Schneider-Electric
LC1K09008B7
Tariff code: 8536419089
Link to the manufacturers site: LC1K09008B7 - TeSys K contactor - 4P (2 NO + 2 NC) - AC-1 <= 440 V 20 A - 24 V AC coil
Main
Range of produc: TeSys K
Range: TeSys
Product or component type: Contactor
Device short name: LC1K
Device application: Control
contactor application: Resistive load
Complementary
utilisation category: AC-1
Poles description: 4P
Pole contact composition: 2 NO + 2 NC
[Ue] rated operational voltage: Power circuit: <= 690 V AC <= 400 Hz; Signalling circuit: <= 690 V AC <= 400 Hz
[Ie] rated operational current: 20 A (at <60 °C) at <= 690 V AC AC-1 for power circuit
Control circuit type: AC at 50/60 Hz
[Uc] control circuit voltage: 24 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage: 8 kV
Overvoltage category: III
[Ith] conventional free air thermal current: 20 A (at 60 °C) for power circuit; 10 A (at 50 °C) for signalling circuit
Irms rated making capacity: 110 A AC for power circuit conforming to IEC 60947
Rated breaking capacity: 110 A at 220...230 V conforming to IEC 60947; 110 A at 380...400 V conforming to IEC 60947; 110 A at 415 V conforming to IEC 60947; 110 A at 440 V conforming to IEC 60947; 80 A at 500 V conforming to IEC 60947; 70 A at 660...690 V conforming to IEC 60947
[Icw] rated short-time withstand current: 90 A 50 °C - 1 s for power circuit; 85 A 50 °C - 5 s for power circuit; 80 A 50 °C - 10 s for power circuit; 60 A 50 °C - 30 s for power circuit; 45 A 50 °C - 1 min for power circuit; 40 A 50 °C - 3 min for power circuit; 20 A 50 °C - >= 15 min for power circuit
Associated fuse rating: 25 A gG at <= 440 V for power circuit; 25 A aM for power circuit
Average impedance: 3 mOhm - Ith 20 A 50 Hz for power circuit
[Ui] rated insulation voltage: Power circuit: 600 V conforming to UL 508; Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V conforming to CSA C22.2 No 14
Inrush power in VA: 30 VA (at 20 °C)
Hold-in power consumption in VA: 4.5 VA (at 20 °C)
Heat dissipation: 1.3 W
Control circuit voltage limits: Operational: 0.8...1.15 Uc (at <50 °C); Drop-out: >= 0.20 Uc (at <50 °C)
Connections - terminals: Screw clamp terminals 1 cable(s) 1.5…4 mm²solid; Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 1.5…4 mm²solid; Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end
Maximum operating rate: 3600 cyc/h
Signalling circuit frequency: <= 400 Hz
mounting support: Plate; Rail
Tightening torque: 0.8…1.3 N.m - on screw clamp terminals Philips No 2; 0.8…1.3 N.m - on screw clamp terminals flat Ø 6 mm; 0.8…1.3 N.m - on screw clamp terminals pozidriv No 2
Operating time: 10...20 ms coil de-energisation and NO opening; 10...20 ms coil energisation and NO closing; 15...25 ms coil de-energisation and NC closing; 5...15 ms coil energisation and NC opening
Safety reliability level: B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability: 10 Mcycles
Electrical durability: 0.16 Mcycles 20 A AC-1 at Ue <= 690 V
Mechanical robustness: Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27; Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6; Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
height: 58 mm
Width: 45 mm
Depth: 57 mm
Net weight: 0.18 kg
Compatibility code: LC1K
Environment
Standards: EN/IEC 60947-4-1; GB/T 14048.4; UL 60947-4-1; CSA C22.2 No 60947-4-1; JIS C8201-4-1
product certifications: CB Scheme; CCC; UL; CSA; EAC; CE; UKCA
IP degree of protection: IP2X conforming to VDE 0106
Protective treatment: TC conforming to IEC 60068; TC conforming to DIN 50016
Ambient air temperature for storage: -50…80 °C
Operating altitude: 2000 m without derating
Flame retardance: V1 conforming to UL 94; Requirement 2 conforming to NF F 16-101; Requirement 2 conforming to NF F 16-102
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 4.800 cm
Package 1 Width: 6.200 cm
Package 1 Length: 6.500 cm
Package 1 Weight: 179.100 g
Unit Type of Package 2: S02
Number of Units in Package 2: 50
Package 2 Height: 15.000 cm
Package 2 Width: 30.000 cm
Package 2 Length: 40.000 cm
Package 2 Weight: 9.215 kg
Unit Type of Package 3: P06
Number of Units in Package 3: 800
Package 3 Height: 75.000 cm
Package 3 Width: 80.000 cm
Package 3 Length: 60.000 cm
Package 3 Weight: 155.440 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Free of Substances of Very High Concern above the threshold
REACh free of SVHC: Yes
EU RoHS Directive: Compliant
Toxic heavy metal free: Yes
Mercury free: Yes
China RoHS Regulation: Pro-active China RoHS declaration (out of China RoHS legal scope)
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP1503003EN
Circularity Profile: ENVEOLI1503003EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
© 2018 Alplan Kft.