Skip to main content

Schneider-Electric
GS2V3

TeSys GS - switch-disconnector-fuse - 3 P - 1250A - DIN 4
Net discounted price 1,959.94 EUR
Available when ordered (delivery time: 8 working day(s))
Barcode: 3389119410762
Tariff code: 8536508090

Link to the manufacturers site: GS2V3 - TeSys GS - switch-disconnector-fuse - 3 P - 1250A - DIN 4

Main

Range: TeSys

Product name: TeSys GS

Device short name: GS2V

Product or component type: Switch-disconnector-fuse

Poles description: 3P

Protected poles description: 3t

Contacts type and composition: 3 NO

[Ith] conventional free air thermal current: 1250 A (at 40 °C)

[Ie] rated operational current: 1000 A at 440 V 2 poles in series per phase DC-23A; 1000 A at 440 V 2 poles in series per phase DC-23B; 630 A at 690 V AC-23A; 630 A at 690 V AC-23B; 1000 A at 440 V AC-23A; 1000 A at 440 V AC-23B; 800 A at 500 V AC-23A; 800 A at 500 V AC-23B

Fuse type: DIN

Fuse size: 4

Network type: AC; DC

Network frequency: 50/60 Hz

Complementary

Type of operating handle: Direct frontal; External right side; External frontal

mounting support: Plate

[Ui] rated insulation voltage: 1000 V AC 50/60 Hz

[Uimp] rated impulse withstand voltage: 12 kV

Rated operational power in W: 400 kW at 690 V; 475 kW at 690 V; 560 kW at 400 V; 560 kW at 500 V

Breaking capacity: 110 W

Making capacity: 10000 A at 400 V AC-23B

Breaking capacity: 8000 A at 400 V (AC-23B)

Short-circuit withstand: 90 kA

Mechanical durability: 5000 cycles

Electrical durability: 100 cycles DC-23A; 100 cycles DC-23B; 500 cycles AC-23A; 500 cycles AC-23B

Connections - terminals: Power circuit: bars80 mm²; Power circuit: lugs-ring terminals 4 cable(s) 185 mm²

[Icm] rated short-circuit making capacity: 100 kA at 400 V with protection by gG fuses

Compatibility code: GS2V

Tightening torque: Power circuit: 44 N.m

Environment

Standards: IEC 60947-3

product certifications: CE

IP degree of protection: IP20 conforming to IEC 60529 (with terminal cover)

ambient air temperature for operation: -20…70 °C

Ambient air temperature for storage: -40…80 °C

Fire resistance: 850 °C fuse cover conforming to IEC 60695-2-1; 960 °C body conforming to IEC 60695-2-1

height: 355 mm

Width: 442 mm

Depth: 289 mm

Net weight: 25 kg

Packing Units

Unit Type of Package 1: PCE

Number of Units in Package 1: 1

Package 1 Height: 51.000 cm

Package 1 Width: 60.000 cm

Package 1 Length: 80.000 cm

Package 1 Weight: 40.960 kg

Offer Sustainability

REACh Regulation: Free of Substances of Very High Concern above the threshold

REACh free of SVHC: Yes

EU RoHS Directive: Compliant

Toxic heavy metal free: Yes

Mercury free: Yes

China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information

RoHS exemption information: Yes