Schneider-Electric
A9FDB606
Tariff code: 8536201090
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: A9FDB606 - iDPN N Arc 1P N 6A C 6000A Arc fault det
Main
Circuit breaker application: Distribution
Range of product: Acti9
Range: Acti9
Product name: Acti9 iDPN N Arc
Product or component type: Arc fault detection circuit breaker
Product specific application: Fire prevention by arc detection
Standards: EN/IEC 62606; IEC 60898-1
Device short name: iDPN N Arc
Poles description: 1P + N
[In] rated current: 6 A at 30 °C
Curve code: C
Breaking capacity: 6000 A Icn at 230 V AC 50 Hz conforming to EN/IEC 60898-1
Network type: AC
Neutral position: Left
Trip unit technology: Thermal-magnetic
Complementary
Number of protected poles: 1
Network frequency: 50 Hz
[Ue] rated operational voltage: 230 V AC 50 Hz conforming to IEC 62606; 230 V AC 50 Hz conforming to EN/IEC 60898-1
Device location in system: Outgoer
Magnetic tripping limit: 5...10 x In
Limitation class: 3 conforming to IEC 60898-1
Threshold tripping voltage: 400 V 200 ms
[Uimp] rated impulse withstand voltage: 4 kV conforming to IEC 60898-1
[Ui] rated insulation voltage: 400 V AC
Contact position indicator: Yes
control type: Toggle
Local signalling: ON, OFF, fault trip
Mounting mode: Clip-on
Mounting support: DIN rail
Colour: White
Mechanical durability: 20000 cycles
Electrical durability: 20000 cycles 230 V AC 50 Hz
Overvoltage category: III
Cable entry: Top
Connections - terminals: Tunnel type terminal for 1 cable(s) 10 mm² flexible; Tunnel type terminal for 2 cable(s) 2.5 mm² flexible; Tunnel type terminal for 1 cable(s) 16 mm² rigid; Tunnel type terminal for 2 cable(s) 2.5 mm² rigid
Wire stripping length: 14 mm
Tightening torque: 2 N.m
Comb busbar and distribution block compatibility: ProDis; Librio
Connection pitch: 9 mm between phase and neutral
9 mm pitches: 4
Height: 81 mm
Width: 36 mm
Depth: 72 mm
Net weight: 190 g
Environment
Heat dissipation: 2.7 W at 230 V - 6 A
IP degree of protection: IP20
Pollution degree: 2
Tropicalisation: Severity B conforming to IEC 60068-2-30 for 28 d
Operating altitude: 2000 m
Ambient air temperature for operation: -25…60 °C
Ambient air temperature for storage: -40…85 °C
Product certifications: RCM
Packing Units
Unit Type of Package 1: Db
Number of Units in Package 1: 1
Package 1 Height: 4.0 cm
Package 1 Width: 8.5 cm
Package 1 Length: 10.0 cm
Package 1 Weight: 220.0 g
Unit Type of Package 2: S02
Number of Units in Package 2: 8
Package 2 Height: 15.0 cm
Package 2 Width: 30.0 cm
Package 2 Length: 40.0 cm
Package 2 Weight: 2.004 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Compliant
Mercury free: Yes
China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP1312033EN
Circularity Profile: ENVEOLI1312033EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
© 2018 Alplan Kft.