Schneider-Electric
CA3KN40ED
Tariff code: 8536419089
Link to the manufacturers site: CA3KN40ED - TeSys K control relay - 4 NO - <= 690 V - 48 V DC standard coil
Main
Range of produc: TeSys K control relay
Range: TeSys
Product name: TeSys CAK
Product or component type: Control relay
Device short name: CA3K
contactor application: Control circuit
utilisation category: AC-15; DC-13
Pole contact composition: 4 NO
[Ue] rated operational voltage: <= 690 V <= 400 Hz
Control circuit type: DC standard
[Uc] control circuit voltage: 48 V DC
Complementary
[Ith] conventional free air thermal current: 10 A (at 50 °C)
Irms rated making capacity: 110 A conforming to IEC 60947
Associated fuse rating: 10 A gG conforming to IEC 60947; 10 A gG conforming to VDE 0660
[Ui] rated insulation voltage: 690 V conforming to IEC 60947; 750 V conforming to VDE 0110 group C; 690 V conforming to BS 5424; 600 V conforming to CSA C22.2 No 14
mounting support: Plate; Rail
Connections - terminals: Screw clamp terminals 1 cable(s) 1.5…4 mm²solid; Screw clamp terminals 2 cable(s) 1.5…4 mm²solid; Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 0.34…1.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible without cable end
Tightening torque: 1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; 1.3 N.m - on screw clamp terminals - with screwdriver Philips No 26 mm; 1.3 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Control circuit voltage limits: Operational: 0.8...1.15 Uc (at <50 °C); Drop-out: 0.1...0.75 Uc (at <50 °C)
Operating time: 10 ms coil de-energisation and NO opening; 30...40 ms coil energisation and NO closing
Mechanical durability: 20 Mcycles
Maximum operating rate: 10000 cyc/h
Immunity to microbreaks: 2 ms
Inrush power in W: 3 W (at 20 °C)
Hold-in power consumption in W: 3 W at 20 °C
Heat dissipation: 3 W
Minimum switching voltage: 17 V
Minimum switching current: 5 mA
Non overlap distance: 0.5 mm
Insulation resistance: > 10 MOhm
height: 58 mm
Width: 45 mm
Depth: 57 mm
Net weight: 0.225 kg
Compatibility code: CA3K
Environment
Standards: EN/IEC 60947-4-1; GB/T 14048.4; UL 60947-4-1; CSA C22.2 No 60947-4-1; JIS C8201-4-1
product certifications: CB Scheme; CCC; UL; CSA; EAC; CE; UKCA
IP degree of protection: IP2X
Protective treatment: TC conforming to IEC 60068
ambient air temperature for operation: -25…50 °C
Ambient air temperature for storage: -50…80 °C
Operating altitude: 2000 m without derating
Flame retardance: V1 conforming to UL 94; Requirement 2 conforming to NF F 16-101; Requirement 2 conforming to NF F 16-102
Mechanical robustness: Vibrations contactor open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6; Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6; Shocks contactor open: 10 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor closed: 15 Gn for 11 ms conforming to IEC 60068-2-27
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 4.7 cm
Package 1 Width: 6.2 cm
Package 1 Length: 6.5 cm
Package 1 Weight: 218.0 g
Unit Type of Package 2: S02
Number of Units in Package 2: 40
Package 2 Height: 15.0 cm
Package 2 Width: 30.0 cm
Package 2 Length: 40.0 cm
Package 2 Weight: 9.163 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Free of Substances of Very High Concern above the threshold
REACh free of SVHC: Yes
EU RoHS Directive: Compliant
Toxic heavy metal free: Yes
Mercury free: Yes
China RoHS Regulation: Pro-active China RoHS declaration (out of China RoHS legal scope)
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP1503003EN
Circularity Profile: ENVEOLI1503003EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
© 2018 Alplan Kft.