Schneider-Electric
LV540352
Tariff code:
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: LV540352 - circuit breaker EasyPact Vigi CVS400N, 50 kA at 415 VAC, 400 A rating TM-D trip unit, MB Vigi module, 4P 4d
Main
range: EasyPact
range of product: EasyPact CVS400...630
product name: EasyPact CVS
product or component type: Earth leakage circuit breaker
device short name: Vigi CVS400N
device application: Distribution
poles description: 4P
protected poles description: 4D
neutral position: Left
earth-leakage protection: With
[In] rated current: 400 A at 40 °C
breaking capacity code: N
network type: AC
breaking capacity: 70 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
utilisation category: Category A
trip unit name: TM-D
trip unit technology: Thermal-magnetic
trip unit rating: 400 A at 40 °C
protection type: Short-circuit protection (magnetic); Overload protection (thermal)
earth-leakage add-on module name: MB
Complementary
network frequency: 50/60 Hz
control type: Toggle
mounting mode: Fixed
mounting support: Backplate
upside connection: Front
downside connection: Front
connections - terminals: Screw connection
[Uimp] rated impulse withstand voltage: 8 kV conforming to EN/IEC 60947-2
thermal protection adjustment range: 280…400 A
[Ics] rated service breaking capacity: 70 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 32 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
mechanical durability: 15000 cycles
electrical durability: 6000 cycles 415 V In conforming to IEC 60947-2
connection pitch: 45 mm
contact position indicator: Yes
neutral protection setting: 1 x Ir (4d)
long time pick-up adjustment type Ir: Adjustable
long time pick-up adjustment range: 0.7...1 x In
long time delay adjustment type: Fixed
instantaneous pick-up adjustment type Ii: Adjustable
instantaneous pick-up adjustment range: 5...10 x In
earth-leakage protection class: Class A
residual earth-leakage sensitity adjustment type: Adjustable 5 settings
[IΔn] residual earth-leakage sensitive adjustment: 0.3 A; 1 A; 3 A; 10 A; 30 A
residual earth-leakage time delay adjustment type: Adjustable 4 settings
[Δt] residual earth-leakage time delay adjustment: 0 ms 40 ms; 60 ms 140 ms; 150 ms 300 ms; 310 ms 800 ms
height: 355 mm
width: 185 mm
depth: 110 mm
net weight: 6.3 kg
compatibility code: CVS400
Environment
electrical shock protection class: Class II
standards: IEC 60947-2; EN 60947-2
product certifications: GOST; IEC
IP degree of protection: IP40
pollution degree: 3 conforming to IEC 60664-1
ambient air temperature for operation: -25…70 °C
ambient air temperature for storage: -50…85 °C
Offer Sustainability
REACh Regulation: Free of Substances of Very High Concern above the threshold
EU RoHS Directive: Compliant
Mercury free: Yes
RoHS exemption information: Yes
China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information
PVC free: Yes
© 2018 Alplan Kft.