Main

range of product: Preventa Safety automation

product or component type: Preventa safety module

safety module name: XPSECPE

safety module application: Increasing the number of safety contacts

function of module: Increasing the number of safety contacts

safety level: Can reach PL e/category 4 can reach the maximum safety level of module base conforming to EN/ISO 13849-1; Can reach SILCL 3 can reach the maximum safety level of module base conforming to EN/IEC 62061

safety reliability data: MTTFd > 100 years conforming to EN/ISO 13849-1; DC = 0...99 % conforming to EN/ISO 13849-1; PFHd = 2.47E-8 1/h conforming to EN/IEC 62061

output type: Relay, 8 NO circuit(s), volt-free

[Us] rated supply voltage: 24 V AC - 15...10 %; 24 V DC - 15...10 %

number of additional circuits: 2 NC + 1 solid state output

Complementary

supply frequency: 50/60 Hz

power consumption in VA: 4 VA

input protection type: Internal, electronic

breaking capacity: 360 VA holding AC-15 B300 relay output; 3600 VA inrush AC-15 B300 relay output

breaking capacity: 3 A at 24 V (DC-13) time constant: 50 ms for relay output; 20 mA at 24 V for solid state output circuit

output thermal current: 6 A per relay for relay output

[Ith] conventional free air thermal current: 24 A for relay output

associated fuse rating: 6 A gG for relay output conforming to EN/IEC 60947-5-1, DIN VDE 0660 part 200

minimum output current: 10 mA for relay output

minimum output voltage: 5 V for relay output

maximum response time on input open: 10 ms

[Ui] rated insulation voltage: 300 V (pollution degree 2) conforming to EN/IEC 60947-5-1, DIN VDE 0110 parts 1 & 2

[Uimp] rated impulse withstand voltage: 4 kV overvoltage category III conforming to EN/IEC 60947-5-1, DIN VDE 0110 parts 1 & 2

local signalling: 3 LEDs

connections - terminals: Spring terminals, removable terminal block, 1 x 0.2...1 x 2.5 mm² solid without cable end; Spring terminals, removable terminal block, 1 x 0.2...1 x 2.5 mm² flexible without cable end; Spring terminals, removable terminal block, 1 x 0.25...1 x 2.5 mm² flexible with cable end, without bezel; Spring terminals, removable terminal block, 1 x 0.25...1 x 1.5 mm² flexible with cable end, with bezel; Spring terminals, removable terminal block, 2 x 0.2...2 x 1 mm² solid without cable end; Spring terminals, removable terminal block, 2 x 0.2...2 x 1 mm² flexible without cable end; Spring terminals, removable terminal block, 2 x 0.25...2 x 1 mm² flexible with cable end, without bezel; Spring terminals, removable terminal block, 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel

mounting support: 35 mm symmetrical DIN rail

net weight: 0.65 kg

Environment

standards: EN/IEC 60204-1; EN/IEC 60947-5-1

product certifications: UL; CSA; CCC

IP degree of protection: IP20 (terminals) conforming to EN/IEC 60529; IP40 (enclosure) conforming to EN/IEC 60529

ambient air temperature for operation: -25…55 °C

ambient air temperature for storage: -25…70 °C