Skip to main content

Schneider-Electric
XCSDMC7902

coded magnetic switch XCSDMC - 2 NC - staggered - 2m
Net discounted price 84.77 EUR
Available when ordered (delivery time: 20 working day(s))
Barcode: 3389110971699
Tariff code: 8536508090

Link to the manufacturers site: XCSDMC7902 - coded magnetic switch XCSDMC - 2 NC - staggered - 2m

Main

Range of produc: Telemecanique Safety switches XCS

Product or component type: Coded magnetic switch

component name: XCSDMC

Design: Rectangular, compact

Size: 51 x 16 x 7 mm

Contacts type and composition: 2 NC

contact operation: Staggered

Material: Plastic

Electrical connection: Pre-cabled

cable composition: 4 x 0.25 mm²

Cable length: 2 m

Number of poles: 2

Approach directions: 3 directions

[Ue] rated operational voltage: 24 V DC

[Ui] rated insulation voltage: 100 V DC

Complementary

[Sa] assured operating distance: 5 mm

[Sar] assured tripping distance: 15 mm

Maximum [Ie] rated operational current: 100 mA

[Uimp] rated impulse withstand voltage: 2.5 kV conforming to EN/IEC 60947-5-1

Resistance across terminals: 10 Ohm

Short-circuit protection: 500 mA external cartridge fuse type gG (gl)

Contacts material: Rhodium

Electrical durability: 1200000 cycles

Maximum switching voltage: 100 V DC

Switching capacity in mA: 0.1...100 mA

Insulation resistance: 1000 MOhm

Breaking capacity: 10 VA

Switching frequency: 150 Hz

Safety level: Can reach category 4 with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1; Can reach PL = e with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1; Can reach SIL 3 with the appropriate monitoring system and correctly wired conforming to EN/IEC 61508

Safety reliability data: B10d = 50000000 value given for a life time of 20 years limited by mechanical or contact wear

Enclosure material: Thermoplastic PBT

cable material: PVC

Depth: 7 mm

height: 51 mm

Width: 16 mm

Net weight: 0.101 kg

Environment

Standards: CSA C22.2 No 14; UL 508; EN/IEC 60947-5-1; EN/IEC 60204-1; EN/ISO 12100; ISO 14119

product certifications: CSA; UL

Protective treatment: TH

ambient air temperature for operation: -25…85 °C

Ambient air temperature for storage: -40…85 °C

Vibration resistance: 10 gn (f= 10…150 Hz) conforming to IEC 60068-2-6

Shock resistance: 30 gn for 11 ms conforming to IEC 60068-2-27

Maximum sensitivity to magnetic fields: 0.3 mT

Electrical shock protection class: Class II conforming to EN/IEC 61140

IP degree of protection: IP66 conforming to IEC 60529; IP67 conforming to IEC 60529

Packing Units

Unit Type of Package 1: PCE

Number of Units in Package 1: 1

Package 1 Height: 2.900 cm

Package 1 Width: 18.900 cm

Package 1 Length: 29.500 cm

Package 1 Weight: 108.000 g

Unit Type of Package 2: S02

Number of Units in Package 2: 20

Package 2 Height: 15.000 cm

Package 2 Width: 30.000 cm

Package 2 Length: 40.000 cm

Package 2 Weight: 2.583 kg

Unit Type of Package 3: P06

Number of Units in Package 3: 320

Package 3 Height: 77.000 cm

Package 3 Width: 80.000 cm

Package 3 Length: 60.000 cm

Package 3 Weight: 49.828 kg

Offer Sustainability

REACh Regulation: Free of Substances of Very High Concern above the threshold

REACh free of SVHC: Yes

EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)

Toxic heavy metal free: Yes

Mercury free: Yes

RoHS exemption information: Yes

© 2018 Alplan Kft.