Schneider-Electric
TM221CE40T
Tariff code: 8537109199
Link to the manufacturers site: TM221CE40T - controller M221 40 IO transistor PNP Ethernet
Main
Range of product: Modicon M221
Product or component type: Logic controller
[Us] rated supply voltage: 24 V DC
Discrete input number: 24, discrete input 4 fast input conforming to IEC 61131-2 Type 1
Analogue input number: 2 at 0...10 V
Discrete output type: Transistor
Discrete output number: 16 transistor 2 fast output
Discrete output voltage: 24 V DC
Discrete output current: 0.5 A
Complementary
Discrete I/O number: 40
Maximum number of I/O expansion module: 7 (local I/O-Architecture); 14 (remote I/O-Architecture)
Supply voltage limits: 20.4…28.8 V
Inrush current: 35 A
Maximum power consumption in W: 17 W at 24 V (with max number of I/O expansion module); 4.9 W at 24 V (without I/O expansion module)
Power supply output current: 0.52 A 5 V for expansion bus; 0.3 A 24 V for expansion bus
Discrete input logic: Sink or source (positive/negative)
Discrete input voltage: 24 V
Discrete input voltage type: DC
Analogue input resolution: 10 bits
LSB value: 10 mV
Conversion time: 1 ms per channel + 1 controller cycle time for analogue input analog input
Permitted overload on inputs: +/- 30 V DC for 5 min (maximum) for analog input; +/- 13 V DC (permanent) for analog input
Voltage state 1 guaranteed: >= 15 V for input
Voltage state 0 guaranteed: <= 5 V for input
Discrete input current: 7 mA for discrete input; 5 mA for fast input
Input impedance: 3.4 kOhm for discrete input; 100 kOhm for analog input; 4.9 kOhm for fast input
Response time: 35 µs turn-off, I2...I5 terminal(s) for input; 5 µs turn-on, I0, I1, I6, I7 terminal(s) for fast input; 35 µs turn-on, other terminals terminal(s) for input; 5 µs turn-off, I0, I1, I6, I7 terminal(s) for fast input; 100 µs turn-off, other terminals terminal(s) for input; 5 µs turn-on, turn-off, Q0...Q1 terminal(s) for output; 50 µs turn-on, turn-off, Q2...Q3 terminal(s) for output; 300 µs turn-on, turn-off, other terminals terminal(s) for output
Configurable filtering time: 0 ms for input; 3 ms for input; 12 ms for input
Discrete output logic: Positive logic (source)
Maximum current per output common: 4 A
Output frequency: 100 kHz for fast output (PWM/PLS mode) at Q0...Q1; 5 kHz for output at Q2...Q3; 0.1 kHz for output at Q4...Q15
Absolute accuracy error: +/- 1 % of full scale for analog input
Maximum leakage current: 0.1 mA for transistor output
Maximum voltage drop: <1 V
Mechanical durability: 20000000 cycles for transistor output
Maximum tungsten load: <12 W for output and fast output
Protection type: Overload and short-circuit protection at 1 A
Reset time: 1 s automatic reset
Memory capacity: 256 kB for user application and data RAM with 10000 instructions; 256 kB for internal variables RAM
Data backed up: 256 kB built-in flash memory for backup of application and data
Data storage equipment: 2 GB SD card (optional)
Battery type: BR2032 or CR2032X lithium non-rechargeable
Backup time: 1 year at 25 °C (by interruption of power supply)
Execution time for 1 KInstruction: 0.3 ms for event and periodic task
Execution time per instruction: 0.2 µs Boolean
Exct time for event task: 60 µs response time
Maximum size of object areas: 512 %KW constant words; 255 %TM timers; 255 %C counters; 8000 %MW memory words; 512 %M memory bits
Realtime clock: With
Clock drift: <= 30 s/month at 25 °C
Regulation loop: Adjustable PID regulator up to 14 simultaneous loops
Positioning functions: Position PTO 2 axe(s)pulse/direction mode (100 kHz); Position PTO 1 axe(s)CW/CCW mode (100 kHz)
Function available: PWM; PLS; Frequency generator
Counting input number: 4 fast input (HSC mode) at 100 kHz 32 bits
Control signal type: A/B; Pulse/direction; Single phase
Integrated connection type: USB port with mini B USB 2.0 connector; Non isolated serial link serial 1 with RJ45 connector and RS232/RS485 interface ; Ethernet with RJ45 connector
Supply: (serial)serial link supply: 5 V, <200 mA
Transmission rate: 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485; 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232; 480 Mbit/s for USB
Communication port protocol: USB port: USB - SoMachine-Network; Non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network; Ethernet
Port Ethernet: 10BASE-T/100BASE-TX 1 port with 100 m copper cable
Communication service: Modbus TCP slave device; Ethernet/IP adapter; Modbus TCP server; Modbus TCP client; DHCP client
Local signalling: 1 LED (green) for PWR; 1 LED (green) for RUN; 1 LED (red) for module error (ERR); 1 LED (green) for SD card access (SD); 1 LED (red) for BAT; 1 LED per channel (green) for I/O state; 1 LED (green) for SL; Ethernet network activity (green) for ACT; Ethernet network link (yellow) for Link (Link Status)
