Skip to main content

Schneider-Electric
LV480405

switch-disconnector fuse, Fupact INFD63, 3 poles, DIN (000), 63 A, front control
Barcode: 3606480343438
Tariff code:

This product is discontinued.

There is a replacement product available.

Link to the manufacturers site: LV480405 - switch-disconnector fuse, Fupact INFD63, 3 poles, DIN (000), 63 A, front control

Main

range of product: INF63

range: FuPact

product name: Fupact INF

device short name: INFD63

product or component type: Switch-disconnector-fuse

device application: Protection

poles description: 3P

protected poles description: 3f

fuse type: DIN

fuse size: NH000

network type: DC; AC

network frequency: 50/60 Hz

Complementary

control type: Without handle

rotary handle mounting location: Front

rotary handle mounting style: Extended; Direct

provision for padlocking: Padlockable

mounting mode: Vertical - horizontal

mounting support: DIN rail, with specific accessories; Mounting plate

[Ie] rated operational current: AC-22A: 63 A AC 50/60 Hz 220/240 V; AC-22A: 63 A AC 50/60 Hz 380/415 V; AC-22A: 63 A AC 50/60 Hz 440/480 V; AC-22A: 63 A AC 50/60 Hz 500/525 V; AC-22A: 63 A AC 50/60 Hz 660/690 V; AC-23A: 63 A AC 50/60 Hz 220/240 V; AC-23A: 63 A AC 50/60 Hz 380/415 V; AC-23A: 63 A AC 50/60 Hz 440/480 V; AC-23A: 63 A AC 50/60 Hz 500/525 V; DC-21B: 50 A DC 440 V 4 poles in series; AC-23A: 63 A AC 50/60 Hz 660/690 V; DC-22B: 63 A DC 220 V 2 poles in series; DC-23B: 63 A DC 220 V 2 poles in series

[Ith] conventional free air thermal current: 63 A ( 40 °C ) vertical; 45 A ( 70 °C ) horizontal; 48 A ( 65 °C ) horizontal; 45 A ( 70 °C ) vertical; 51 A ( 60 °C ) horizontal; 48 A ( 65 °C ) vertical; 53 A ( 55 °C ) horizontal; 51 A ( 60 °C ) vertical; 56 A ( 50 °C ) horizontal; 53 A ( 55 °C ) vertical; 56 A ( 50 °C ) vertical; 58 A ( 45 °C ) horizontal; 61 A ( 40 °C ) horizontal; 58 A ( 45 °C ) vertical; 63 A ( 35 °C ) horizontal

[Ithe] conventional enclosed thermal current: 63 A at 40 °C, Power dissipation per fuse: 7.5 W (300 mm x 350 mm x 200 mm)

maximum power: 30 kW at 380/400 V AC 50/60 Hz; 30 kW at 415 V AC 50/60 Hz; 37 kW at 500/525 V AC 50/60 Hz; 60 kW at 660/690 V AC 50/60 Hz; 18.5 kW at 220/240 V AC 50/60 Hz

rated duty: Uninterrupted

intermittent duty class: Class 120 - 60 %

[Ui] rated insulation voltage: 1000 V AC 50/60 Hz; 1000 V DC

[Uimp] rated impulse withstand voltage: 12 kV

[Ue] rated operational voltage: 250 V DC; 690 V AC 50/60 Hz; 690 V AC 50/60 Hz AC-20; 690 V DC DC-20

[Im] rated making and breaking capacity: Icm 105 kA at 690 V conforming to DIN (with fuse); Icm 13 kA at 690 V (without fuse); Icm 17 kA at 415 V (without fuse); Icm 17 kA at 500 V (without fuse); Icm 176 kA at 415 V conforming to BS (with fuse); Icm 220 kA at 500 V conforming to DIN (with fuse); Icn 100 kA at 500 V conforming to DIN (with fuse); Icn 50 kA at 690 V conforming to DIN (with fuse); Icn 80 kA at 415 V conforming to BS (with fuse)

suitability for isolation: Yes

contact position indicator: Yes

visible break: No

contact operation: Double-break

Environment

mechanical durability: 10000 cycles

electrical durability: AC-22A: 1500 cycles 500 V AC 50/60 Hz; AC-22A: 1500 cycles 690 V AC 50/60 Hz; AC-23A: 1500 cycles 500 V AC 50/60 Hz; AC-23A: 1500 cycles 690 V AC 50/60 Hz

[Icw] rated short-time withstand current: 0.46 kA for 30 s; 0.56 kA for 20 s; 1.44 kA for 3 s; 2.5 kA for 1 s

design: Horizontal design

connections terminals: Screw clamp terminals

connections - terminals: Screw clamp terminals 63 A 2.5…25 mm² flexible; Screw clamp terminals 63 A 2.5…25 mm² rigid

tightening torque: 2 N.m for terminal

height: 100 mm

width: 114.5 mm

depth: 120.5 mm

standards: EN/IEC 60269-4; EN/IEC 60947-1; EN/IEC 60947-3; EN/IEC 60947-5; EN/IEC 60269-1

product certifications: CCC

IP degree of protection: IP20 conforming to IEC 60529; IP65 conforming to IEC 60529

IK degree of protection: IK07 conforming to EN 50102; IK10 conforming to EN 50102

pollution degree: 3

ambient air temperature for operation: -25…70 °C

ambient air temperature for storage: -50…85 °C

compatibility code: INF63

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Free of Substances of Very High Concern above the threshold

REACh free of SVHC: Yes

EU RoHS Directive: Compliant

Toxic heavy metal free: Yes

Mercury free: Yes

RoHS exemption information: Yes

China RoHS Regulation:  Pro-active China RoHS declaration (out of China RoHS legal scope)

Environmental Disclosure: ENVPEP110102EN

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

PVC free: Yes

© 2018 Alplan Kft.