Schneider-Electric
LXD3F7
Tariff code: 8505902999
Link to the manufacturers site: LXD3F7 - TeSys D - contactor coil - LXD3 - 110 V AC 50/60 Hz for 40… 65 A contactor
Main
Range of produc: TeSys Deca
Range: TeSys
Product or component type: Contactor coil
Device short name: LXD3
Control circuit type: AC at 50/60 Hz
[Uc] control circuit voltage: 110 V AC 50/60 Hz
Average resistance: 42.28 Ohm at 20 °C
Inductance of closed circuit: 2.5 H
Product compatibility: LC1D40A...D65A; LC1DT60A; LC1DT80A
Mechanical durability: 6 Mcycles
Maximum operating rate: 3600 cyc/h 60 °C
Complementary
Coil technology: Without built-in suppressor module
Control circuit voltage limits: Drop-out: 0.3...0.6 Uc at 50/60 Hz (at <60 °C); Operational: 0.8...1.1 Uc at 50 Hz (at <60 °C); Operational: 0.85...1.1 Uc at 60 Hz (at <60 °C)
Inrush power in VA: 160 VA 60 Hz cos phi 0.75 (at 20 °C); 160 VA 50 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in VA: 15 VA 60 Hz cos phi 0.3 (at 20 °C); 15 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation: 4…5 W at 50/60 Hz
Environment
ambient air temperature for operation: -5…60 °C
Net weight: 0.07 kg
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 9.600 cm
Package 1 Width: 5.500 cm
Package 1 Length: 5.500 cm
Package 1 Weight: 123.000 g
Unit Type of Package 2: S02
Number of Units in Package 2: 30
Package 2 Height: 15.000 cm
Package 2 Width: 30.000 cm
Package 2 Length: 40.000 cm
Package 2 Weight: 4.043 kg
Offer Sustainability
REACh Regulation: Free of Substances of Very High Concern above the threshold
REACh free of SVHC: Yes
EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)
Toxic heavy metal free: Yes
Mercury free: Yes
China RoHS Regulation: Pro-active China RoHS declaration (out of China RoHS legal scope)
RoHS exemption information: Yes
PVC free: Yes