Schneider-Electric
VW3A4565
Tariff code:
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: VW3A4565 - line choke - 0.032 mH - 720 A - 3 phases - 428 W - for variable speed drive
Main
range of product: Altivar
product or component type: Line choke
product compatibility: ATV61HC40N4D - line choke - 1 per drive; ATV71HC31N4 - line choke - 1 per drive
network number of phases: Three phase
range compatibility: Altivar 71; Altivar 61
device application: Reduction of current harmonics
value of inductance: 0.032 mH
[In] rated current: 720 A
saturation current: 1352 A
thermal losses: 428 W
electrical connection: Bare wires diameter: 13 mm
Complementary
supply frequency: 50...60 Hz
max current: 1.65 x nominal current (duration = 60 s)
maximum voltage drop at rated load: 5 %
electrical insulation class: Class F
minimum clearance distance: 5.5 mm IEC 60664
leakage distance: 11.5 mm conforming to IEC 60664
net weight: 82 kg
width: 385 mm
height: 445 mm
depth: 275 mm
Environment
standards: EN 50178; VDE 0160 level 1; IEC 60076 (with HD398)
IP degree of protection: Choke: IP00; Terminals: IP00
environmental characteristic: 3B1 conforming to IEC 721-3-3; 3C2 conforming to IEC 721-3-3; 3S1 conforming to IEC 721-3-3
pollution degree: 2 conforming to EN 50178
vibration resistance: 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6; 1.5 mm peak to peak (f= 3…13 Hz) conforming to IEC 60068-2-6
shock resistance: 15 gn for 11 ms conforming to IEC 60068-2-27
relative humidity: 0…95 %
ambient air temperature for operation: 45…55 °C (with current derating of 2 % per °C); 0…45 °C (without current derating)
ambient air temperature for storage: -25…70 °C
operating altitude: <= 1000 m without current derating; <= 1000 m without derating; 1000...3000 m with current derating 1 % per 100 m
Offer Sustainability
REACh Regulation: Free of Substances of Very High Concern above the threshold
REACh free of SVHC: Yes
EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)
Toxic heavy metal free: Yes
Mercury free: Yes
RoHS exemption information: Yes
China RoHS Regulation: X