Skip to main content

Schneider-Electric
LC1D65008Q7

TeSys D contactor - 4P(2 NO + 2 NC) - AC-1 <= 440 V 80 A 380 V AC 50/60 Hz coil
Barcode: 3389110073140
Tariff code:

This product is discontinued.

Please contact us for possible replacement product options.

Link to the manufacturers site: LC1D65008Q7 - TeSys D contactor - 4P(2 NO + 2 NC) - AC-1 <= 440 V 80 A 380 V AC 50/60 Hz coil

Main

range of product: TeSys D

range: TeSys

product name: TeSys D

product or component type: Contactor

device short name: LC1D

contactor application: Resistive load

utilisation category: AC-1

poles description: 4P

pole contact composition: 2 NO + 2 NC

[Ue] rated operational voltage: Power circuit: <= 690 V AC 25...400 Hz; Power circuit: <= 300 V DC

[Ie] rated operational current: 80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit

control circuit type: AC at 50/60 Hz

[Uc] control circuit voltage: 380 V AC 50/60 Hz

[Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947

overvoltage category: III

[Ith] conventional free air thermal current: 80 A (at 60 °C) for power circuit

Irms rated making capacity: 1000 A at 440 V for power circuit conforming to IEC 60947

rated breaking capacity: 1000 A at 440 V for power circuit conforming to IEC 60947

[Icw] rated short-time withstand current: 520 A 40 °C - 10 s for power circuit; 900 A 40 °C - 1 s for power circuit; 110 A 40 °C - 10 min for power circuit; 260 A 40 °C - 1 min for power circuit

associated fuse rating: 125 A gG at <= 690 V coordination type 1 for power circuit; 125 A gG at <= 690 V coordination type 2 for power circuit

average impedance: 1.5 mOhm - Ith 80 A 50 Hz for power circuit

[Ui] rated insulation voltage: Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Power circuit: 690 V conforming to IEC 60947-4-1

electrical durability: 1.4 Mcycles 80 A AC-1 at Ue <= 440 V

power dissipation per pole: 9.6 W AC-1

protective cover: Without

mounting support: Rail; Plate

standards: CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 508

product certifications: CCC; CSA; RINA; GL; DNV; GOST; LROS (Lloyds register of shipping); UL; BV

connections - terminals: Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end; Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end; Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end; Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end; Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end; Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end; Power circuit: screw clamp terminals 1 cable(s) 1…35 mm²flexible without cable end; Power circuit: screw clamp terminals 2 cable(s) 1…25 mm²flexible without cable end; Power circuit: screw clamp terminals 1 cable(s) 1…35 mm²flexible with cable end; Power circuit: screw clamp terminals 2 cable(s) 1…25 mm²flexible with cable end; Power circuit: screw clamp terminals 1 cable(s) 1…35 mm²solid without cable end; Power circuit: screw clamp terminals 2 cable(s) 1…25 mm²solid without cable end

tightening torque: Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2; Power circuit: 8 N.m - on screw clamp terminals - cable 25…35 mm² hexagonal screw head 4 mm; Power circuit: 5 N.m - on screw clamp terminals - cable 1…25 mm² hexagonal screw head 4 mm

operating time: 4...19 ms opening; 12...26 ms closing

safety reliability level: B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

mechanical durability: 6 Mcycles

maximum operating rate: 3600 cyc/h 60 °C

Complementary

coil technology: Without built-in suppressor module

control circuit voltage limits: 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz; 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz

inrush power in VA: 140 VA 60 Hz cos phi 0.75 (at 20 °C); 160 VA 50 Hz cos phi 0.75 (at 20 °C)

hold-in power consumption in VA: 13 VA 60 Hz cos phi 0.3 (at 20 °C); 15 VA 50 Hz cos phi 0.3 (at 20 °C)

heat dissipation: 4…5 W at 50/60 Hz

contact compatibility: M1

compatibility code: LC1D

Environment

IP degree of protection: IP20 front face conforming to IEC 60529

protective treatment: TH conforming to IEC 60068-2-30

pollution degree: 3

ambient air temperature for operation: -40…60 °C; 60…70 °C with derating

ambient air temperature for storage: -60…80 °C

operating altitude: 0...3000 m

fire resistance: 850 °C conforming to IEC 60695-2-1

flame retardance: V1 conforming to UL 94

mechanical robustness: Vibrations contactor open: 2 Gn, 5...300 Hz; Vibrations contactor closed: 4 Gn, 5...300 Hz; Shocks contactor closed: 15 Gn for 11 ms; Shocks contactor open: 10 Gn for 11 ms

height: 127 mm

width: 85 mm

depth: 125 mm

net weight: 1.45 kg

Offer Sustainability

Sustainable offer status: Green Premium product

REACh free of SVHC: Yes

EU RoHS Directive: Compliant

Toxic heavy metal free: Yes

Mercury free: Yes

RoHS exemption information: Yes

China RoHS Regulation:  Pro-active China RoHS declaration (out of China RoHS legal scope)

Environmental Disclosure: ENVPEP1503009EN

Circularity Profile: ENVEOLI1503009EN

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

PVC free: Yes

© 2018 Alplan Kft.