Schneider-Electric
ATV320U15M2W
Tariff code: 8504409590
Link to the manufacturers site: ATV320U15M2W - Altivar Machine ATV320 frekvenciaváltó, 1,5kW, 1f, 230VAC, Modbus/CANopen, IP66, szakaszoló kapcsoló nélkül
Main
Range of product: Altivar Machine ATV320
Product or component type: Variable speed drive
Product specific application: Complex machines
Variant: Standard version
Format of the drive: Enclosed
Network number of phases: Single phase
Design of frequency changer: U converter
Mounting mode: Wall mount
communication port protocol: Modbus serial; CANopen
Option card: Communication module, CANopen; Communication module, EtherCAT; Communication module, Profibus DP V1; Communication module, PROFINET; Communication module, Ethernet Powerlink; Communication module, EtherNet/IP; Communication module, DeviceNet
[Us] rated supply voltage: 200...240 V - 15...10 %
[Us] rated supply voltage: 200...240 V
Relative symmetric mains voltage tolerance: 10 %
Nominal output current: 8.0 A
Number of input phases: 1
Number of output phases: 1
Motor power kW: 1.5 kW for heavy duty
EMC filter: Class C2 EMC filter integrated
IP degree of protection: IP66
Complementary
Discrete input number: 7
Discrete input type: STO safe torque off, 24 V DC, impedance: 1.5 kOhm; DI1...DI6 logic inputs, 24 V DC (30 V); DI5 programmable as pulse input: 0…30 kHz, 24 V DC (30 V)
Discrete input logic: Positive logic (source); Negative logic (sink)
Discrete output number: 3
Discrete output type: Open collector DQ+ 0…1 kHz 30 V DC 100 mA; Open collector DQ- 0…1 kHz 30 V DC 100 mA
Analogue input number: 3
Analogue input type: AI1 voltage: 0...10 V DC, impedance: 30 kOhm, resolution 10 bits; AI2 bipolar differential voltage: +/- 10 V DC, impedance: 30 kOhm, resolution 10 bits; AI3 current: 0...20 mA (or 4-20 mA, x-20 mA, 20-x mA or other patterns by configuration), impedance: 250 Ohm, resolution 10 bits
Analogue output number: 1
Analogue output type: Software-configurable current AQ1: 0...20 mA impedance 800 Ohm, resolution 10 bits; Software-configurable voltage AQ1: 0...10 V DC impedance 470 Ohm, resolution 10 bits
Relay output type: Configurable relay logic R1A 1 NO electrical durability 100000 cycles; Configurable relay logic R1B 1 NC electrical durability 100000 cycles; Configurable relay logic R1C; Configurable relay logic R2A 1 NO electrical durability 100000 cycles; Configurable relay logic R2C
Number of inputs, bidirectional, not potential-free: 0
Number of inputs, potential-free: 0
Maximum switching current: Relay output R1A, R1B, R1C on resistive load, cos phi = 1: 3 A at 250 V AC; Relay output R1A, R1B, R1C on resistive load, cos phi = 1: 3 A at 30 V DC; Relay output R1A, R1B, R1C, R2A, R2C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC; Relay output R1A, R1B, R1C, R2A, R2C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC; Relay output R2A, R2C on resistive load, cos phi = 1: 5 A at 250 V AC; Relay output R2A, R2C on resistive load, cos phi = 1: 5 A at 30 V DC
Minimum switching current: Relay output R1A, R1B, R1C, R2A, R2C: 5 mA at 24 V DC
Encoder protocol: RS 422
Computer port: True
Optical interface present: False
Method of access: Slave CANopen
Number of HW interfaces parallel: 0.0
Number of HW interfaces industrial Ethernet: 0.0
Number of HW interfaces PROFINET: 0.0
Number of HW interfaces serial RS232: 0.0
Number of HW interfaces serial RS422: 0.0
Number of HW interfaces serial RS485: 1.0
Number of HW interfaces serial TTY: 0.0
Number of HW interfaces USB: 0.0
Number of HW interfaces other: 1.0
Supporting protocol for AS-Interface Safety at Work: False
Supporting protocol for ASI: False
Supporting protocol for SUCONET: False
Supporting protocol for BACnet: False
Supporting protocol for CAN: True
Supporting protocol for Data-Highway: False
Supporting protocol for DeviceNet: True
Supporting protocol for DeviceNet Safety: False
Supporting protocol for EtherNet/IP: True
Supporting protocol for Foundation Fieldbus: False
Supporting protocol for INTERBUS: False
Supporting protocol for INTERBUS-Safety: False
Supporting protocol for KNX: False
Supporting protocol for LON: False
Supporting protocol for MODBUS: True
Supporting protocol for other bus systems: True
Supporting protocol for PROFIBUS: True
Supporting protocol for PROFINET CBA: False
Supporting protocol for PROFINET IO: True
Supporting protocol for PROFIsafe: False
Supporting protocol for SafetyBUS P: False
Supporting protocol for SERCOS: False
Supporting protocol for TCP/IP: True
4 quadrant operation possible: True
Asynchronous motor control profile: Voltage/frequency ratio, 5 points; Flux vector control without sensor, standard; Voltage/frequency ratio - Energy Saving, quadratic U/f; Flux vector control without sensor - Energy Saving; Voltage/frequency ratio, 2 points
Synchronous motor control profile: Vector control without sensor
Transient overtorque: 170…200 % of nominal motor torque
Maximum output frequency: 0.599 kHz
Acceleration and deceleration ramps: Linear; U; S; CUS; Ramp switching; Acceleration/deceleration ramp adaptation; Acceleration/deceleration automatic stop with DC injection
Motor slip compensation: Automatic whatever the load; Adjustable 0...300 %; Not available in voltage/frequency ratio (2 or 5 points)
