Skip to main content

Schneider-Electric
RM17UAS14

voltage control relay RM17-U - range 9..15 V DC
Net discounted price 84.15 EUR
Available when ordered (delivery time: 8 working day(s))
Barcode: 3389119405102
Tariff code: 8536419089

Link to the manufacturers site: RM17UAS14 - voltage control relay RM17-U - range 9..15 V DC

Main

Range of produc: Harmony Control Relays

Relay type: Voltage control relay

Product or component type: Voltage control relay

Product specific application: For single-phase and DC supply

Relay name: RM17UAS

Relay monitored parameters: Overvoltage or undervoltage detection; Self-powered

Time delay type: Adjustable 0.1...10 s, 0 + 10 % on crossing the threshold

Switching capacity in VA: 1250 VA

Minimum switching current: 10 mA at 5 V DC

Maximum switching current: 5 A AC/DC

Measurement range: 9...15 V voltage DC

Utilisation category: AC-12 conforming to IEC 60947-5-1; AC-13 conforming to IEC 60947-5-1; AC-14 conforming to IEC 60947-5-1; AC-15 conforming to IEC 60947-5-1; DC-12 conforming to IEC 60947-5-1; DC-13 conforming to IEC 60947-5-1; DC-14 conforming to IEC 60947-5-1

Contacts type and composition: 1 C/O

Connections - terminals: Screw connectors

[Uc] control circuit voltage: 110...240 V

[In] rated current: 5 A

Complementary

Reset time: 1500 ms time delay

Maximum switching voltage: 250 V AC/DC

Supply voltage limits: 7…20 V DC

Maximum power consumption in W: 1 W DC

Immunity to microbreaks: 20 ms at 12 V

Output contacts: 1 C/O

Nominal output current: 5 A

Hysteresis: 5…20 % of threshold setting

Run-up delay at power-up: 1000 ms DC

Measurement accuracy: +/- 10 % of the full scale value

Repeat accuracy: +/- 0.5 % for input and measurement circuit; +/- 1 % for time delay

Measurement error: < 1 % over the whole range with voltage variation; 0.2 %/°C with temperature variation

Polarity: Non reversible polarity on DC supply

Quality labels: CE

Overvoltage category: III conforming to IEC 60664-1

Insulation resistance: > 500 MOhm at 500 V DC conforming to IEC 60255-5; > 500 MOhm at 500 V DC conforming to IEC 60664-1

[Ui] rated insulation voltage: 250 V conforming to IEC 60664-1; 400 V conforming to IEC 60664-1

Operating position: Any position without derating

Connections - terminals: Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end; Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end; Screw terminals, 1 x 0.2...2 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end; Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end

Tightening torque: 0.6…1 N.m conforming to IEC 60947-1

Housing material: Self-extinguishing plastic

Local signalling: LED (green) for power ON; LED (yellow) for relay ON

Mounting support: 35 mm symmetrical DIN rail conforming to IEC 60715

Electrical durability: 100000 cycles

Mechanical durability: 30000000 cycles

Operating rate: <= 360 operations/hour full load

Width: 17.5 mm

Net weight: 0.08 kg

Compatibility code: RM17

Environment

Electromagnetic compatibility: Emission standard for industrial environments conforming to IEC 61000-6-4; Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3; Immunity for industrial environments conforming to NF EN/IEC 61000-6-2

Standards: IEC 60255-6

product certifications: CSA; C-Tick; GL; UL; GOST

Directives: 73/23/EEC - low voltage directive; 89/336/EEC - electromagnetic compatibility

Ambient air temperature for storage: -40…70 °C

Ambient air temperature for operation: -20…50 °C

Relative humidity: 95 % at 55 °C conforming to IEC 60068-2-30

Vibration resistance: 0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6; 1 gn (f= 57.6…150 Hz) conforming to IEC 60255-21-1

Shock resistance: 5 gn conforming to IEC 60068-2-27

IP degree of protection: IP20 (terminals) conforming to IEC 60529; IP30 (casing) conforming to IEC 60529

Pollution degree: 3 conforming to IEC 60664-1

Dielectric test voltage: 2 kV, 1 min AC 50 Hz conforming to IEC 60255-5; 2 kV, 1 min AC 50 Hz conforming to IEC 60664-1

Non-dissipating shock wave: 4 kV conforming to IEC 60255-5; 4 kV conforming to IEC 60664-1; 4 kV conforming to IEC 61000-4-5

Packing Units

Unit Type of Package 1: PCE

Number of Units in Package 1: 1

Package 1 Height: 2.600 cm

Package 1 Width: 8.000 cm

Package 1 Length: 9.600 cm

Package 1 Weight: 85.900 g

Unit Type of Package 2: S02

Number of Units in Package 2: 48

Package 2 Height: 15.000 cm

Package 2 Width: 30.000 cm

Package 2 Length: 40.000 cm

Package 2 Weight: 4.492 kg

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)

Mercury free: Yes

China RoHS Regulation: X

RoHS exemption information: Yes

Environmental Disclosure: ENVPEP1504008EN

Circularity Profile: ENVEOLI1504008EN

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins