Schneider-Electric
M6200A0A0B0A0B0R
Tariff code:
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: M6200A0A0B0A0B0R - SE 6200-I-5A-P240-STCOM-PULSE-ALL PML 62
Main
range: PowerLogic
range of product: PowerLogic
product name: PowerLogic ION6200
device short name: ION6200
product or component type: Energy and power quality meter
Complementary
power quality analysis: harmonic distortion
device application: Metering
type of measurement: Active and reactive energy; Apparent energy; Current; Voltage; Frequency; Harmonic distorsion (I THD & U THD); Active and reactive power total; Apparent power total; Power factor; Demand current (I1, I2, I3, Ig); Active and reactive power per phase; Apparent power per phase
[Us] rated supply voltage: 100...240 V AC 50/60 Hz; 110...300 V DC
network frequency: 60 Hz; 50 Hz
[In] rated current: 10 A
poles description: 3P + N; 3P; 2P + N
power consumption in VA: 0.05 VA
display type: 7 segments LED + decimal point
sampling rate: 64 samples/cycle
measurement current: 0.005…12 A
measurement voltage: 60…400 V AC 50...60 Hz between phase and neutral; 103.5…690 V AC 50...60 Hz between phases
frequency measurement range: 50…60 Hz
number of inputs: 0
measurement accuracy: Current 0.3 %; Voltage 0.3 %; Power +/- 0.5 %; Frequency +/- 0.1 %; Power factor +/- 1 %; Energy +/- 0.5 %
accuracy class: Class 0.5 power conforming to IEC 60687; Class 0.5 energy conforming to IEC 60687; Class 0.5 power conforming to ANSI C12.20; Class 0.5 energy conforming to ANSI C12.20
number of outputs: 2 pulse
communication port protocol: Modbus RTU, master at 19200 bauds; ION
communication port support: Screw terminal block: RS485 isolated
transmission rate: 19200 bauds
tamperproof of settings: Protected by access code
Environment
electromagnetic compatibility: Electrostatic discharge immunity test conforming to IEC 61000-4-2; Immunity to radiated fields conforming to IEC 61000-4-3; Immunity to fast transients conforming to IEC 61000-4-4; Surge immunity test conforming to IEC 61000-4-5; Conducted radio-frequency immunity test conforming to IEC 61000-4-6; Emission standard for industrial environments conforming to IEC 61000-4-2
mounting mode: Panel-mounted
mounting support: Enclosure door
type of installation: Indoor installation
IP degree of protection: IP30 back: ; IP65 front:
relative humidity: 5…95 %
pollution degree: 2
ambient air temperature for operation: -20…70 °C
ambient air temperature for storage: -40…85 °C
product certifications: CUL conforming to CSA C22.2
standards: CSA 1010-1; EN 61010-1; UL 3111-1
width: 110 mm
depth: 65 mm
height: 110 mm
net weight: 0.68 kg
Offer Sustainability
EU RoHS Directive: Compliant
Mercury free: Yes
RoHS exemption information: Yes
China RoHS Regulation: X
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins