Range: PowerLogic

Product name: PowerLogic PM5000

Device short name: PM5650

Product or component type: Power meter

Market segment: Buildings small building cost management: billing: main incomer; Buildings small building cost management: billing: sub feeder; Buildings medium building cost management: billing: main incomer; Buildings medium building cost management: billing: sub feeder; Buildings large building cost management: billing: main incomer; Buildings large building cost management: billing: sub feeder; Buildings multi-site cost management: billing: main incomer; Buildings multi-site cost management: billing: sub feeder; Data center cost management: billing: main incomer; Data center cost management: billing: sub feeder; Healthcare cost management: billing: main incomer; Healthcare cost management: billing: sub feeder; Industry cost management: billing: main incomer; Industry cost management: billing: sub feeder; Buildings small building cost management: cost allocation: main incomer; Buildings small building cost management: cost allocation: sub feeder; Buildings medium building cost management: cost allocation: main incomer; Buildings medium building cost management: cost allocation: sub feeder; Buildings large building cost management: cost allocation: main incomer; Buildings large building cost management: cost allocation: sub feeder; Buildings multi-site cost management: cost allocation: main incomer; Buildings multi-site cost management: cost allocation: sub feeder; Data center cost management: cost allocation: main incomer; Data center cost management: cost allocation: sub feeder; Healthcare cost management: cost allocation: main incomer; Healthcare cost management: cost allocation: sub feeder; Industry cost management: cost allocation: main incomer; Industry cost management: cost allocation: sub feeder; Buildings small building network management: main incomer; Buildings small building network management: sub feeder; Buildings medium building network management: main incomer; Buildings medium building network management: sub feeder; Buildings large building network management: sub feeder; Buildings multi-site network management: sub feeder; Data center network management: sub feeder; Healthcare network management: sub feeder; Industry network management: sub feeder

Complementary

Power quality analysis: up to the 63rd harmonic; waveform capture; voltage sag and swell detection

Metering type: Measured neutral current; Calculated ground current

Device application: Gateway; WAGES metering; Power monitoring; Multi-tariff

Type of measurement: Current; Voltage; Frequency; Power factor; Energy; Active and reactive power

[Us] rated supply voltage: 100...300 V DC; 90...528 V AC 45...65 Hz

Network frequency: 60 Hz; 50 Hz

[In] rated current: 1 A; 5 A

Poles description: 3P + N; 3P; 1P + N

Maximum power consumption in VA: 16 VA at 480 V

Ride-through time: 35 ms 120 V AC typical; 129 ms 230 V AC typical; 50 ms 125 V DC typical

Display type: Monochrome graphic LCD

Display resolution: 128 x 128 pixels

Sampling rate: 128 samples/cycle

Measurement current: 50…10000 mA

Analogue input type: Voltage (impedance 5 MOhm); Current (impedance <= 0.3 mOhm)

Measurement voltage: 20…400 V AC 45...65 Hz between phase and neutral; 20…828 V AC 45...65 Hz between phases

Frequency measurement range: 45…65 Hz

Number of inputs: 4 digital

Measurement accuracy: Apparent power +/- 0.5 %; Frequency +/- 0.05 %; Active energy +/- 0.2 %; Reactive energy +/- 1 %; Active power +/- 0.2 %; Voltage +/- 0.1 %; Power factor +/- 0.005; Current +/- 0.15 %; Reactive power +/- 1 %

Accuracy class: Class 0.2S active energy conforming to IEC 62053-22

Number of outputs: 2 digital

Information displayed: Tariff (8)

Communication port protocol: Modbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires, insulation 2500 V; JBUS; Modbus TCP/IP at 10/100 Mbit/s, insulation 2500 V; Ethernet Modbus TCP/IP daisy chain; BACnet IP; DNP3 over ethernet

Communication port support: RS485; ETHERNET

communication gateway: Ethernet/serial

data recording: Event logs; Maintenance logs; Min/max of instantaneous values; Data logs; Alarm logs; Time stamping

memory capacity: 1.1 MB

Web services: Alarm notification by e-mail; Web server; Diagnostic via predefined web pages; Real time viewing of data

Ethernet service: SNTP client; SNMP-Traps

Connections - terminals: Voltage circuit: screw terminal block4; Control circuit: screw terminal block2; Current transformer: screw terminal block6; RS485 link: screw terminal block4; Digital input: screw terminal block8; Digital output: screw terminal block4; Ethernet network: RJ45 connector2

Mounting mode: Flush-mounted

Mounting support: Framework

Standards: EN 50470-3; IEC 61557-12:2015; IEC 62053-22:2020; IEC 62053-24; IEC 60529; EN 50470-1; UL 61010-1; IEC 62053-23:2020; IEC 62052-11:2020; IEC 62052-31:2015

Product certifications: CE conforming to IEC 61010-1; CULus conforming to UL 61010-1

Width: 96 mm

Depth: 72 mm

height: 96 mm

Net weight: 450 g

Environment

Electromagnetic compatibility: Limits for harmonic current emissions class A conforming to IEC 61000-3-2; Conducted RF disturbances level 3 conforming to IEC 61000-4-6; Magnetic field at power frequency level 4 conforming to IEC 61000-4-8; Conducted and radiated emissions class B conforming to EN 55022; Limitation of voltage changes, voltage fluctuations and flicker in low-voltage conforming to IEC 61000-3-3; Electrostatic discharge - test level: 8 kV level 4 conforming to IEC 61000-4-2; Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3; Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4; Surge immunity test level 4 conforming to IEC 61000-4-5; Voltage dips and interruptions immunity test conforming to IEC 61000-4-11

IP degree of protection: IP54 display: conforming to IEC 60529; IP30 rear: conforming to IEC 60529

Relative humidity: 5…95 % at 50 °C non-condensing

Pollution degree: 2

Ambient air temperature for operation: -25…70 °C

Ambient air temperature for storage: -40…85 °C

Operating altitude: <= 3000 m

Compatibility code: PM5650

Packing Units

Unit Type of Package 1: PCE

Number of Units in Package 1: 1

Package 1 Height: 11.5 cm

Package 1 Width: 12.5 cm

Package 1 Length: 12.5 cm

Package 1 Weight: 646 g

Unit Type of Package 2: S03

Number of Units in Package 2: 12

Package 2 Height: 30 cm

Package 2 Width: 30 cm

Package 2 Length: 40 cm

Package 2 Weight: 8.133 kg

Unit Type of Package 3: P06

Number of Units in Package 3: 96

Package 3 Height: 75 cm

Package 3 Width: 80 cm

Package 3 Length: 60 cm

Package 3 Weight: 73.064 kg

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive: Compliant with Exemptions

Mercury free: Yes

China RoHS Regulation: X

RoHS exemption information: Yes

Environmental Disclosure: ENVPEP1310016EN

Circularity Profile: ENVEOLI1310016EN

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins