Schneider-Electric
LUCMT1BL
Tariff code: 8537109899
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: LUCMT1BL - multifunction control unit LUCM - class 5...30 - 0.35...1.05A - 24 V DC
Main
Range: TeSys
Range of product: TeSys Ultra
Device short name: LUCM
Product or component type: Multifunction control unit
Device application: Motor control; Motor protection
Product specific application: Most sophisticated control and protection requirements, with display
Function available: Overload, no-load running; Protection against phase failure and phase imbalance; Protection against overload and short-circuit; Manual or automatic reset; Earth fault protection; Log function; Differentiation of thermal overload and magnetic fault; Protection function alarm; Monitoring function, indication of main motor parameters
Product compatibility: Power base LUTM
Network frequency: 40...60 Hz
Load type: 3-phase motor - cooling: self-cooled - setting factory setting; 3-phase motor - cooling: self-cooled, force cooled - setting settable; Single-phase motor - cooling: self-cooled, force cooled - setting settable
Utilisation category: AC-41; AC-44; AC-43
Thermal protection adjustment range: 0.35…1.05 A
Thermal overload class: Class 5…30 - frequency limit: 50…60 Hz - temperature compensation: -25…55 °C conforming to IEC 60947-6-2; Class 5…30 - frequency limit: 50…60 Hz - temperature compensation: -25…55 °C conforming to UL 508
Tripping threshold: 14.2 x Ir +/- 20 %
Phase failure sensitivity: Yes
[Uc] control circuit voltage: 24 V DC
Complementary
Control circuit voltage limits: 20...28 V for DC circuit 24 V in operation; 14.5 V for DC circuit 24 V drop-out
Typical current consumption: 130 mA at 24 V DC I maximum while closing; 60 mA at 24 V DC I rms sealed
Heat dissipation: 2 W for control circuit
Operating time: 35 ms opening for control circuit; 70 ms closing for control circuit
Physical interface: RS485 multidrop - connector(s): RJ45 - location: front panel - communication protocol: Modbus RTU 19200 bit/s
Return time: <= 200 ms
Messages display capacity: 2 lines of 12 characters - display LCD - English - accuracy +/- 5 % - resolution 1 % of Ir; 2 lines of 12 characters - display LCD - French - accuracy +/- 5 % - resolution 1 % of Ir; 2 lines of 12 characters - display LCD - German - accuracy +/- 5 % - resolution 1 % of Ir; 2 lines of 12 characters - display LCD - Italian - accuracy +/- 5 % - resolution 1 % of Ir; 2 lines of 12 characters - display LCD - Spanish - accuracy +/- 5 % - resolution 1 % of Ir
Reset: Automatic reset - setting: setting range; Manual - setting: factory setting; Manual - setting: setting range; Remote reset - setting: setting range
Time before reset: 1…1000 s - reset manual or automatic reset - setting settable; 120 s - reset manual - setting factory setting
User language: English - setting factory setting; English, French, German, Italian, Spanish - setting settable
Information displayed: Average current (factory setting); Average current (settable); Cause of last 5 faults (settable); Current in phase (settable); Earth leakage current (settable); Phase imbalance (settable); Thermal state of motor (settable)
Standards: EN 60947-6-2; IEC 60947-6-2; UL 508; CSA C22.2 No 14
Product certifications: UL; CSA
[Ui] rated insulation voltage: 250 V conforming to IEC 60947-6-2; 250 V conforming to UL 60947-4-1; 250 V conforming to CSA C22.2 No 60947-4-1
[Uimp] rated impulse withstand voltage: 4 kV conforming to IEC 60947-6-2
Fixing mode: Plug-in (front face)
Width: 45 mm
Height: 66 mm
Depth: 60 mm
Net weight: 0.175 kg
Compatibility code: LUCM
Environment
IP degree of protection: IP20 front panel and wired terminals conforming to IEC 60947-1; IP20 other faces conforming to IEC 60947-1; IP40 front panel outside connection zone conforming to IEC 60947-1
Protective treatment: TH conforming to IEC 60068
Ambient air temperature for operation: -25…60 °C
Ambient air temperature for storage: -40…85 °C
Operating altitude: 2000 m
Fire resistance: 960 °C parts supporting live components conforming to IEC 60695-2-12; 650 °C conforming to IEC 60695-2-12
Shock resistance: 10 gn power poles open conforming to IEC 60068-2-27; 15 gn power poles closed conforming to IEC 60068-2-27
Vibration resistance: 2 gn, 5…300 Hz, power poles open conforming to IEC 60068-2-6; 4 gn, 5…300 Hz, power poles closed conforming to IEC 60068-2-6
Resistance to electrostatic discharge: 8 kV level 3 in open air conforming to IEC 61000-4-2; 8 kV level 4 on contact conforming to IEC 61000-4-2
Resistance to radiated fields: 10 V/m 3 conforming to IEC 61000-4-3
Resistance to fast transients: 2 kV class 3 serial link conforming to IEC 61000-4-4; 4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4
Immunity to radioelectric fields: 10 V conforming to IEC 61000-4-6
Immunity to microbreaks: 3 ms
Immunity to voltage dips: 70 % / 500 ms conforming to IEC 61000-4-11
Packing Units
Unit Type of Package 1: Db
Number of Units in Package 1: 1
Package 1 Height: 5.5 cm
Package 1 Width: 8.0 cm
Package 1 Length: 10.2 cm
Package 1 Weight: 171.9 g
Unit Type of Package 2: S02
Number of Units in Package 2: 23
Package 2 Height: 15.0 cm
Package 2 Width: 30.0 cm
Package 2 Length: 40.0 cm
Package 2 Weight: 4.276 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Compliant
Mercury free: Yes
China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP080204EN
Circularity Profile: ENVEOLI100414
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
PVC free: Yes
Halogen content performance: Halogen free plastic parts product
© 2018 Alplan Kft.