Schneider-Electric
16924
Tariff code: 8536303099
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: 16924 - residual current circuit breaker ID - 4 poles - 125 A - class A 30 mA
Main
Range of produc: ID RCCB
Range: Acti9
Product name: Acti9 RCCB-ID
Product or component type: Residual current circuit breaker (RCCB)
Device short name: RCCB-ID
Poles description: 4P
Neutral position: Left
[In] rated current: 125 A
Network type: AC
Earth-leakage sensitivity: 30 mA
earth-leakage protection time delay: Instantaneous
Earth-leakage protection class: Type A
Rated breaking and making capacity: Im = 1250 A 400 V conforming to IEC 61008
Rated conditional short-circuit current: Inc 10 kA 125 A
Complementary
device location in system: Outgoer
Network frequency: 50/60 Hz
[Ue] rated operational voltage: 400 V AC 50 Hz conforming to IEC 61008
Residual current tripping technology: Electromechanical
[Ui] rated insulation voltage: 440 V AC 50 Hz conforming to IEC 61008-1
[Uimp] rated impulse withstand voltage: 4 kV conforming to IEC 61008-1
control type: Toggle
Mounting mode: Fixed
mounting support: 35 mm symmetrical DIN rail
Connection pitch: 18 mm between phases
9 mm pitches: 8
height: 86 mm
Width: 72 mm
Depth: 76 mm
Net weight: 420 g
Colour: Grey
Mechanical durability: 5000 cycles
Electrical durability: 2000 cycles
Provision for padlocking: Padlockable
Connections - terminals: Tunnel type terminals2 cable(s) 1.5…16 mm² flexible; Tunnel type terminals2 cable(s) 1.5…16 mm² rigid; Tunnel type terminals1 cable(s) 1.5…50 mm² rigid; Tunnel type terminals1 cable(s) 1.5…35 mm² flexible; Tunnel type terminals1 cable(s) 1.5…35 mm² flexible with ferrule; Tunnel type terminals2 cable(s) 1.5…16 mm² flexible with ferrule
Wire stripping length: 11 mm
Tightening torque: 3 N.m
Compatibility code: ID_RCCB
Market segment: Small commercial
Environment
Standards: IEC 60947-3; IEC 60947-1; IEC 61008
IP degree of protection: IP20 conforming to IEC 60529; IP40 (modular enclosure) conforming to IEC 60529
Pollution degree: 3
Tropicalisation: 2 conforming to IEC 61008
Relative humidity: 95 % at 55 °C
Operating altitude: 2000 m
ambient air temperature for operation: -25…40 °C
Ambient air temperature for storage: -40…85 °C
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 7.0 cm
Package 1 Width: 8.0 cm
Package 1 Length: 9.0 cm
Package 1 Weight: 451.0 g
Unit Type of Package 2: S02
Number of Units in Package 2: 12
Package 2 Height: 15.0 cm
Package 2 Width: 30.0 cm
Package 2 Length: 40.0 cm
Package 2 Weight: 5.759 kg
Offer Sustainability
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Compliant
Toxic heavy metal free: Yes
Mercury free: Yes
China RoHS Regulation: Pro-active China RoHS declaration (out of China RoHS legal scope)
RoHS exemption information: Yes
Circularity Profile: N/A
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins