Schneider-Electric
LC1K12004Q7
Tariff code:
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: LC1K12004Q7 - TeSys K contactor - 4P (4 NO) - AC-1 <= 440 V 20 A - 380...400 V AC coil
Main
range of product: TeSys K
range: TeSys
product or component type: Contactor
product name: TeSys K
device application: Control
contactor application: Resistive load
Complementary
utilisation category: AC-1
poles description: 4P
pole contact composition: 4 NO
[Ie] rated operational current: 20 A (at <50 °C) at <= 440 V AC AC-1 for power circuit; 16 A (at <70 °C) at 690 V AC AC-1 for power circuit
control circuit type: AC at 50/60 Hz
[Uc] control circuit voltage: 380...400 V AC 50/60 Hz
overvoltage category: III
[Ith] conventional free air thermal current: 20 A (at 50 °C) for power circuit
Irms rated making capacity: 144 A AC for power circuit conforming to NF C 63-110; 144 A AC for power circuit conforming to IEC 60947
rated breaking capacity: 110 A at 440 V conforming to IEC 60947; 80 A at 500 V conforming to IEC 60947; 70 A at 660...690 V conforming to IEC 60947
associated fuse rating: 25 A gG at <= 440 V for power circuit; 25 A aM for power circuit
average impedance: 3 mOhm - Ith 20 A 50 Hz for power circuit
inrush power in VA: 30 VA (at 20 °C)
hold-in power consumption in VA: 4.5 VA (at 20 °C)
heat dissipation: 1.3 W
control circuit voltage limits: Operational: 0.8...1.15 Uc (at <50 °C); Drop-out: 0.2...0.75 Uc (at <50 °C)
maximum operating rate: 3600 cyc/h
signalling circuit frequency: <= 400 Hz
operating time: 10...20 ms coil de-energisation and NO opening; 10...20 ms coil energisation and NO closing
safety reliability level: B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
mechanical robustness: Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27; Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6; Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
compatibility code: LC1K
Environment
product certifications: CSA; UL
protective treatment: TC conforming to IEC 60068; TC conforming to DIN 50016
operating altitude: 2000 m without derating
flame retardance: V1 conforming to UL 94; Requirement 2 conforming to NF F 16-101; Requirement 2 conforming to NF F 16-102
Offer Sustainability
Sustainable offer status: Green Premium product
REACh free of SVHC: Yes
EU RoHS Directive: Compliant
Toxic heavy metal free: Yes
Mercury free: Yes
RoHS exemption information: Yes
China RoHS Regulation: Pro-active China RoHS declaration (out of China RoHS legal scope)
Environmental Disclosure: ENVPEP1503003EN
Circularity Profile: ENVEOLI1503003EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
© 2018 Alplan Kft.