Schneider-Electric
LP2K12013BD
Tariff code:
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: LP2K12013BD - TeSys K reversing contactor - 3P - AC-3 <= 440 V 20 A - 1 NC - 24 V DC coil
Main
range of product: TeSys K
range: TeSys
product name: TeSys K
product or component type: Reversing contactor
device short name: LP2K
device application: Control
contactor application: Resistive load; Motor control
utilisation category: AC-1; AC-3; AC-4
device presentation: Preassembled with reversing power busbar
poles description: 3P
pole contact composition: 3 NO
[Ue] rated operational voltage: Power circuit: 690 V AC 50/60 Hz; Signalling circuit: <= 690 V AC 50/60 Hz
[Ie] rated operational current: 20 A (at <50 °C) at <= 440 V AC AC-1 for power circuit; 16 A (at <70 °C) at 690 V AC AC-1 for power circuit; 12 A at <= 440 V AC AC-3 for power circuit
motor power kW: 4 kW at 480 V AC 50/60 Hz; 4 kW at 500...600 V AC 50/60 Hz; 4 kW at 660...690 V AC 50/60 Hz; 3 kW at 220...230 V AC 50/60 Hz; 5.5 kW at 380...415 V AC 50/60 Hz; 5.5 kW at 440 V AC 50/60 Hz
control circuit type: DC standard
[Uc] control circuit voltage: 24 V DC
auxiliary contact composition: 1 NC
[Uimp] rated impulse withstand voltage: 8 kV
overvoltage category: III
[Ith] conventional free air thermal current: 20 A (at 50 °C) for power circuit; 10 A (at 50 °C) for signalling circuit
Irms rated making capacity: 110 A AC for signalling circuit conforming to IEC 60947; 144 A AC for power circuit conforming to NF C 63-110; 144 A AC for power circuit conforming to IEC 60947
rated breaking capacity: 110 A at 440 V conforming to IEC 60947; 80 A at 500 V conforming to IEC 60947; 70 A at 660...690 V conforming to IEC 60947
[Icw] rated short-time withstand current: 115 A 50 °C - 1 s for power circuit; 105 A 50 °C - 5 s for power circuit; 100 A 50 °C - 10 s for power circuit; 75 A 50 °C - 30 s for power circuit; 55 A 50 °C - 1 min for power circuit; 50 A 50 °C - 3 min for power circuit; 80 A - 1 s for signalling circuit; 90 A - 500 ms for signalling circuit; 110 A - 100 ms for signalling circuit; 25 A 50 °C - >= 15 min for power circuit
associated fuse rating: 25 A gG at <= 440 V for power circuit; 25 A aM for power circuit; 10 A gG for signalling circuit conforming to IEC 60947; 10 A gG for signalling circuit conforming to VDE 0660
average impedance: 3 mOhm - Ith 20 A 50 Hz for power circuit
[Ui] rated insulation voltage: Power circuit: 600 V conforming to UL 508; Power circuit: 690 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V conforming to UL 508; Power circuit: 600 V conforming to CSA C22.2 No 14; Signalling circuit: 600 V conforming to CSA C22.2 No 14
electrical durability: 0.3 Mcycles 20 A AC-1 at Ue <= 440 V; 1.3 Mcycles 12 A AC-3 at Ue <= 440 V
interlocking type: Mechanical
mounting support: Plate; Rail
standards: VDE 0660; IEC 60947; BS 5424; NF C 63-110
product certifications: UL; CSA
connections - terminals: Spring terminals 1 cable(s) 0.75…1.5 mm²solid; Spring terminals 1 cable(s) 0.75…1.5 mm²flexible without cable end
operating time: 30...40 ms coil energisation and NO closing; 10 ms coil de-energisation and NO opening
safety reliability level: B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
mechanical durability: 5 Mcycles
maximum operating rate: 3600 cyc/h
Complementary
control circuit voltage limits: Operational: 0.8...1.15 Uc (at <50 °C); Drop-out: 0.1...0.75 Uc (at <50 °C)
inrush power in W: 3 W (at 20 °C)
hold-in power consumption in W: 3 W at 20 °C
heat dissipation: 3 W
auxiliary contacts type: type instantaneous 1 NC
minimum switching current: 5 mA for signalling circuit
minimum switching voltage: 17 V for signalling circuit
non overlap distance: 0.5 mm
insulation resistance: > 10 MOhm for signalling circuit
compatibility code: LP2K
Environment
IP degree of protection: IP20 conforming to VDE 0106
protective treatment: TC conforming to IEC 60068; TC conforming to DIN 50016
ambient air temperature for operation: -25…50 °C
ambient air temperature for storage: -50…80 °C
operating altitude: 2000 m without derating
flame retardance: V1 conforming to UL 94; Requirement 2 conforming to NF F 16-101; Requirement 2 conforming to NF F 16-102
mechanical robustness: Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27; Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6; Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6; Shocks contactor opened, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor opened, on Y axis: 6 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor closed, on X axis: 15 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor closed, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
height: 58 mm
width: 90 mm
depth: 57 mm
net weight: 0.48 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh free of SVHC: Yes
EU RoHS Directive: Compliant
Toxic heavy metal free: Yes
Mercury free: Yes
RoHS exemption information: Yes
China RoHS Regulation: Pro-active China RoHS declaration (out of China RoHS legal scope)
Environmental Disclosure: ENVPEP1503003EN
Circularity Profile: ENVEOLI1503003EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins