Skip to main content

Schneider-Electric
GS2S4

TeSys GS - switch-disconnector-fuse - 4 P - 630A - DIN 3
Barcode: 3389119410861
Tariff code:

This product is discontinued.

Please contact us for possible replacement product options.

Link to the manufacturers site: GS2S4 - TeSys GS - switch-disconnector-fuse - 4 P - 630A - DIN 3

Main

range: TeSys

product name: TeSys GS

device short name: GS2S

product or component type: Switch-disconnector-fuse

poles description: 4P

protected poles description: 4t

contacts type and composition: 4 NO

[Ith] conventional free air thermal current: 630 A (at 40 °C)

[Ie] rated operational current: 400 A at 440 V 2 poles in series per phase with terminal covers DC-23A; 630 A at 440 V 2 poles in series per phase with terminal covers DC-23B; 315 A at 690 V AC-23A; 400 A at 690 V AC-23B; 500 A at 500 V AC-23A; 500 A at 500 V AC-23B; 630 A at 400 V AC-23A; 630 A at 400 V AC-23B

fuse type: DIN

fuse size: 3

network type: AC; DC

network frequency: 50/60 Hz

Complementary

type of operating handle: External right side; Direct frontal; External frontal

mounting support: Plate

[Ui] rated insulation voltage: 1000 V AC 50/60 Hz

[Uimp] rated impulse withstand voltage: 12 kV

rated operational power in W: 295 kW at 690 V; 355 kW at 400 V; 355 kW at 500 V; 400 kW at 690 V

making capacity: 6300 A at 400 V AC-23B

[Icm] rated short-circuit making capacity: 100 kA at 400 V with protection by gG fuses

breaking capacity: 5040 A at 400 V (AC-23B)

short-circuit withstand: 70 kA

mechanical durability: 8000 cycles

electrical durability: 1000 cycles AC-23A; 1000 cycles AC-23B; 200 cycles DC-23A; 200 cycles DC-23B

connections - terminals: Power circuit: bars63 mm²; Power circuit: lugs-ring terminals 2 cable(s) 150 mm²; Power circuit: lugs-ring terminals 2 cable(s) 300 mm²

tightening torque: Power circuit: 44 N.m

compatibility code: GS2S

Environment

standards: IEC 60947-3

product certifications: CE

IP degree of protection: IP20 conforming to IEC 60529 (with terminal cover)

ambient air temperature for operation: -20…70 °C

ambient air temperature for storage: -40…80 °C

fire resistance: 850 °C fuse cover conforming to IEC 60695-2-1; 960 °C body conforming to IEC 60695-2-1

height: 300 mm

width: 458 mm

depth: 250 mm

net weight: 20 kg

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Free of Substances of Very High Concern above the threshold

REACh free of SVHC: Yes

EU RoHS Directive: Compliant

Toxic heavy metal free: Yes

Mercury free: Yes

RoHS exemption information: Yes

China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure: ENVPEP2003010EN

Circularity Profile: ENVEOLI2003010EN

© 2018 Alplan Kft.