Schneider-Electric
XPSECPE5130P
Tariff code: 8536490099
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: XPSECPE5130P - SAFETY EXTENSION MODULE, 24V AC/DC, CONT
Main
range of product: Preventa Safety automation
product or component type: Preventa safety module
safety module name: XPSECPE
safety module application: Increasing the number of safety contacts
function of module: Increasing the number of safety contacts
safety level: Can reach PL e/category 4 can reach the maximum safety level of module base conforming to EN/ISO 13849-1; Can reach SILCL 3 can reach the maximum safety level of module base conforming to EN/IEC 62061
safety reliability data: MTTFd > 100 years conforming to EN/ISO 13849-1; DC = 0...99 % conforming to EN/ISO 13849-1; PFHd = 2.47E-8 1/h conforming to EN/IEC 62061
output type: Relay, 8 NO circuit(s), volt-free
[Us] rated supply voltage: 24 V AC - 15...10 %; 24 V DC - 15...10 %
number of additional circuits: 2 NC + 1 solid state output
Complementary
supply frequency: 50/60 Hz
power consumption in VA: 4 VA
input protection type: Internal, electronic
breaking capacity: 360 VA holding AC-15 B300 relay output; 3600 VA inrush AC-15 B300 relay output
breaking capacity: 3 A at 24 V (DC-13) time constant: 50 ms for relay output; 20 mA at 24 V for solid state output circuit
output thermal current: 6 A per relay for relay output
[Ith] conventional free air thermal current: 24 A for relay output
associated fuse rating: 6 A gG for relay output conforming to EN/IEC 60947-5-1, DIN VDE 0660 part 200
minimum output current: 10 mA for relay output
minimum output voltage: 5 V for relay output
maximum response time on input open: 10 ms
[Ui] rated insulation voltage: 300 V (pollution degree 2) conforming to EN/IEC 60947-5-1, DIN VDE 0110 parts 1 & 2
[Uimp] rated impulse withstand voltage: 4 kV overvoltage category III conforming to EN/IEC 60947-5-1, DIN VDE 0110 parts 1 & 2
local signalling: 3 LEDs
connections - terminals: Captive screw clamp terminals, 1 x 0.2...1 x 2.5 mm² solid without cable end; Captive screw clamp terminals, 1 x 0.2...1 x 2.5 mm² flexible without cable end; Captive screw clamp terminals, 1 x 0.25...1 x 2.5 mm² flexible with cable end, without bezel; Captive screw clamp terminals, 1 x 0.25...1 x 1.5 mm² flexible with cable end, with bezel; Captive screw clamp terminals, 2 x 0.2...2 x 1 mm² solid without cable end; Captive screw clamp terminals, 2 x 0.2...2 x 1 mm² flexible without cable end; Captive screw clamp terminals, 2 x 0.25...2 x 1 mm² flexible with cable end, without bezel; Captive screw clamp terminals, 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel
mounting support: 35 mm symmetrical DIN rail
net weight: 0.55 kg
Environment
standards: EN/IEC 60204-1; EN/IEC 60947-5-1
product certifications: CSA; UL; CCC
IP degree of protection: IP20 (terminals) conforming to EN/IEC 60529; IP40 (enclosure) conforming to EN/IEC 60529
ambient air temperature for operation: -25…55 °C
ambient air temperature for storage: -25…70 °C