Electrical connection: removable screw terminal block for inputs; removable screw terminal block for outputs; terminal block, 3 terminal(s) for connecting the 24 V DC power supply; connector, 4 terminal(s) for analogue inputs; Mini B USB 2.0 connector for a programming terminal
Maximum cable distance between devices: Shielded cable: <10 m for fast input; Unshielded cable: <30 m for output; Unshielded cable: <30 m for digital input; Unshielded cable: <1 m for analog input; Shielded cable: <3 m for fast output
Insulation: Between input and internal logic at 500 V AC; Between fast input and internal logic at 500 V AC; Non-insulated between inputs; Between output and internal logic at 500 V AC; Non-insulated between analogue input and internal logic; Non-insulated between analogue inputs
Marking: CE
Mounting support: Top hat type TH35-15 rail conforming to IEC 60715; Top hat type TH35-7.5 rail conforming to IEC 60715; plate or panel with fixing kit
Height: 90 mm
Depth: 70 mm
Width: 160 mm
Net weight: 0.456 kg
Environment
Standards: IEC 61131-2; UL 508; CAN/CSA C22.2 No. 213; IACS E10; ANSI/ISA 12-12-01
Product certifications: RCM; EAC; ABS; LR; cULus; DNV-GL; CE; UKCA; cULus HazLoc
Environmental characteristic: Ordinary and hazardous location
Resistance to electrostatic discharge: 8 kV in air conforming to IEC 61000-4-2; 4 kV on contact conforming to IEC 61000-4-2
Resistance to electromagnetic fields: 10 V/m 80 MHz...1 GHz conforming to IEC 61000-4-3; 3 V/m 1.4 GHz...2 GHz conforming to IEC 61000-4-3; 1 V/m 2...2.7 GHz conforming to IEC 61000-4-3
Resistance to magnetic fields: 30 A/m 50/60 Hz conforming to IEC 61000-4-8
Resistance to fast transients: 2 kV (power lines) conforming to IEC 61000-4-4; 2 kV (relay output) conforming to IEC 61000-4-4; 1 kV (I/O) conforming to IEC 61000-4-4; 1 kV (Ethernet line) conforming to IEC 61000-4-4; 1 kV (serial link) conforming to IEC 61000-4-4
Surge withstand: 2 kV power lines (AC) common mode conforming to IEC 61000-4-5; 2 kV relay output common mode conforming to IEC 61000-4-5; 1 kV I/O common mode conforming to IEC 61000-4-5; 1 kV shielded cable common mode conforming to IEC 61000-4-5; 0.5 kV power lines (DC) differential mode conforming to IEC 61000-4-5; 1 kV power lines (AC) differential mode conforming to IEC 61000-4-5; 1 kV relay output differential mode conforming to IEC 61000-4-5; 0.5 kV power lines (DC) common mode conforming to IEC 61000-4-5
Resistance to conducted disturbances: 10 V 0.15...80 MHz conforming to IEC 61000-4-6; 3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL); 10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
Electromagnetic emission: Conducted emissions - test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines (AC)) at 0.15…0.5 MHz conforming to IEC 55011; Conducted emissions - test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines (AC)) at 0.5…300 MHz conforming to IEC 55011; Conducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10…150 kHz conforming to IEC 55011; Conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz conforming to IEC 55011; Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to IEC 55011; Conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150…1500 kHz conforming to IEC 55011; Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 200…1000 MHz conforming to IEC 55011
Immunity to microbreaks: 10 ms
Ambient air temperature for operation: -10…55 °C (horizontal installation); -10…35 °C (vertical installation)
Ambient air temperature for storage: -25…70 °C
Relative humidity: 10…95 %, without condensation (in operation); 10…95 %, without condensation (in storage)
IP degree of protection: IP20 with protective cover in place
Pollution degree: <= 2
Operating altitude: 0...2000 m
Storage altitude: 0…3000 m
Vibration resistance: 3.5 mm at 5…8.4 Hz on symmetrical rail; 3.5 mm at 5…8.4 Hz on panel mounting; 1 gn at 8.4…150 Hz on symmetrical rail; 1 gn at 8.4…150 Hz on panel mounting
Shock resistance: 147 m/s² for 11 ms
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 11.139 cm
Package 1 Width: 14.201 cm
Package 1 Length: 21.045 cm
Package 1 Weight: 760.0 g
Unit Type of Package 2: CAR
Number of Units in Package 2: 12
Package 2 Height: 29.3 cm
Package 2 Width: 39.2 cm
Package 2 Length: 56.9 cm
Package 2 Weight: 10.211 kg
Unit Type of Package 3: P12
Number of Units in Package 3: 144
Package 3 Height: 105.0 cm
Package 3 Width: 120.0 cm
Package 3 Length: 80.0 cm
Package 3 Weight: 132 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free: Yes
China RoHS Regulation: X
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP1403012EN
Circularity Profile: ENVEOLI1403012EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
© 2018 Alplan Kft.