Skip to main content

Schneider-Electric
18661

NG125 - circuit breaker - NG125N - 4P - 125A - C curve
Barcode: 3303430186618
Tariff code:

This product is discontinued.

Please contact us for possible replacement product options.

Link to the manufacturers site: 18661 - NG125 - circuit breaker - NG125N - 4P - 125A - C curve

Main

range of product: NG125

range: Acti 9

product name: Acti9 NG125

product or component type: Miniature circuit-breaker

device short name: NG125N

device application: Distribution

poles description: 4P

number of protected poles: 4

[In] rated current: 125 A at 40 °C

network type: AC; DC

trip unit technology: Thermal-magnetic

curve code: C

breaking capacity code: N

breaking capacity: 20 kA Icu at <= 500 V DC conforming to EN/IEC 60947-2; 10 kA Icu at 500 V AC 50/60 Hz conforming to EN/IEC 60947-2; 20 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2; 25 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2; 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2

utilisation category: Category A conforming to IEC 60947-2

suitability for isolation: Yes conforming to IEC 60947-2

Complementary

network frequency: 50/60 Hz

[Ue] rated operational voltage: 380...415 V AC 50/60 Hz; 500 V AC 50/60 Hz; <= 500 V DC; 220...240 V AC 50/60 Hz; 440 V AC 50/60 Hz

magnetic tripping limit: 8 x In

[Ics] rated service breaking capacity: 37.5 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz; 18.75 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz; 15 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz; 7.5 kA 75 % conforming to EN/IEC 60947-2 - 500 V AC 50/60 Hz; 20 kA 100 % conforming to EN/IEC 60947-2 - <= 500 V DC

[Ui] rated insulation voltage: 690 V AC 50/60 Hz conforming to EN/IEC 60947-2

[Uimp] rated impulse withstand voltage: 8 kV conforming to EN/IEC 60947-2

contact position indicator: Yes

control type: Manual tripping test; Toggle

local signalling: Trip indicator; ON/OFF indication

mounting mode: Clip-on

mounting support: 35 mm symmetrical DIN rail

comb busbar and distribution block compatibility: NO

9 mm pitches: 12

height: 103 mm

width: 108 mm

depth: 81 mm

net weight: 0.96 kg

mechanical durability: 20000 cycles

electrical durability: 5000 cycles

provision for padlocking: Padlockable

locking options description: Integrated padlocking

connections - terminals: Tunnel type terminals16…70 mm² rigid; Tunnel type terminals10…50 mm² flexible

wire stripping length: 20 mm

tightening torque: 6 N.m

earth-leakage protection: Separate block

compatibility code: NG125

market segment: Small commercial

Environment

standards: EN/IEC 60947-2

IP degree of protection: IP20 conforming to IEC 60529

IK degree of protection: IK05 conforming to EN/IEC 62262

pollution degree: 3 conforming to IEC 60947-2

overvoltage category: IV

tropicalisation: 2 conforming to IEC 60068-1

relative humidity: 95 % at 55 °C

ambient air temperature for operation: -30…70 °C

ambient air temperature for storage: -40…70 °C

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Free of Substances of Very High Concern above the threshold

REACh free of SVHC: Yes

EU RoHS Directive: Compliant

Toxic heavy metal free: Yes

Mercury free: Yes

RoHS exemption information: Yes

China RoHS Regulation:  Pro-active China RoHS declaration (out of China RoHS legal scope)

Environmental Disclosure: ENVPEP1406008EN

Circularity Profile: ENVEOLI1406008_V1

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

© 2018 Alplan Kft.