PM3255 power meter - 2 digital I - 2 digital O - RS485
Net discounted price 509.13 EUR
Available when ordered (delivery time: 35 working day(s))
Barcode: 3606480481611
Tariff code: 9028309000

Link to the manufacturers site: METSEPM3255 - PM3255 power meter - 2 digital I - 2 digital O - RS485

Main

Range: PowerLogic

Product name: PowerLogic PM3000

Device short name: PM3255

product or component type: Power meter

Market segment: Buildings small building cost management: billing: sub feeder; Buildings medium building cost management: billing: sub feeder; Buildings large building cost management: billing: sub feeder; Buildings multi-site cost management: billing: sub feeder; Data center cost management: billing: sub feeder; Healthcare cost management: billing: sub feeder; Industry cost management: billing: sub feeder; Buildings small building cost management: cost allocation: sub feeder; Buildings medium building cost management: cost allocation: sub feeder; Buildings large building cost management: cost allocation: sub feeder; Buildings multi-site cost management: cost allocation: sub feeder; Data center cost management: cost allocation: sub feeder; Healthcare cost management: cost allocation: sub feeder; Industry cost management: cost allocation: sub feeder

Complementary

Power quality analysis: up to the 15th harmonic

device application: Multi-tariff; Power monitoring; Sub billing

Type of measurement: Active and reactive power; Apparent power; Current; Voltage; Energy; Power factor; Frequency; Total current harmonic distortion THD (I); Total voltage harmonic distortion THD (U)

[Us] rated supply voltage: 100...277 V AC 45...65 Hz; 173...480 V AC 45...65 Hz; 100...300 V DC

Network frequency: 60 Hz; 50 Hz

[In] rated current: 5 A; 1 A

Poles description: 3P; 3P + N; 1P + N

Power consumption in VA: 5 VA

Display type: Backlit LCD

Display resolution: 128 x 96 pixels

Sampling rate: 32 samples/cycle

Measurement current: 0.02…1.2 A; 0.05…6 A

Analogue input type: Current 0...5 A; Current 0...1 A

Measurement voltage: 50…330 V AC 45...65 Hz direct; 50…330 V AC 45...65 Hz phase to neutral; 80…570 V AC 45...65 Hz direct; 80…570 V AC 45...65 Hz phase to phase; 570…999000 V AC 45...65 Hz with external VT

Frequency measurement range: 45…65 Hz

Number of inputs: 2 digital 0...4 mA 11...40 V DC

Measurement accuracy: Current 0.3 % 0.5...6 A; Current 0.5 % 0.1...1.2 A; Voltage 0.3 % 50...330 V; Voltage 0.3 % 80...570 V

Accuracy class: Class 0.5S active energy conforming to IEC 62053-22; Class 1 active energy conforming to IEC 62053-21; Class 2 reactive energy conforming to IEC 62053-23; Class C active energy conforming to EN 50470-3

Number of outputs: 2 digital (static)

Information displayed: Tariff (4)

Communication port protocol: Modbus at 9.6...38.4 kbauds

Communication port support: RS485

Data recording: Energy consumption logs; 15 alarms; Power logs; Time stamping; Min/max of instantaneous values

Memory capacity: 512 KB

Mounting mode: Clip-on

Mounting support: DIN rail

Standards: BS EN 61557-12; IEC 61557-12; EN 61557-12; BS EN 61326-1; IEC 61326-1; EN 61326-1; BS EN 62052-11; IEC 62052-11; EN 62052-11; BS EN 62053-21; IEC 62053-21; EN 62053-21; BS EN 62053-22; IEC 62053-22; EN 62052-22; BS EN 62053-23; IEC 62053-23; EN 62052-23; BS EN 61010-1; EN 61010-1; IEC 61010-1; UL 61010-1; BS EN 61010-2-30; IEC 61010-2-30; EN 61010-2-30; UL 61010-2-30; ANSI C12.20

Product certifications: CE conforming to IEC 61010-1 (safety); CE conforming to EN 61557-12 (power monitor); CE conforming to EN/IEC 61326-1 (EMC); UKCA conforming to BS EN 61010-1 (safety); UKCA conforming to BS EN 61557-12 (power monitor); UKCA conforming to BS EN 61326-1 (EMC); CULus conforming to EN 61010-1 (safety); CULus conforming to UL 61010-1 (safety); EAC (sub-meter); RCM

Width: 90 mm

Depth: 70 mm

Height: 95 mm

Net weight: 0.26 kg

Market segment: Small commercial; Residential

Environment

Electromagnetic compatibility: Electrostatic discharge level 4 conforming to IEC 61000-4-2; Susceptibility to electromagnetic fields level 3 conforming to IEC 61000-4-3; Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4; Surge immunity test level 4 conforming to IEC 61000-4-5; Conducted RF disturbances level 3 conforming to IEC 61000-4-6; Magnetic field at power frequency - test level: 0.5 mT conforming to IEC 61000-4-8; Conducted and radiated emissions class B conforming to EN 55022

Overvoltage category: III

IP degree of protection: IP40 front panel: conforming to IEC 60529; IP20 body: conforming to IEC 60529

Relative humidity: 5…95 % at 50 °C

Pollution degree: 2

Ambient air temperature for operation: -25…70 °C

Ambient air temperature for storage: -40…85 °C

Operating altitude: < 3000 m

Compatibility code: PM3255

Packing Units

Unit Type of Package 1: PCE

Number of Units in Package 1: 1

Package 1 Height: 13.5 cm

Package 1 Width: 13.5 cm

Package 1 Length: 9.0 cm

Package 1 Weight: 410.0 g

Unit Type of Package 2: S03

Number of Units in Package 2: 16

Package 2 Height: 30.0 cm

Package 2 Width: 30.0 cm

Package 2 Length: 40.0 cm

Package 2 Weight: 7.036 kg

Unit Type of Package 3: P12

Number of Units in Package 3: 384

Package 3 Height: 95.0 cm

Package 3 Width: 80.0 cm

Package 3 Length: 120.0 cm

Package 3 Weight: 177.864 kg

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive: Compliant with Exemptions

Mercury free: Yes

China RoHS Regulation: X

RoHS exemption information: Yes

Environmental Disclosure: ENVPEP111275EN

Circularity Profile: ENVEOLI111258EN

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins