Skip to main content

Schneider-Electric
TSXSCY11601

RS485 communication module - 2 twisted shielded pairs cable - 32 devices
Barcode: 3595862054034
Tariff code:

This product is discontinued.

Please contact us for possible replacement product options.

Link to the manufacturers site: TSXSCY11601 - RS485 communication module - 2 twisted shielded pairs cable - 32 devices

Main

range of product: Modicon Premium Automation platform

product or component type: Communication module

software designation: Unity Pro

structure type: Heterogeneous industrial bus

Complementary

product compatibility: Premium; Atrium

method of access: Master/slave type

integrated connection type: 1 serial link: 1 SUB-D 25 connector

communication port protocol: Modbus

communication port support: RS485 isolated

mode of transmission: Asynchronous in baseband

transmission frame: RTU/ASCII; Character mode; Uni-Telway

transmission rate: 1.2...19.2 kbit/s

transmission support medium: 2 twisted shielded pairs cable

number of devices: 32

number of addresses: 0…247

bus length: 0…1300 m character mode; 0…1300 m Modbus; 0…1300 m Uni-Telway

maximum tap links length: 15 m

requests: 120 words per request; 1920 bits per request

control parameter: One CRC 16 on each frame

monitoring function: Diagnostic counters; Event counters

modbus funtions available: Event connection Modbus master 0C; Event connection Modbus slave 0C; Event counter Modbus master 0B; Event counter Modbus slave 0B; Identification Modbus slave 11; Slave identification Modbus master 11; Write n output bits Modbus slave 0F; Write n output words Modbus slave 10; Diagnostic Modbus master 08; Diagnostic Modbus slave 08; Exceptional read status Modbus master 07; Exceptional read status Modbus slave 07; Read bits Modbus master 01; Read input bits Modbus master 02; Read input bits Modbus master 04; Read n input bits Modbus slave 02; Read n input words Modbus slave 04; Read n output bits Modbus slave 01; Read n output words Modbus slave 03; Read words Modbus master 03; Write 1 bits or n bits Modbus master 05; Write 1 input word Modbus slave 06; Write 1 output bit Modbus slave 05; Write 1 word or n word Modbus master 06

local signalling: 1 LED for communication (CH0); 1 LED for internal fault, module failure (ERR); 1 LED for module operating (RUN)

current consumption: 350 mA at 5 V DC

module format: Standard

net weight: 0.34 kg

Environment

ambient air temperature for operation: 0…60 °C

ambient air temperature for storage: -25…70 °C

relative humidity: 5…95 % without condensation

operating altitude: <= 2000 m

© 2018 Alplan Kft.