Schneider-Electric
LP1D40008BD
Tariff code: 8536490099
Link to the manufacturers site: LP1D40008BD - TeSys D contactor - 4P(2 NO + 2 NC) - AC-1 - <= 440 V 60 A - 24 V DC coil
Main
Range: TeSys
Range of produc: TeSys Deca
Product or component type: Contactor
Device short name: LP1D
contactor application: Resistive load
utilisation category: AC-1
Poles description: 4P
[Ue] rated operational voltage: Power circuit: <= 1000 V AC 25...400 Hz
[Ie] rated operational current: 60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage: 24 V DC
Complementary
Compatibility code: LP1D
Pole contact composition: 2 NO + 2 NC
Contact compatibility: M3
Protective cover: Without
[Ith] conventional free air thermal current: 60 A (at 60 °C) for power circuit
Irms rated making capacity: 800 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity: 800 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current: 72 A 40 °C - 10 min for power circuit; 165 A 40 °C - 1 min for power circuit; 320 A 40 °C - 10 s for power circuit; 720 A 40 °C - 1 s for power circuit
Associated fuse rating: 80 A gG at <= 690 V coordination type 1 for power circuit; 80 A gG at <= 690 V coordination type 2 for power circuit
Average impedance: 1.5 mOhm - Ith 60 A 50 Hz for power circuit
Power dissipation per pole: 5.4 W AC-1
[Ui] rated insulation voltage: Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified
Overvoltage category: III
Pollution degree: 3
[Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947
Safety reliability level: B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability: 10 Mcycles
Electrical durability: 1.4 Mcycles 60 A AC-1 at Ue <= 440 V
Control circuit type: DC DC standard
Coil technology: Built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits: 0.1...0.3 Uc (-40…70 °C):drop-out DC; 0.85...1.1 Uc (-40…55 °C):operational DC; 1...1.1 Uc (55…70 °C):operational DC
Inrush power in W: 22 W (at 20 °C)
Hold-in power consumption in W: 22 W at 20 °C
Operating time: 4...19 ms opening; 12...26 ms closing
Time constant: 75 ms
Maximum operating rate: 3600 cyc/h 60 °C
Connections - terminals: Power circuit: screw clamp terminals 1 2.5…25 mm² - cable stiffness: flexible without cable end; Power circuit: screw clamp terminals 2 2.5…16 mm² - cable stiffness: flexible without cable end; Power circuit: screw clamp terminals 1 2.5…25 mm² - cable stiffness: flexible with cable end; Power circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: flexible with cable end; Power circuit: screw clamp terminals 1 2.5…25 mm² - cable stiffness: solid; Power circuit: screw clamp terminals 2 2.5…16 mm² - cable stiffness: solid; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid; Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid
Tightening torque: Power circuit: 8 N.m - on screw clamp terminals - cable 25…35 mm² hexagonal screw head 4 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2; Power circuit: 5 N.m - on screw clamp terminals - cable 1…25 mm² hexagonal screw head 4 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
mounting support: Plate; Rail
Environment
Standards: CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 508
product certifications: UL; CSA; CCC; EAC; UKCA; CB; DNV-GL; RINA; BV; LROS (Lloyds register of shipping)
IP degree of protection: IP20 front face conforming to IEC 60529
Permissible ambient air temperature around the device: -40…60 °C; 60…70 °C with derating
Operating altitude: 0...3000 m
Fire resistance: 850 °C conforming to IEC 60695-2-1
Flame retardance: V1 conforming to UL 94
Mechanical robustness: Shocks contactor open (8 Gn for 11 ms) ; Shocks contactor closed (10 Gn for 11 ms) ; Vibrations contactor opened (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz)
height: 127 mm
Width: 85 mm
Depth: 182 mm
Net weight: 2.21 kg
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 11.0 cm
Package 1 Width: 16.2 cm
Package 1 Length: 21.8 cm
Package 1 Weight: 2.265 kg
Unit Type of Package 2: S02
Number of Units in Package 2: 2
Package 2 Height: 15 cm
Package 2 Width: 30 cm
Package 2 Length: 40 cm
Package 2 Weight: 4.828 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Free of Substances of Very High Concern above the threshold
REACh free of SVHC: Yes
EU RoHS Directive: Compliant
Toxic heavy metal free: Yes
Mercury free: Yes
China RoHS Regulation: Pro-active China RoHS declaration (out of China RoHS legal scope)
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP110205EN
Circularity Profile: N/A
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
PVC free: Yes
© 2018 Alplan Kft.