Schneider-Electric
18280
Tariff code: 8536201090
Link to the manufacturers site: 18280 - RCCB with re-closer - REDtest - 2 poles - 25 A - class A - 30 mA
Main
Range of produc: RED
Range: Acti9
Product or component type: Residual current circuit breaker (RCCB)
Device short name: REDtest
Protection type: Recloser
Poles description: 2P
Neutral position: Right
Signal contacts composition: 1NO or intermittent 1 Hz
[In] rated current: 25 A
Earthing system: TT; TN-S
Network type: AC
Earth-leakage sensitivity: 30 mA
Complementary
device location in system: Outgoer
Network frequency: 50 Hz
[Ue] rated operational voltage: 230 V AC 50 Hz phase to neutral
Reset: Fault reset earth leakage
Test function: Auto test 0...300 s; Manual at > 195 V
earth-leakage protection time delay: Instantaneous
Earth-leakage protection class: Type A
Minimum leakage resistance: 70 kOhm at operating; 20 kOhm at non-operating
[Im] rated making and breaking capacity: Idm 630 A 230 V
Rated conditional short-circuit current: Inc: 6 kA - associated with DPN, 40 A; Inc: 6 kA - associated with DPNN, 40 A; Inc: 6 kA - associated with iC60N, 25 A; Inc: 6 kA - associated with iC60H, 25 A; Inc: 6 kA - associated with iC60L, 25 A; Inc: 6 kA - associated with NG125, 25 A; Inc: 6 kA - associated with gG fuse, 25 A
[Ui] rated insulation voltage: 500 V
[Uimp] rated impulse withstand voltage: 4 kV
Surge current: 250 A
control type: Toggle
Local signalling: 2 LEDs; Residual current device : ON/OFF indication; Recloser : ON/OFF indication
Operating mode: Reclosing time: < 10 s; Max nb of consecutive restart: 3; Min interval between 2 closings: 180 s; Stopping restart cycle if insulation fault present; Insulation fault presence monitoring
Insulation fault diagnosis: If fault detected, diagnosis stopped
Signalling circuit voltage: AC: 12...230 V
Signalling output current: 0.6 mA min; 100 mA max, cos phi =1
Mounting mode: Fixed
mounting support: 35 mm symmetrical DIN rail
9 mm pitches: 10
height: 115 mm
Width: 89.2 mm
Depth: 79.5 mm
Net weight: 0.37 kg
Mechanical durability: 1000 cycles open-close
Connections - terminals: Guard tunnel terminal 35 mm² rigid; Guard tunnel terminal 35 mm² flexible; Guard tunnel terminal 35 mm² flexible with ferrule
Auxiliary connection terminal: Tunnel type terminal in 2.5 mm² flexible; Tunnel type terminal in 2.5 mm² rigid; Tunnel type terminal in 2.5 mm² flexible with ferrule
Wire stripping length: Power circuit: 12 mm; Signaling: 5 mm
Tightening torque: Power circuit: 2 N.m; Signaling: 0.5 N.m
Market segment: Small commercial
Compatibility code: REDtest
Environment
Standards: EN 61008; IEC 61008
IP degree of protection: IP20
Pollution degree: 2
Electromagnetic compatibility: 8/20 µs wave immunity, 250 A
Tropicalisation: 2
Relative humidity: 95 % at 55 °C
ambient air temperature for operation: -5…40 °C
Ambient air temperature for storage: -20…60 °C
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 12.3 cm
Package 1 Width: 15.0 cm
Package 1 Length: 17.2 cm
Package 1 Weight: 635.0 g
Unit Type of Package 2: S03
Number of Units in Package 2: 8
Package 2 Height: 30.0 cm
Package 2 Width: 30.0 cm
Package 2 Length: 40.0 cm
Package 2 Weight: 5.65 kg
Offer Sustainability
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Compliant with Exemptions
China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information
RoHS exemption information: Yes
Circularity Profile: N/A
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins