Skip to main content

Schneider-Electric
LC1F4002

TeSys F contactor - 2P(2 NO) - AC-1 - <= 440 V 500 A - without coil
Barcode: 3389110227000
Tariff code:

This product is discontinued.

Please contact us for possible replacement product options.

Link to the manufacturers site: LC1F4002 - TeSys F contactor - 2P(2 NO) - AC-1 - <= 440 V 500 A - without coil

Main

range of product: TeSys F

range: TeSys

product name: TeSys F

product or component type: Contactor

device short name: LC1F

contactor application: Resistive load

utilisation category: AC-1

poles description: 2P

pole contact composition: 2 NO

[Ue] rated operational voltage: <= 1000 V AC 50/60 Hz; <= 460 V DC

[Ie] rated operational current: 500 A (at <40 °C) at <= 440 V AC AC-1

Complementary

[Uc] control circuit voltage: 48...1000 V AC 40...400 Hz with LX1/LX9 coil; 48...440 V DC with LX4 coil; 100...250 V AC 50/60 Hz with LXE coil; 100...380 V DC with LXE coil

[Uimp] rated impulse withstand voltage: 8 kV

overvoltage category: III

[Ith] conventional free air thermal current: 500 A (at 40 °C)

Irms rated making capacity: 4000 A AC conforming to IEC 60947-4-1

rated breaking capacity: 3200 A conforming to IEC 60947-4-1

[Icw] rated short-time withstand current: 3600 A 40 °C - 10 s; 2400 A 40 °C - 30 s; 1700 A 40 °C - 1 min; 1200 A 40 °C - 3 min; 1000 A 40 °C - 10 min

associated fuse rating: 400 A aM at <= 440 V; 500 A gG at <= 440 V

average impedance: 0.26 mOhm - Ith 500 A 50 Hz

[Ui] rated insulation voltage: 1000 V conforming to IEC 60947-4-1; 1500 V conforming to VDE 0110 group C

control circuit voltage limits: Operational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coil; Drop-out: 0.3...0.5 Uc AC 40...400 Hz with LX1/LX9 coil; Operational: 0.85...1.1 Uc DC with LX4 coil; Drop-out: 0.2...0.35 Uc DC with LX4 coil; Operational: 85...275 V AC 50/60 Hz with LXE coil; Drop-out: 0...60 V AC 50/60 Hz with LXE coil; Operational: 85...418 V DC with LXE coil; Drop-out: 0...45 V DC with LXE coil

power dissipation per pole: 65 W AC-1

heat dissipation: 14 W; 2.2…5.5 W

operating time: 40...75 ms closing for with LX1/LX9 coil; 100...170 ms opening for with LX1/LX9 coil; 50...60 ms closing for with LX4 coil; 45...60 ms opening for with LX4 coil; 40...80 ms closing for with LXE coil; 6...54 ms opening for with LXE coil

mounting support: Plate

standards: JIS C8201-4-1; IEC 60947-4-1; IEC 60947-1; EN 60947-4-1; EN 60947-1

product certifications: CB; ABS; DNV; RMRoS; LROS (Lloyds register of shipping); BV; RINA; UL; CSA; UKCA

connections - terminals: Power circuit: bar 2 cable(s) - busbar cross section: 30 x 5 mm; Power circuit: lugs-ring terminals 2 cable(s) 150 mm²; Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end; Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible with cable end; Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end; Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end; Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²; Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²; Control circuit: screw clamp terminals 1.0 cable(s) 0.2…2.5 mm²flexible without cable end; Control circuit: screw clamp terminals 1.0 cable(s) 0.25…2.5 mm²flexible with cable end; Control circuit: screw clamp terminals 1.0 cable(s) 0.2…2.5 mm²solid without cable end

tightening torque: Power circuit: 35 N.m; Control circuit: 1.2 N.m; Control circuit: 0.6 N.m

mechanical durability: 10 Mcycles

inrush power in VA: 1000…1150 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil; 920…1140 VA (at 20 °C)with LX4 coil; 360…470 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil; 410…450 VA (at 20 °C)with LXE coil

hold-in power consumption in VA: 12…18 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil; 4…7.5 VA (at 20 °C)with LX4 coil; 4.5…7.0 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil; 2.5…4.0 VA (at 20 °C)with LXE coil

maximum operating rate: 2400 cyc/h 55 °C

compatibility code: LC1F

Environment

IP degree of protection: IP20 front face with shrouds conforming to IEC 60529; IP20 front face with shrouds conforming to VDE 0106

protective treatment: TH

ambient air temperature for operation: -5…55 °C

ambient air temperature for storage: -60…80 °C

permissible ambient air temperature around the device: -40…70 °C

operating altitude: 3000 m without derating

mechanical robustness: Vibrations contactor open: 1.5 Gn, 5...300 Hz; Vibrations contactor closed: 5 Gn, 5...300 Hz; Shocks contactor open: 6 Gn for 1/2 sine wave (11 ms); Shocks contactor closed: 15 Gn for 1/2 sine wave (11 ms)

height: 206 mm

width: 213 mm

depth: 219 mm

net weight: 8 kg

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Free of Substances of Very High Concern above the threshold

EU RoHS Directive: Compliant

Mercury free: Yes

RoHS exemption information: Yes

China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure: ENVPEP1505009EN

Circularity Profile: ENVEOLI1505009EN

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins