Schneider-Electric
LC1F630M7
Tariff code: 8536490099
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: LC1F630M7 - TeSys F contactor - 3P (3 NO) - AC-3 - <= 440 V 630 A - coil 220 V AC
Main
range: TeSys
range of product: TeSys F
product or component type: Contactor
device short name: LC1F
contactor application: Resistive load; Motor control
utilisation category: AC-3; AC-1; AC-4
poles description: 3P
[Ue] rated operational voltage: <= 1000 V AC 50/60 Hz; <= 460 V DC
[Uc] control circuit voltage: 220 V AC 40...400 Hz
[Ie] rated operational current: 1000 A (at <40 °C) at <= 440 V AC AC-1; 630 A (at <55 °C) at <= 440 V AC AC-3
Complementary
[Uimp] rated impulse withstand voltage: 8 kV
[Ith] conventional free air thermal current: 1000 A (at 40 °C); 1250 A
rated breaking capacity: 5040 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current: 5050 A 40 °C - 10 s; 4400 A 40 °C - 30 s; 3400 A 40 °C - 1 min; 2200 A 40 °C - 3 min; 1600 A 40 °C - 10 min
associated fuse rating: 1000 A gG at <= 440 V; 630 A aM at <= 440 V
average impedance: 0.12 mOhm - Ith 1000 A 50 Hz
[Ui] rated insulation voltage: 1000 V conforming to IEC 60947-4-1; 1500 V conforming to VDE 0110 group C
power dissipation per pole: 120 W AC-1; 48 W AC-3
overvoltage category: III
pole contact composition: 3 NO
motor power kW: 335 kW at 380...400 V AC 50/60 Hz (AC-3); 375 kW at 415 V AC 50/60 Hz (AC-3); 400 kW at 440 V AC 50/60 Hz (AC-3); 400 kW at 500 V AC 50/60 Hz (AC-3); 450 kW at 660...690 V AC 50/60 Hz (AC-3); 450 kW at 1000 V AC 50/60 Hz (AC-3); 200 kW at 220...230 V AC 50/60 Hz (AC-3); 100 kW at 400 V AC 50/60 Hz (AC-4)
control circuit voltage limits: Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C); Drop-out: 0.25...0.5 Uc 40...400 Hz (at 55 °C)
mechanical durability: 5 Mcycles
inrush power in VA: 1650 VA, 40...400 Hz cos phi 0.9 (at 20 °C)
hold-in power consumption in VA: 22 VA, 40...400 Hz cos phi 0.9 (at 20 °C)
maximum operating rate: 1200 cyc/h 55 °C
operating time: 40...80 ms closing; 100...200 ms opening
connections - terminals: Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end; Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end; Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end; Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end; Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end; Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end; Power circuit: bar 2 cable(s) - busbar cross section: 60 x 5 mm; Power circuit: bolted connection
tightening torque: Control circuit: 1.2 N.m; Power circuit: 58 N.m
mounting support: Plate
heat dissipation: 20 W
power range: 250…500 kW at 380…440 V 3 phases; 110…220 kW at 200…240 V 3 phases; 250…500 kW at 480…500 V 3 phases
motor starter type: Direct on-line contactor
contactor coil voltage: 220 V AC standard
standards: EN 60947-1; IEC 60947-4-1; JIS C8201-4-1; IEC 60947-1; EN 60947-4-1
product certifications: LROS (Lloyds register of shipping); CB; UL; RMRoS; CSA; ABS; BV; DNV; RINA; UKCA
compatibility code: LC1F
control circuit type: AC at 40...400 Hz
Environment
IP degree of protection: IP20 front face with shrouds conforming to IEC 60529; IP20 front face with shrouds conforming to VDE 0106
protective treatment: TH
ambient air temperature for operation: -5…55 °C
ambient air temperature for storage: -60…80 °C
permissible ambient air temperature around the device: -40…70 °C
height: 304 mm
width: 309 mm
depth: 255 mm
operating altitude: 3000 m without derating
net weight: 18.6 kg
Packing Units
Number of Units in Package 1: 1
Number of Units in Package 2: 4
Package 1 Height: 29.46 cm
Package 1 Length: 46.99 cm
Package 1 Weight: 18.78 kg
Package 1 Width: 36.83 cm
Package 2 Height: 80 cm
Package 2 Length: 60 cm
Package 2 Weight: 82.232 kg
Package 2 Width: 80 cm
Unit Type of Package 1: PCE
Unit Type of Package 2: P06
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Compliant
Mercury free: Yes
RoHS exemption information: Yes
China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure: ENVPEP1505009EN
Circularity Profile: ENVEOLI1505009EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
© 2018 Alplan Kft.