Schneider-Electric
LC3D120AU7
Tariff code:
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: LC3D120AU7 - TeSys D - star delta starter - 3 x 3P (3 NO) - 12 A - 240 V AC coil
Main
range of product: TeSys D
range: TeSys; TeSys Deca
product name: TeSys D; TeSys Deca
product or component type: Star delta starter
device short name: LC3D
contactor application: Motor control
utilisation category: AC-3
device presentation: Pre-wired
poles description: 3 x 3P
pole contact composition: 3 x 3 NO
[Ue] rated operational voltage: Power circuit: <= 690 V AC 25...400 Hz
[Ie] rated operational current: 12 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
motor power kW: 11 kW at 380/400 V AC 50/60 Hz; 11 kW at 415 V AC 50/60 Hz; 11 kW at 440 V AC 50/60 Hz; 5.5 kW at 220/230 V AC 50/60 Hz
control circuit type: AC at 50/60 Hz
[Uc] control circuit voltage: 240 V AC 50/60 Hz
auxiliary contact composition: 1 NC for KM1 star contactor
[Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947
overvoltage category: III
[Ui] rated insulation voltage: Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified; Power circuit: 1000 V conforming to IEC 60947-4-1; Signalling circuit: 1000 V conforming to IEC 60947-1
electrical durability: 2 Mcycles 12 A AC-3 at Ue <= 440 V
provided equipment: Protective cover
interlocking type: Mechanical
mounting support: Rail
standards: EN 60947-5-1; IEC 60947-4-1; UL 508; EN 60947-4-1; IEC 60947-5-1; CSA C22.2 No 14; IEC 60335-1
product certifications: GOST; CCC; GL; UL; CSA; BV; DNV; LROS (Lloyds register of shipping); RINA
Complementary
connections - terminals: Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end; Power circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end; Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end; Power circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end; Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end; Power circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end; Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
tightening torque: Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2; Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
mechanical durability: 15 Mcycles
maximum operating rate: 30 cyc/h 60 °C
starting time: 30 s
coil technology: Without built-in suppressor module
control circuit voltage limits: Drop-out: 0.3...0.6 Uc at 50/60 Hz (at <60 °C); Operational: 0.8...1.1 Uc at 50 Hz (at <60 °C); Operational: 0.85...1.1 Uc at 60 Hz (at <60 °C)
inrush power in VA: 70 VA 60 Hz cos phi 0.75 (at 20 °C); 70 VA 50 Hz cos phi 0.75 (at 20 °C)
hold-in power consumption in VA: 7.5 VA 60 Hz cos phi 0.3 (at 20 °C); 7 VA 50 Hz cos phi 0.3 (at 20 °C)
heat dissipation: 2…3 W at 50/60 Hz
auxiliary contacts type: Mechanically linked conforming to IEC 60947-5-1 3 x 1 NO + 1 NC; Mirror contact conforming to IEC 60947-4-1 3 x 1 NC
signalling circuit frequency: 25...400 Hz
minimum switching current: 5 mA for signalling circuit
switching voltage: 17 V for signalling circuit
non-overlap time: 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact
width: 143 mm
height: 124 mm
depth: 143 mm
net weight: 1.53 kg
Environment
insulation resistance: > 10 MOhm for signalling circuit
IP degree of protection: IP20 front face conforming to IEC 60529
protective treatment: TH conforming to IEC 60068-2-30
pollution degree: 3
ambient air temperature for storage: -60…80 °C
ambient air temperature for operation: -40…70 °C at Uc
operating altitude: 3000 m without derating
fire resistance: 850 °C conforming to IEC 60695-2-1
flame retardance: V1 conforming to UL 94
mechanical robustness: Vibrations contactor open: 2 Gn, 5...300 Hz; Vibrations contactor closed: 4 Gn, 5...300 Hz; Shocks contactor open: 10 Gn for 11 ms; Shocks contactor closed: 15 Gn for 11 ms
Offer Sustainability
REACh free of SVHC: Yes
EU RoHS Directive: Compliant
Toxic heavy metal free: Yes
Mercury free: Yes
RoHS exemption information: Yes
China RoHS Regulation: Pro-active China RoHS declaration (out of China RoHS legal scope)
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
PVC free: Yes
© 2018 Alplan Kft.