; IP20 on upper part without blanking plate on cover conforming to EN/IEC 60529; IP21 conforming to EN/IEC 61800-5-1; IP21 conforming to EN/IEC 60529; IP41 on upper part conforming to EN/IEC 61800-5-1; IP41 on upper part conforming to EN/IEC 60529
Vibration resistance: 1.5 mm (f= 3…13 Hz) conforming to EN/IEC 60068-2-6; 1 gn (f= 13…200 Hz) conforming to EN/IEC 60068-2-8
Shock resistance: 15 gn for 11 ms conforming to IEC 60068-2-27
Environmental characteristic: Classes 3C1 conforming to IEC 60721-3-3; Classes 3S2 conforming to IEC 60721-3-3
Noise level: 54 dB conforming to 86/188/EEC
Operating altitude: 1000...3000 m limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m; <= 1000 m without derating
Relative humidity: 5…95 % without condensation conforming to IEC 60068-2-3; 5…95 % without dripping water conforming to IEC 60068-2-3
Ambient air temperature for operation: -10…40 °C (without derating); 40…50 °C (with derating factor)
Operating position: Vertical +/- 10 degree
Product certifications: C-Tick; CSA; NOM 117; UL
Marking: CE
Standards: IEC 61800-3 environments 2 category C3; UL Type 1; EN 61800-3 environments 2 category C3; EN 61800-3 environments 2 category C2; EN 61800-5-1; EN 61800-3 environments 2 category C1; EN 61800-3; IEC 61800-3 environments 1 category C3; EN 61800-3 environments 1 category C1; IEC 61800-3 environments 1 category C2; IEC 61800-3 environments 2 category C2; EN 61800-3 environments 1 category C3; IEC 61800-3 environments 2 category C1; IEC 61800-5-1; IEC 61800-3 environments 1 category C1; IEC 61800-3; EN 61800-3 environments 1 category C2
Assembly style: With heat sink
Electromagnetic compatibility: Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2; Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3; Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4; 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5; Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6; Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
Regulation loop: Adjustable PI regulator
Ambient air temperature for storage: -25…70 °C
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 28.000 cm
Package 1 Width: 39.000 cm
Package 1 Length: 30.000 cm
Package 1 Weight: 11.320 kg
Unit Type of Package 2: P06
Number of Units in Package 2: 4
Package 2 Height: 75.000 cm
Package 2 Width: 60.000 cm
Package 2 Length: 80.000 cm
Package 2 Weight: 53.800 kg
Offer Sustainability
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free: Yes
China RoHS Regulation: X
RoHS exemption information: Yes
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
© 2018 Alplan Kft.