Schneider-Electric
LV438576
Tariff code:
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: LV438576 - circuit breaker Compact NSX100N - TMD - 40 A - 1 pole 1d
Main
range: ComPact
product name: ComPact NSX
range of product: ComPact NSX100...250; ComPact NSX100...250 DC
device short name: NSX100N
product or component type: Circuit breaker
device application: Distribution
poles description: 1P
protected poles description: 1t
[In] rated current: 40 A at 40 °C
[Ue] rated operational voltage: 250 V DC; 277 V AC 50/60 Hz
network type: DC; AC
network frequency: 50/60 Hz
suitability for isolation: Yes conforming to EN/IEC 60947-2
utilisation category: Category A
breaking capacity: 50 kA Icu at 250 V DC 1P conforming to IEC 60947-2; 50 kA Icu at 125 V DC 1P conforming to IEC 60947-2; 25 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity code: N 25 kA 240 V AC
trip unit name: TM-D
trip unit technology: Thermal-magnetic
control type: Toggle
mounting mode: Fixed
Complementary
[Ui] rated insulation voltage: 750 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage: 8 kV conforming to IEC 60947-2
[Ics] rated service breaking capacity: 50 kA at 250 V DC conforming to IEC 60947-2; 50 kA at 125 V DC conforming to IEC 60947-2; 25 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
mechanical durability: 20000 cycles
electrical durability: 10000 cycles at 277 V In; 20000 cycles at 277 V In/2
mounting support: Backplate
upside connection: Front
downside connection: Front
connection pitch: 35 mm
protection type: for overload protection (thermal); for short-circuit protection (magnetic)
trip unit rating: 40 A at 40 °C
long time pick-up adjustment type Ir: Fixed
long time pick-up adjustment range: 1 In
magnetic tripping current: 500 A
earth-leakage protection: Without
width: 35 mm
height: 161 mm
depth: 86 mm
compatibility code: NSX100
Environment
standards: EN/IEC 60947
product certifications: CCC; EAC; Marine
overvoltage category: Class II
electrical shock protection class: Class II
pollution degree: 3 conforming to IEC 60664-1
IP degree of protection: IP40 conforming to IEC 60529
IK degree of protection: IK07 conforming to IEC 62262
ambient air temperature for operation: -25…70 °C
ambient air temperature for storage: -50…85 °C
relative humidity: 0…95 %
operating altitude: 0...2000 m without derating; 2000 m...5000 m with derating
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Free of Substances of Very High Concern above the threshold
EU RoHS Directive: Compliant
Mercury free: Yes
RoHS exemption information: Yes
China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure: ENVPEP120606EN
Circularity Profile: ENVEOLI120604EN
© 2018 Alplan Kft.