Schneider-Electric
LU2B32FU
Tariff code: 8536508090
Link to the manufacturers site: LU2B32FU - power base - TeSys U - 32 A - 110...220 V DC screw clamps control
Main
Range of produc: TeSys Ultra
Range: TeSys
Product name: TeSys Ultra
Device short name: LU2B
Product or component type: Reversing power base
Device application: Motor control; Motor protection
Product compatibility: Control unit LUC.X6FU; Control unit LUC.1XFU; Control unit LUC.05FU; Control unit LUC.12FU; Control unit LUC.18FU; Control unit LUC.32FU
Poles description: 3P
Suitability for isolation: Yes
[Ue] rated operational voltage: 690 V AC for power circuit
Network frequency: 40...60 Hz
[Ith] conventional free air thermal current: 32 A
[Ie] rated operational current: 28.5 A at <= 440 V; 23 A at 500 V; 21 A at 690 V
utilisation category: AC-43; AC-44; AC-41
[Ics] rated service breaking capacity: 50 kA at 230 V; 50 kA at 440 V; 10 kA at 500 V; 4 kA at 690 V
Auxiliary contact composition: 1 NO + 1 NC
Auxiliary contacts type: type linked contacts (1 NO + 1 NC) conforming to IEC 60947-4-1; type mirror contact (1 NC) conforming to IEC 60947-1
[Uc] control circuit voltage: 110...240 V AC 50/60 Hz; 110...220 V DC
Control circuit voltage limits: 55 V DC drop-out; 55 V AC drop-out; 88...242 V DC in operation; 88...264 V AC in operation
Complementary
Typical current consumption: 1000 mA at 110...220 V DC I maximum while closing; 1000 mA at 110...240 V AC I maximum while closing
Heat dissipation: 3 W for control circuit with LUCA, LUCB, LUCC, LUCD; 1.8 W for control circuit with LUCM
Inrush restraint duration: 25 ms AC 50/60 Hz; 15 ms DC
Safety reliability level: B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Operating time: 150 ms with change of direction for power circuit; 35 ms opening for control circuit; 75 ms without change of direction for power circuit; 50 ms closing for control circuit
Mechanical durability: 15 Mcycles
Maximum operating rate: 3600 cyc/h
product certifications: CE; UL; CSA; CCC; EAC; ASEFA; ATEX; Marine
Standards: EN 60947-6-2; IEC 60947-6-2; UL 60947-4-1, with phase barrier; CSA C22.2 No 60947-4-1, with phase barrier
[Ui] rated insulation voltage: 690 V conforming to IEC 60947-6-2 (pollution degree 3); 600 V conforming to UL 60947-4-1; 600 V conforming to CSA C22.2 No 60947-4-1
[Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947-6-2
Safe separation of circuit: 400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1 appendix N; 400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1 appendix N
Fixing mode: Clipped (DIN rail); Screw-fixed (plate)
Connections - terminals: Control circuit: screw clamp terminals 1 cable(s) 0.34…1.5 mm² flexible with cable end; Control circuit: screw clamp terminals 1 cable(s) 0.75…1.5 mm² flexible without cable end; Control circuit: screw clamp terminals 1 cable(s) 0.75…1.5 mm² rigid; Control circuit: screw clamp terminals 2 cable(s) 0.34…1.5 mm² flexible with cable end; Control circuit: screw clamp terminals 2 cable(s) 0.75…1.5 mm² flexible without cable end; Control circuit: screw clamp terminals 2 cable(s) 0.75…1.5 mm² rigid; Power circuit: screw clamp terminals 1 cable(s) 1…10 mm² rigid; Power circuit: screw clamp terminals 1 cable(s) 1…6 mm² flexible with cable end; Power circuit: screw clamp terminals 1 cable(s) 2.5…10 mm² flexible without cable end; Power circuit: screw clamp terminals 2 cable(s) 1…6 mm² flexible with cable end; Power circuit: screw clamp terminals 2 cable(s) 1…6 mm² rigid; Power circuit: screw clamp terminals 2 cable(s) 1.5…6 mm² flexible without cable end
Tightening torque: Control circuit: 0.8…1.2 N.m flat screwdriver 5 mm; Control circuit: 0.8…1.2 N.m Philips no 1 screwdriver 5 mm; Power circuit: 1.9…2.5 N.m flat screwdriver 6 mm; Power circuit: 1.9…2.5 N.m Philips No 2 screwdriver 6 mm; Power circuit: 1.9…2.5 N.m pozidriv No 2 screwdriver 6 mm
Width: 45 mm
height: 224 mm
Depth: 126 mm
Net weight: 1.27 kg
Compatibility code: LU2B
Environment
IP degree of protection: IP20 conforming to IEC 60947-1 (front panel and wired terminals); IP20 conforming to IEC 60947-1 (other faces); IP40 conforming to IEC 60947-1 (front panel outside connection zone)
Protective treatment: TH conforming to IEC 60068
Ambient air temperature for operation: -25…60 °C with LUCM; -25…70 °C with LUCA, LUCB, LUCC, LUCD
Ambient air temperature for storage: -40…85 °C
Fire resistance: 960 °C parts supporting live components conforming to IEC 60695-2-12; 650 °C conforming to IEC 60695-2-12
Operating altitude: 2000 m
Shock resistance: 10 gn power poles open conforming to IEC 60068-2-27; 15 gn power poles closed conforming to IEC 60068-2-27
Vibration resistance: 2 gn (f= 5…300 Hz) power poles open conforming to IEC 60068-2-27; 4 gn (f= 5…300 Hz) power poles closed conforming to IEC 60068-2-27
Resistance to electrostatic discharge: 8 kV level 3 in open air conforming to IEC 61000-4-2; 8 kV level 4 on contact conforming to IEC 61000-4-2
Resistance to radiated fields: 10 V/m 3 conforming to IEC 61000-4-3
Resistance to fast transients: 2 kV class 3 serial link conforming to IEC 61000-4-4; 4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4
Non-dissipating shock wave: 1 kV serial mode conforming to IEC 60947-6-2; 2 kV common mode conforming to IEC 60947-6-2
Immunity to radioelectric fields: 10 V conforming to IEC 61000-4-6
Immunity to microbreaks: 3 ms for control circuit
Immunity to voltage dips: 70 % / 500 ms conforming to IEC 61000-4-11
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 5.5 cm
Package 1 Width: 15.0 cm
Package 1 Length: 25.5 cm
Package 1 Weight: 1.307 kg
Unit Type of Package 2: S03
Number of Units in Package 2: 9
Package 2 Height: 30.0 cm
Package 2 Width: 30.0 cm
Package 2 Length: 40.0 cm
Package 2 Weight: 12.25 kg
Offer Sustainability
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Compliant with Exemptions
Mercury free: Yes
China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information
RoHS exemption information: Yes
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins