Skip to main content

Schneider-Electric
LC1F1504

TeSys F contactor - 4P(4 NO) - AC-1 - <= 440 V 250 A - without coil
Barcode: 3389110122374
Tariff code:

This product is discontinued.

Please contact us for possible replacement product options.

Link to the manufacturers site: LC1F1504 - TeSys F contactor - 4P(4 NO) - AC-1 - <= 440 V 250 A - without coil

Main

range of product: TeSys F

range: TeSys

product name: TeSys F

product or component type: Contactor

device short name: LC1F

contactor application: Resistive load

utilisation category: AC-1

poles description: 4P

pole contact composition: 4 NO

[Ue] rated operational voltage: <= 690 V AC 50/60 Hz; <= 460 V DC

[Ie] rated operational current: 250 A (at <40 °C) at <= 440 V AC-1

Complementary

[Uc] control circuit voltage: 24...575 V AC 40...400 Hz with LX1/LX9 coil; 24...460 V DC with LX4 coil; 100...250 V AC 50/60 Hz with LXE coil; 100...380 V DC with LXE coil

[Uimp] rated impulse withstand voltage: 8 kV

overvoltage category: III

[Ith] conventional free air thermal current: 250 A (at 40 °C)

Irms rated making capacity: 1500 A conforming to IEC 60947-4-1

rated breaking capacity: 1200 A conforming to IEC 60947-4-1

[Icw] rated short-time withstand current: 1200 A 40 °C - 10 s; 700 A 40 °C - 30 s; 600 A 40 °C - 1 min; 450 A 40 °C - 3 min; 350 A 40 °C - 10 min

associated fuse rating: 250 A gG at <= 440 V

average impedance: 0.35 mOhm - Ith 250 A 50 Hz

[Ui] rated insulation voltage: 1000 V conforming to IEC 60947-4-1; 1500 V conforming to VDE 0110 group C

control circuit voltage limits: Operational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coil; Drop-out: 0.2...0.55 Uc AC 40...400 Hz with LX1/LX9 coil; Operational: 0.85...1.1 Uc DC with LX4 coil; Drop-out: 0.15...0.2 Uc DC with LX4 coil; Operational: 85...275 V AC 50/60 Hz with LXE coil; Drop-out: 0...60 V AC 50/60 Hz with LXE coil; Operational: 85...418 V DC with LXE coil; Drop-out: 0...45 V DC with LXE coil

power dissipation per pole: 22 W AC-1

heat dissipation: 5.9…7.2 W; 2.2…2.5 W

operating time: 35 ms closing for with LX1/LX9 coil; 130 ms opening for with LX1/LX9 coil; 30...40 ms closing for with LX4 coil; 30...50 ms opening for with LX4 coil; 40...80 ms closing for with LXE coil; 6...54 ms opening for with LXE coil

mounting support: Plate

standards: EN 60947-1; JIS C8201-4-1; IEC 60947-1; IEC 60947-4-1; EN 60947-4-1

product certifications: ABS; CSA; BV; CB; RINA; RMRoS; DNV; LROS (Lloyds register of shipping); UL; UKCA

connections - terminals: Power circuit: lugs-ring terminals 1 cable(s) 120 mm² - busbar cross section: 25 x 3 mm; Power circuit: connector 1 cable(s) 120 mm²; Power circuit: bar 2 cable(s) ; Power circuit: bolted connection; Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end; Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible with cable end; Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end; Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end; Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²; Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²; Control circuit: screw clamp terminals 1.0 cable(s) 0.2…2.5 mm²flexible without cable end; Control circuit: screw clamp terminals 1.0 cable(s) 0.25…2.5 mm²flexible with cable end; Control circuit: screw clamp terminals 1.0 cable(s) 0.2…2.5 mm²solid without cable end

tightening torque: Power circuit: 18 N.m; Control circuit: 1.2 N.m; Control circuit: 0.6 N.m

mechanical durability: 10 Mcycles

inrush power in VA: 690…855 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil; 543…665 VA (at 20 °C)with LX4 coil; 280…310 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil; 270…320 VA (at 20 °C)with LXE coil

hold-in power consumption in VA: 6.6…8.1 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil; 3.94…4.83 VA (at 20 °C)with LX4 coil; 4.5…7.0 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil; 2.5…4.0 VA (at 20 °C)with LXE coil

maximum operating rate: 2400 cyc/h 55 °C

compatibility code: LC1F

Environment

IP degree of protection: IP2x front face with shrouds conforming to IEC 60529; IP2x front face with shrouds conforming to VDE 0106

protective treatment: TH

ambient air temperature for operation: -40…60 °C

ambient air temperature for storage: -60…80 °C

permissible ambient air temperature around the device: 60…70 °C at Uc

operating altitude: 3000 m without derating

mechanical robustness: Vibrations contactor open: 2 Gn, 5...300 Hz; Vibrations contactor closed: 6 Gn, 5...300 Hz; Shocks contactor open: 9 Gn for 1/2 sine wave (11 ms); Shocks contactor closed: 15 Gn for 1/2 sine wave (11 ms)

height: 170 mm

width: 200.5 mm

depth: 171 mm

net weight: 3.83 kg

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive: Compliant

Mercury free: Yes

RoHS exemption information: Yes

China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure: ENVPEP111201EN

Circularity Profile: ENVEOLI111214EN_V1

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

© 2018 Alplan Kft.