Schneider-Electric
K50D002UP
Tariff code: 8536508090
Link to the manufacturers site: K50D002UP - cam changeover switch - 2-pole - 60° - 50 A - screw mounting
Main
Range of produc: Harmony K
Product or component type: Complete cam switch
component name: K50
[Ith] conventional free air thermal current: 50 A
Mounting location: Front
Fixing mode: 4 holes
Cam switch head type: With front plate 64 x 64 mm
Type of operator: Black handle
Rotary handle padlocking: Without
Presentation of legend: With metallic legend, 1 - 0 - 2 black marking
Cam switch function: Changeover switch
Return: Without
Off position: With Off position
Poles description: 2P
Switching positions: Left: 0° - 300°; Right: 0° - 60°
IP degree of protection: IP40 conforming to IEC 60529
Complementary
Switching angle: 60 °
[Ui] rated insulation voltage: 690 V (pollution degree 3) conforming to IEC 60947-1
Short-circuit current: 5000 A
Short-circuit protection: 63 A cartridge fuse, type gG
[Uimp] rated impulse withstand voltage: 6 kV conforming to EN 947-1; 6 kV conforming to IEC 947-1
contact operation: Slow-break
Positive opening: With
Electrical connection: Captive screw clamp terminals flexible, clamping capacity: 2 x 6 mm²; Captive screw clamp terminals solid, clamping capacity: 2 x 10 mm²
Tightening torque: 2 N.m
Switching capacity in mA: 15000 mA DC at 120 V 2 contact(s) for inductive load (T = 50 ms); 15000 mA DC at 180 V 3 contact(s) for inductive load (T = 50 ms); 15000 mA DC at 60 V 1 contact(s) for inductive load (T = 50 ms); 20000 mA DC at 140 V 3 contact(s) for inductive load (T = 50 ms); 20000 mA DC at 48 V 1 contact(s) for inductive load (T = 50 ms); 20000 mA DC at 95 V 2 contact(s) for inductive load (T = 50 ms); 30000 mA DC at 30 V 1 contact(s) for inductive load (T = 50 ms); 30000 mA DC at 60 V 2 contact(s) for inductive load (T = 50 ms); 30000 mA DC at 90 V 3 contact(s) for inductive load (T = 50 ms); 3500 mA DC at 110 V 1 contact(s) for inductive load (T = 50 ms); 3500 mA DC at 220 V 2 contact(s) for inductive load (T = 50 ms); 3500 mA DC at 330 V 3 contact(s) for inductive load (T = 50 ms); 37000 mA DC at 120 V 2 contact(s) for resistive load (T = 1 ms); 37000 mA DC at 180 V 3 contact(s) for resistive load (T = 1 ms); 37000 mA DC at 60 V 1 contact(s) for resistive load (T = 1 ms); 40000 mA DC at 140 V 3 contact(s) for resistive load (T = 1 ms); 40000 mA DC at 24 V 1 contact(s) for inductive load (T = 50 ms); 40000 mA DC at 48 V 1 contact(s) for resistive load (T = 1 ms); 40000 mA DC at 48 V 2 contact(s) for inductive load (T = 50 ms); 40000 mA DC at 70 V 3 contact(s) for inductive load (T = 50 ms); 40000 mA DC at 95 V 2 contact(s) for resistive load (T = 1 ms); 50000 mA DC at 24 V 1 contact(s) for resistive load (T = 1 ms); 50000 mA DC at 48 V 2 contact(s) for resistive load (T = 1 ms); 50000 mA DC at 70 V 3 contact(s) for resistive load (T = 1 ms)
Mechanical durability: 300000 cycles
CAD overall width: 64 mm
CAD overall height: 64 mm
CAD overall depth: 103 mm
Net weight: 0.305 kg
Compatibility code: K50D
Environment
Standards: IEC 60947-3
Product certifications: CULus 120 V 3 hp 1 phase; CULus 480 V 25 hp 3 phases; CULus 240 V 7.5 hp 1 phase; CULus 240 V 7.5 hp 3 phases
Protective treatment: TC
ambient air temperature for operation: -25…55 °C
Ambient air temperature for storage: -40…70 °C
Overvoltage category: Class II conforming to IEC 60536; Class II conforming to NF C 20-030
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 11.500 cm
Package 1 Width: 7.200 cm
Package 1 Length: 7.200 cm
Package 1 Weight: 283.900 g
Unit Type of Package 2: S03
Number of Units in Package 2: 30
Package 2 Height: 30.000 cm
Package 2 Width: 30.000 cm
Package 2 Length: 40.000 cm
Package 2 Weight: 9.233 kg
Offer Sustainability
REACh Regulation: Free of Substances of Very High Concern above the threshold
REACh free of SVHC: Yes
EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)
Toxic heavy metal free: Yes
Mercury free: Yes
China RoHS Regulation: X
RoHS exemption information: Yes
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins