LV433560

circuit breaker Compact NSX250HB1, 85 kA at 500 VAC, Micrologic 6.2 E-M trip unit 150 A, 3 poles 3d
Barcode: 3606480480539
Tariff code: 8536209090

This product is discontinued.

Please contact us for possible replacement product options.

Link to the manufacturers site: LV433560 - circuit breaker Compact NSX250HB1, 85 kA at 500 VAC, Micrologic 6.2 E-M trip unit 150 A, 3 poles 3d

Main

Range: ComPact

Product name: ComPact NSX

Range of product: ComPact NSX100...250

Device short name: NSX250HB1

Product or component type: Circuit breaker

Device application: Motor

Poles description: 3P

Protected poles description: 3t

[In] rated current: 150 A at 65 °C

[Ue] rated operational voltage: 690 V AC 50/60 Hz

Network type: AC

Network frequency: 50/60 Hz

Suitability for isolation: Yes conforming to EN/IEC 60947-2

Utilisation category: Category A

Breaking capacity: 85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 80 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2; 75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2

Breaking capacity code: HB1 75 kA 690 V AC

Trip unit name: Micrologic 6.2 E-M

Trip unit technology: Electronic

Trip unit protection functions: LSIG

control type: Toggle

Mounting mode: Fixed

Complementary

[Ui] rated insulation voltage: 800 V AC 50/60 Hz

[Uimp] rated impulse withstand voltage: 8 kV

[Ics] rated service breaking capacity: 85 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2; 80 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2; 75 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2

Mechanical durability: 20000 cycles

Electrical durability: 5000 cycles at 690 V In; 10000 cycles at 690 V In/2; 10000 cycles at 440 V In; 20000 cycles at 440 V In/2

Mounting support: Backplate

upside connection: Front

Downside connection: Front

Connection pitch: 35 mm

Protection type: L : for overload protection (long time); S : for short time short-circuit protection; I : for instantaneous short-circuit protection; G : for ground fault protection

Trip unit rating: 150 A at 65 °C

Motor tripping class: 30; 20; 10; 5

Complementary motor protection: Phase unbalance; Underload; Protracted starting time; Stalled rotor

Long time pick-up adjustment type Ir: Adjustable 9 settings

long time pick-up adjustment range: 70...150 A

long time delay adjustment type: Adjustable

[tr] long-time delay adjustment range: 10 s at 7.2 x Ir for trip class 10; 120 s at 1.5 x Ir for trip class 5; 20 s at 7.2 x Ir for trip class 20; 240 s at 1.5 x Ir for trip class 10; 26 s at 6 x Ir for trip class 20; 480 s at 1.5 x Ir for trip class 20; 5 s at 7.2 x Ir for trip class 5; 13.5 s at 6 x Ir for trip class 10; 6.5 s at 6 x Ir for trip class 5; 30 s at 7.2 x Ir for trip class 30; 38 s at 6 x Ir for trip class 30; 720 s at 1.5 x Ir for trip class 30

Thermal memory: 20 minutes before and after tripping

Short-time pick-up adjustment type Isd: Adjustable

[Isd] short-time pick-up adjustment range: 5...13 x Ir

Short-time delay adjustment type: Fixed

Instantaneous pick-up adjustment type Ii: Fixed

Instantaneous pick-up adjustment range: 2250 A

Ground-fault pick-up adjustment type: Adjustable 9 settings

[Ig] ground-fault pick-up adjustment range: 0.2...1 x In; Ig enable on/off

Ground-fault time delay adjustment type -tg: Adjustable 5 settings

[tg] Ground-fault time delay adjustment range: 0…0.4 s

Earth-leakage protection: Without

Zone selective interlocking ZSI: With

Number of slots: 5 slot(s)

Local signalling: Flashing LED (green) for ready to operate; LED 95 % Ith (red) for temperature over set point

Display type: LCD display

type of measurement: Energy meter

Communication of data: Maximeters/minimeters; Time-stamped histories and event tables; Protection and alarm settings; Demand current and power; Energy metering; Power quality; Thermal image function; Maintenance indicators; Instantaneous and demand values; Phase sequence

Width: 105 mm

Height: 161 mm

Depth: 86 mm

Net weight: 2.4 kg

Compatibility code: NSX250

Environment

Standards: EN/IEC 60947

Product certifications: Marine; CCC; EAC

Overvoltage category: Class II

Electrical shock protection class: Class II

Pollution degree: 3 conforming to IEC 60664-1

IP degree of protection: IP40 conforming to IEC 60529

IK degree of protection: IK07 conforming to IEC 62262

Ambient air temperature for operation: -25…70 °C

Ambient air temperature for storage: -40…85 °C

Relative humidity: 0…95 %

Operating altitude: 0...2000 m without derating; 2000 m...5000 m with derating

Packing Units

Unit Type of Package 1: Db

Number of Units in Package 1: 1

Package 1 Height: 13.5 cm

Package 1 Width: 10.8 cm

Package 1 Length: 19.2 cm

Package 1 Weight: 2.082 kg

Offer Sustainability

Sustainable offer status: Green Premium product

EU RoHS Directive: Compliant

Mercury free: Yes

China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information

RoHS exemption information: Yes

Environmental Disclosure: ENVPEP120606EN

Circularity Profile: ENVEOLI120604EN

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

© 2018 Alplan Kft.