Skip to main content

Schneider-Electric
GS1LLD3

TeSys GS - switch-disconnector fuse - 3 P - 160 A - DIN 00
Barcode: 3389110253986
Tariff code:

This product is discontinued.

Please contact us for possible replacement product options.

Link to the manufacturers site: GS1LLD3 - TeSys GS - switch-disconnector fuse - 3 P - 160 A - DIN 00

Main

range: TeSys

product name: TeSys GS

device short name: GS1 L

product or component type: Switch-disconnector-fuse

device application: Protection

poles description: 3P

protected poles description: 3t

contacts type and composition: 3 NO

[Ith] conventional free air thermal current: 160 A (at 40 °C)

[Ie] rated operational current: 125 A at 440 V 2 poles in series per phase DC-23A; 125 A at 440 V 2 poles in series per phase DC-23B; 125 A at 690 V with terminal cover AC-23A; 125 A at 690 V with terminal cover AC-23B; 160 A at 400 V AC-23A; 160 A at 400 V AC-23B; 160 A at 500 V AC-23A; 160 A at 500 V AC-23B

fuse type: DIN

fuse size: 00

network type: AC; DC

network frequency: 50/60 Hz

Complementary

type of operating handle: Direct right side

mounting support: Plate

[Ui] rated insulation voltage: 750 V AC 50/60 Hz

[Uimp] rated impulse withstand voltage: 8 kV

rated operational power in W: 90 kW at 400 V; 110 kW at 500 V; 110 kW at 690 V

making capacity: 1600 A at 400 V AC-23B

[Icm] rated short-circuit making capacity: 100 kA at 400 V with protection by gG fuses

breaking capacity: 1280 A at 400 V (AC-23B)

short-circuit withstand: 22.7 kA

mechanical durability: 10000 cycles

electrical durability: 1000 cycles AC-23A; 1000 cycles AC-23B; 200 cycles DC-23A; 200 cycles DC-23B

connections - terminals: Power circuit: bars; Power circuit: lugs-ring terminals50…95 mm² flexible

tightening torque: Power circuit: 12 N.m - on bars; Power circuit: 12 N.m - on lugs-ring terminals

compatibility code: GS1 L

Environment

standards: IEC 60947-3

product certifications: CE

protective treatment: TH

IP degree of protection: IP20 conforming to IEC 60529 (with terminal cover)

ambient air temperature for operation: -20…70 °C

ambient air temperature for storage: -40…80 °C

fire resistance: 850 °C fuse cover conforming to IEC 60695-2-1; 960 °C body conforming to IEC 60695-2-1

height: 162 mm

width: 150 mm

depth: 126.5 mm

net weight: 1.8 kg

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Free of Substances of Very High Concern above the threshold

REACh free of SVHC: Yes

EU RoHS Directive: Compliant

Toxic heavy metal free: Yes

Mercury free: Yes

RoHS exemption information: Yes

China RoHS Regulation: X

Environmental Disclosure: ENVPEP2003007EN

Circularity Profile: ENVEOLI2003007EN