Schneider-Electric
LC2D25BD
Tariff code: 8536490099
Link to the manufacturers site: LC2D25BD - REVERSING CONTACTOR 575VAC 25A IEC
Main
Range of produc: TeSys Deca; TeSys Deca
Range: TeSys; TeSys Deca
Product name: TeSys Deca; TeSys Deca
Product or component type: Reversing contactor
Device short name: LC2D
contactor application: Resistive load; Motor control
utilisation category: AC-1; AC-3; AC-3e
device presentation: Preassembled with reversing power busbar
Poles description: 3P
Pole contact composition: 3 NO
[Ue] rated operational voltage: Power circuit: <= 690 V AC 25...400 Hz; Power circuit: <= 300 V DC
[Ie] rated operational current: 25 A (at <60 °C) at <= 440 V AC AC-3 for power circuit; 40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
Motor power kW: 5.5 kW at 220...230 V AC 50...60 Hz; 11 kW at 380...400 V AC 50...60 Hz; 11 kW at 415 V AC 50...60 Hz; 11 kW at 440 V AC 50...60 Hz; 15 kW at 500 V AC 50...60 Hz; 15 kW at 660...690 V AC 50...60 Hz
Motor power hp: 3 hp at 230/240 V AC 60 Hz for 1 phase motors; 5 hp at 200/208 V AC 60 Hz for 3 phases motors; 2 hp at 115 V AC 60 Hz for 1 phase motors; 7.5 hp at 230/240 V AC 60 Hz for 3 phases motors; 15 hp at 460/480 V AC 60 Hz for 3 phases motors; 20 hp at 575/600 V AC 60 Hz for 3 phases motors
Control circuit type: DC standard
[Uc] control circuit voltage: 24 V DC
Auxiliary contact composition: 1 NO + 1 NC
[Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947
Overvoltage category: III
[Ith] conventional free air thermal current: 10 A (at 60 °C) for signalling circuit; 40 A (at 60 °C) for power circuit
Irms rated making capacity: 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 450 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity: 450 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current: 50 A 40 °C - 10 min for power circuit; 120 A 40 °C - 1 min for power circuit; 240 A 40 °C - 10 s for power circuit; 380 A 40 °C - 1 s for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit
Associated fuse rating: 10 A gG for signalling circuit conforming to IEC 60947-5-1; 63 A gG at <= 690 V coordination type 1 for power circuit; 40 A gG at <= 690 V coordination type 2 for power circuit
Average impedance: 2 mOhm - Ith 40 A 50 Hz for power circuit
[Ui] rated insulation voltage: Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified
Electrical durability: 1.65 Mcycles 25 A AC-3 at Ue <= 440 V; 1.4 Mcycles 40 A AC-1 at Ue <= 440 V; 1.65 Mcycles 25 A AC-3e at Ue <= 440 V
Power dissipation per pole: 1.25 W AC-3; 3.2 W AC-1; 1.25 W AC-3e
Protective cover: With
Interlocking type: Mechanical
mounting support: Plate; Rail
Standards: CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 508; IEC 60335-1
product certifications: DNV; CSA; CCC; UL; GL; LROS (Lloyds register of shipping); BV; RINA; GOST; UKCA
Connections - terminals: Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end; Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end; Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end; Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end; Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid; Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid; Power circuit: screw clamp terminals 1 cable(s) 2.5…10 mm²flexible without cable end; Power circuit: screw clamp terminals 2 cable(s) 2.5…10 mm²flexible without cable end; Power circuit: screw clamp terminals 1 cable(s) 1…10 mm²flexible with cable end; Power circuit: screw clamp terminals 2 cable(s) 1.5…6 mm²flexible with cable end; Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm²solid; Power circuit: screw clamp terminals 2 cable(s) 2.5…10 mm²solid
Tightening torque: Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2; Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver Philips No 2; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2; Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Operating time: 53.55...72.45 ms closing; 16...24 ms opening
Safety reliability level: B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability: 30 Mcycles
Maximum operating rate: 3600 cyc/h 60 °C
Complementary
Coil technology: Built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits: 0.1...0.25 Uc (-40…70 °C):drop-out DC; 0.7...1.25 Uc (-40…60 °C):operational DC; 1...1.25 Uc (60…70 °C):operational DC
Time constant: 28 ms
Inrush power in W: 5.4 W (at 20 °C)
Hold-in power consumption in W: 5.4 W at 20 °C
Auxiliary contacts type: type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency: 25...400 Hz
Minimum switching current: 5 mA for signalling circuit
Minimum switching voltage: 17 V for signalling circuit
Non-overlap time: 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact
Insulation resistance: > 10 MOhm for signalling circuit
Contact compatibility: M4
Compatibility code: LC2D
Power range: 4…6 kW at 200…240 V 3 phases; 7…11 kW at 380…440 V 3 phases; 7…11 kW at 480…500 V 3 phases
Motor starter type: Reversing contactor
Contactor coil voltage: 24 V DC standard
Environment
IP degree of protection: IP20 front face conforming to IEC 60529
Climatic withstand: conforming to IACS E10; conforming to IEC 60947-1 Annex Q category D
Protective treatment: TH conforming to IEC 60068-2-30
Pollution degree: 3
Ambient air temperature for operation: -40…60 °C; 60…70 °C with derating
Ambient air temperature for storage: -60…80 °C
Operating altitude: 0...3000 m
Fire resistance: 850 °C conforming to IEC 60695-2-1
Flame retardance: V1 conforming to UL 94
Mechanical robustness: Vibrations contactor open: 2 Gn, 5...300 Hz; Vibrations contactor closed: 4 Gn, 5...300 Hz; Shocks contactor closed: 15 Gn for 11 ms; Shocks contactor open: 8 Gn for 11 ms
height: 85 mm
Width: 90 mm
Depth: 101 mm
Net weight: 1.117 kg
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 11.300 cm
Package 1 Width: 11.500 cm
Package 1 Length: 14.000 cm
Package 1 Weight: 1.019 kg
Unit Type of Package 2: S02
Number of Units in Package 2: 5
Package 2 Height: 15.000 cm
Package 2 Width: 30.000 cm
Package 2 Length: 40.000 cm
Package 2 Weight: 6.650 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Compliant with Exemptions
Mercury free: Yes
China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP110230EN
Circularity Profile: ENVEOLI1102030EN
PVC free: Yes
© 2018 Alplan Kft.