Skip to main content

Schneider-Electric
RM35TF30

multifunction phase control relay RM35-T - range 194..528 V AC
Net discounted price 157.00 EUR
Available when ordered (delivery time: 22 working day(s))
Barcode: 3389119405263
Tariff code: 8536490099

Link to the manufacturers site: RM35TF30 - multifunction phase control relay RM35-T - range 194..528 V AC

Main

Range of produc: Harmony Control Relays

Relay type: Multifunction control relay

Product or component type: 3-phase control relay

Product specific application: For 3-phase supply

Relay name: RM35TF

Relay monitored parameters: Undervoltage and overvoltage in window mode; Phase sequence; Phase failure detection; Asymmetry

Time delay type: Adjustable 0.1...10 s, +/- 10 % of the full scale value

Switching capacity in VA: 1250 VA

Measurement range: 220...480 V voltage AC

Contacts type and composition: 2 C/O

Connections - terminals: Screw connectors

[Uc] control circuit voltage: 220...480 V

[In] rated current: 5 A

Complementary

Reset time: 1500 ms at 480 V

Maximum switching voltage: 250 V AC; 250 V DC

Minimum switching current: 10 mA at 5 V DC

Maximum switching current: 5 A AC; 5 A DC

Supply voltage limits: 194…528 V AC, 3 phases

Control circuit voltage limits: - 12 % + 10 % Un

Power consumption in VA: 0…22 VA at 400 V AC 50 Hz

Voltage detection threshold: < 194 V

control circuit frequency: 50...60 Hz +/- 10 %

Output contacts: 2 C/O

Nominal output current: 5 A

Measurement voltage limits: 176…528 V AC

Hysteresis: 2 %

run-up delay at power-up: 650 ms

Maximum measuring cycle: 140 ms measurement cycle as true rms value

Threshold adjustment voltage: 2...20 % of Un selected; -12...-2 % in the range 220 V AC; +2...+10 % in the range 480 V AC

Voltage range: 220...480 V phase to phase

Adjustment of asymmetry threshold: 5...15 % of Un selected

Repeat accuracy: 0.3 % for time delay; 0.5 % for input and measurement circuit

Measurement error: < 1 % over the whole range with voltage variation; 0.05 %/°C with temperature variation

Response time: < 200 ms (in the event of a fault)

Marking: CE

Overvoltage category: III conforming to IEC 60664-1

Insulation resistance: > 500 MOhm at 500 V DC conforming to IEC 60255-5; > 500 MOhm at 500 V DC conforming to IEC 60664-1

[Ui] rated insulation voltage: 400 V conforming to IEC 60664-1

Supply frequency: 50/60 Hz +/- 10 %

Operating position: Any position without derating

Connections - terminals: Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end; Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end; Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end; Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end

Tightening torque: 0.6…1 N.m conforming to IEC 60947-1

Housing material: Self-extinguishing plastic

Local signalling: LED (green) for power ON; LED (yellow) for relay ON; LED (yellow) for fault

Mounting support: 35 mm symmetrical DIN rail conforming to IEC 60715

Electrical durability: 100000 cycles

Mechanical durability: 30000000 cycles

Operating rate: <= 360 operations/hour full load

Utilisation category: AC-12 conforming to IEC 60947-5-1; AC-13 conforming to IEC 60947-5-1; AC-14 conforming to IEC 60947-5-1; AC-15 conforming to IEC 60947-5-1; DC-12 conforming to IEC 60947-5-1; DC-13 conforming to IEC 60947-5-1

Safety reliability data: MTTFd = 399.5 years; B10d = 360000

Width: 35 mm

Net weight: 0.13 kg

Compatibility code: RM3

Environment

Electromagnetic compatibility: Emission standard for industrial environments conforming to IEC 61000-6-4; Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3; Immunity for industrial environments conforming to IEC 61000-6-2

Standards: IEC 60255-1

product certifications: GL; UL; CSA; GOST; C-Tick

Directives: 89/336/EEC - electromagnetic compatibility; 73/23/EEC - low voltage directive

Ambient air temperature for storage: -40…70 °C

Ambient air temperature for operation: -20…50 °C

Relative humidity: 95 % at 55 °C conforming to IEC 60068-2-30

Vibration resistance: 0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6; 1 gn (f= 57.6…150 Hz) conforming to IEC 60255-21-1

Shock resistance: 15 gn for 11 ms conforming to IEC 60255-21-1

IP degree of protection: IP20 (terminals) conforming to IEC 60529; IP30 (casing) conforming to IEC 60529

Pollution degree: 3 conforming to IEC 60664-1

Dielectric test voltage: 2 kV, 1 min AC 50 Hz

Non-dissipating shock wave: 4 kV

Packing Units

Unit Type of Package 1: PCE

Number of Units in Package 1: 1

Package 1 Height: 4.800 cm

Package 1 Width: 7.800 cm

Package 1 Length: 9.700 cm

Package 1 Weight: 133.000 g

Unit Type of Package 2: S03

Number of Units in Package 2: 48

Package 2 Height: 30.000 cm

Package 2 Width: 30.000 cm

Package 2 Length: 40.000 cm

Package 2 Weight: 7.070 kg

Unit Type of Package 3: P06

Number of Units in Package 3: 384

Package 3 Height: 75.000 cm

Package 3 Width: 60.000 cm

Package 3 Length: 80.000 cm

Package 3 Weight: 64.124 kg

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)

Mercury free: Yes

China RoHS Regulation: X

RoHS exemption information: Yes

Environmental Disclosure: ENVPEP1504008EN

Circularity Profile: ENVEOLI1504008EN