Switching frequency: 2...16 kHz adjustable; 4...16 kHz with derating factor
Nominal switching frequency: 4 kHz
Braking to standstill: By DC injection
Brake chopper integrated: True
Maximum associated fuse rating: 40 A
Line current: 17.8 A at 200 V (heavy duty); 14.9 A at 240 V (heavy duty)
Maximum input current: 17.8 A
Maximum output voltage: 240 V
Nominal output power: 1.5 kW
Apparent power: 3.6 kVA at 240 V (heavy duty)
Capacity of DC link: 1410 µF
Network frequency: 50...60 Hz
Relative symmetric network frequency tolerance: 5 %
Prospective line Isc: 1 kA
1 phase low current possible: False
Base load current at high overload: 6.9 A
Application in domestic and commercial area permitted: False
Application in industrial area permitted: True
EMC limit value (complied): True
Power loss per device current dependent: 76.0 W
Power loss static current independent: 76.0 W
Power dissipation in W: Self-cooled: 76.0 W at 200 V, switching frequency 4 kHz
Housing material: Plastic
With safety function Safely Limited Speed (SLS): True
With safety function Safe brake management (SBC/SBT): False
With safety function Safe Operating Stop (SOS): False
With safety function Safe Position (SP): False
With safety function Safe programmable logic: False
With safety function Safe Speed Monitor (SSM): False
With safety function Safe Stop 1 (SS1): True
With sft fct Safe Stop 2 (SS2): False
With safety function Safe torque off (STO): True
With safety function Safely Limited Position (SLP): False
With safety function Safe Direction (SDI): False
Protection type: Input phase breaks: drive; Overcurrent between output phases and earth: drive; Overheating protection: drive; Short-circuit between motor phases: drive; Thermal protection: drive
Operating element present: True
Width: 250 mm
Height: 340 mm
Depth: 235.0 mm
Net weight: 7.4 kg
Linearity error: AI1, AI2, AI3: +/- 0.2...0.5 % of maximum value for analog input; AQ1: +/- 0.3 % for analog output
Accuracy: +/- 0.7 % AI1, AI2, AI3 for a temperature of -10...60 °C analog input; +/- 0.5 % AI1, AI2, AI3 for a temperature of 25 °C analog input; +/- 1 % AQ1 for a temperature of 25 °C analog output; +/- 2 % AQ1 for a temperature of -10...60 °C analog output
Sampling duration: 2 ms (AI1, AI2, AI3) - analog input; 2 ms (AQ1) - analog output
Refresh time: Logic input (DI1...DI4): 8 ms; Relay output (R1A, R1B, R1C): 2 ms; Relay output (R2A, R2C): 2 ms
Environment
NEMA degree of protection: NEMA 4X
Operating position: Vertical +/- 10 degree
Product certifications: CE; ATEX; NOM; GOST; EAC; RCM; KC
Marking: CE; ATEX; UL; CSA; EAC; RCM
Standards: IEC 61800-5-1
Electromagnetic compatibility: Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2; Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3; Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4; 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5; Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6; Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
Environmental class (during operation): Class 3C3 according to IEC 60721-3-3; Class 3S2 according to IEC 60721-3-3
Environmental class (during storage): Class 1C3 according to EN 60721-3; Class 1S2 according to EN 60721-3
Environmental class (during transport): Class 2C3 according to EN 60721-3; Class 2S1 according to EN 60721-3
Maximum acceleration under shock impact (during operation): 150 m/s² at 11 ms
Maximum acceleration under shock load (during storage): 150 m/s² at 11 ms
Maximum acceleration under shock load (during transport): 150 m/s² at 11 ms
Maximum acceleration under vibratory load (during storage): 10 m/s² at 13...200 Hz
Maximum acceleration under vibratory load (during transport): 10 m/s² at 13...200 Hz
Maximum acceleration under vibrational stress (during operation): 10 m/s² at 13...200 Hz
Maximum deflection under vibratory load (during storage): 3.5 mm at 2...13 Hz
Maximum deflection under vibratory load (during transport): 3.5 mm at 2...13 Hz
Maximum deflection under vibratory load (during operation): 1.5 mm at 2...13 Hz
Permitted relative humidity (during operation): Class 3K5 according to EN 60721-3
Permitted relative humidity (during storage): Class 1K5 according to EN 60721-3
Permitted relative humidity (during transport): Class 2K5 according to EN 60721-3
Overvoltage category: III
Regulation loop: Adjustable PID regulator
Speed accuracy: +/- 10 % of nominal slip 0.2 Tn to Tn
Pollution degree: 3
Ambient air transport temperature: -25…70 °C
Ambient air temperature for operation: -10…40 °C without derating; 40…60 °C with derating factor
Ambient air temperature for operation: -10…60 °C
Ambient air temperature for storage: -25…70 °C
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 29.300 cm
Package 1 Width: 30.500 cm
Package 1 Length: 45.000 cm
Package 1 Weight: 9.899 kg
Unit Type of Package 2: S06
Number of Units in Package 2: 4
Package 2 Height: 77.000 cm
Package 2 Width: 60.000 cm
Package 2 Length: 80.000 cm
Package 2 Weight: 48.000 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free: Yes
China RoHS Regulation: X
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP1908003EN
Circularity Profile: ENVEOLI1908003EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
© 2018 Alplan Kft.