Schneider-Electric
28606
Tariff code:
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: 28606 - circuit breaker NG160E - TMD - 40 A - 3 poles 3d
Main
range: ComPact
range of product: NG160
product name: NG160
product or component type: Circuit breaker
device short name: NG160E
circuit breaker name: NG160E
device application: Distribution
poles description: 3P
protected poles description: 3t
network type: AC
network frequency: 50/60 Hz
[In] rated current: 40 A at 40 °C
breaking capacity code: E
breaking capacity: 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 16 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2; 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2; 8 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity: 6 kA at 500 V AC 50/60 Hz; 7.5 kA at 440 V AC 50/60 Hz; 12 kA at 380/415 V AC 50/60 Hz; 18.75 kA at 220/240 V AC 50/60 Hz
suitability for isolation: Yes
trip unit name: TM-D
trip unit technology: Thermal-magnetic
trip unit rating: 40 A
protection type: Overload protection (thermal); Short-circuit protection (magnetic)
Complementary
control type: Toggle
mounting mode: Clipped
mounting support: 35 mm symmetrical DIN rail
upside connection: Front
downside connection: Front
connections - terminals: Tunnel type terminals
mechanical durability: 10000 cycles
electrical durability: 5000 cycles 440 V
local signalling: ON/OFF indication
magnetic tripping current: 600 A
long time pick-up adjustment type Ir: Fixed
earth-leakage protection: Separate block
height: 120 mm
width: 90 mm
depth: 82.5 mm
product compatibility: Single terminal
compatibility code: NG160
Environment
standards: IEC 60947-3
Offer Sustainability
EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)
Environmental Disclosure: ENVPEP060504EN
Circularity Profile: ENVEOLI100403